Siemens 3SU1400-1AA10-3BA0 SIRIUS ACT 1 NO Spring-Terminal Contact Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select 1 NO where an actuated closing contact is required.
- Match the front-panel operator and module holder.
- Size the load using its utilization category and voltage.
- Keep prepared finely stranded leads within the 0.75 mm² maximum.
3SU1400-1AA10-3BA0 SIRIUS ACT 1 NO Spring-Terminal Contact Module
A single normally open contact module with spring-loaded terminals for SIRIUS ACT front-plate assemblies.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3SU1400-1AA10-3BA0 |
| Product Type | Contact module |
| Core Function | Operator-actuated circuit switching |
| Application | SIRIUS ACT front-panel controls |
Normally open switching
One NO contact closes the control circuit when the associated operator actuates it.
AC and DC control duties
Use the utilization-category current rating that corresponds to the load and circuit voltage.
Compact spring connection
The 9.8 mm wide module accepts bare or prepared conductors within distinct terminal limits.
Product Overview
3SU1400-1AA10-3BA0 adds one normally open contact to a SIRIUS ACT front-panel operator, using spring-loaded field terminals.
The module fits front-plate arrangements in plastic or metal enclosures and supports AC/DC control circuits with voltage-dependent utilization ratings.
Key Functions
Switch a normally open control path
The single NO element provides an actuated control contact for the selected SIRIUS ACT operator.
Match the electrical switching duty
AC-15 ratings range from 6 A at 24–230 V to 1.4 A at 500 V, while DC-13 ratings depend on the DC circuit voltage.
Wire a modular front-panel assembly
Spring-loaded terminals support the compact module arrangement behind the front plate.
Official Specifications
| Contact configuration | 1 NO; 0 NC |
|---|---|
| Contact material | Silver alloy |
| Connection technology | Spring-loaded terminals |
| Operating voltage range | 5–500 V AC at 50/60 Hz or 5–500 V DC |
| AC-15 rated operational current | 6 A at 24, 48, 110 and 230 V; 3 A at 400 V; 1.4 A at 500 V |
| DC-13 rated operational current | 3 A at 24 V; 1.5 A at 48 V; 0.7 A at 110 V; 0.3 A at 230 V; 0.1 A at 400–500 V |
| Conventional thermal current | 10 A |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 6 kV |
| Pollution degree | 3 |
| Maximum operating frequency | 3600 operations/h |
| Typical mechanical and electrical endurance | 10,000,000 operating cycles |
| Solid and finely stranded bare conductors | 2 × (0.25–1.5 mm²) |
| Finely stranded conductors with end preparation | 2 × (0.25–0.75 mm²) |
| Module protection | Enclosure IP40; terminals IP20 |
| Operating ambient temperature | −25 to +70 °C |
| Storage ambient temperature | −40 to +80 °C |
| Shock and vibration resistance | 15 g for 11 ms half-sine; 5 g over 10–500 Hz |
| Dimensions (W × H × D) | 9.8 × 36 × 27.7 mm |
| Net module weight | 8 g |
Frequently Asked Questions
Can 3SU1400-1AA10-3BA0 provide a normally closed stop contact?
No, this module contains one normally open contact and no normally closed contact.
Can I switch a 230 V AC control load with 3SU1400-1AA10-3BA0?
The AC-15 rated operational current is 6 A at 230 V, so the connected control load must remain within that duty rating.
Is the 10 A thermal rating of 3SU1400-1AA10-3BA0 also its 24 V DC inductive switching rating?
No, its DC-13 rated operational current at 24 V is 3 A, while 10 A is the conventional thermal current.
Which conductor limit applies to prepared flexible leads on 3SU1400-1AA10-3BA0?
Finely stranded conductors with end preparation are limited to 0.25–0.75 mm², compared with 0.25–1.5 mm² for bare solid or finely stranded wires.
Can 3SU1400-1AA10-3BA0 be incorporated into both plastic and metal enclosures?
Yes, the contact module is suitable for integration in either plastic or metal enclosures.
How frequently can I operate 3SU1400-1AA10-3BA0 in a repetitive control application?
The maximum operating frequency is 3600 operations per hour.
Does 3SU1400-1AA10-3BA0 provide positive opening for a safety contact function?
No, the normally open contact module does not provide a positive-opening function.