Overview
SIRIUS 3RV2

3RV2742-5GD10 SIRIUS S3 40 A System-Protection Circuit Breaker

A size S3 system-protection breaker with a 40 A thermal release, 520 A magnetic trip and UL 489 approval.

At a Glance

Brand Siemens
Model 3RV2742-5GD10
Product Type Three-pole circuit breaker
Core Function Interrupting overload and short-circuit currents
Application Industrial system and feeder protection

Interrupt abnormal currents

A 40 A thermal release is combined with a 520 A instantaneous magnetic trip.

Provide isolation functionality

The breaker supports disconnector functionality and is operated by a handle.

Fit industrial feeders

The S3 device uses main-circuit screw terminals and supports screw or 35 mm DIN-rail mounting.

Product Overview

3RV2742-5GD10 protects an AC system circuit using thermal overload and magnetic short-circuit releases.

The three-pole S3 device provides disconnector functionality and a handle indication, with optional auxiliary-switch expansion for control-panel integration.

Ordering focus: Match the 40 A rating and voltage-dependent breaking capacity to the protected system.
Key Functions

Interrupt abnormal currents

A 40 A thermal release is combined with a 520 A instantaneous magnetic trip.

Provide isolation functionality

The breaker supports disconnector functionality and is operated by a handle.

Fit industrial feeders

The S3 device uses main-circuit screw terminals and supports screw or 35 mm DIN-rail mounting.

Official Specifications
Rated Current and Thermal Release 40 A
Main Circuit 3-pole AC circuit; 50–60 Hz
Operating Voltage Range 20–600 V AC
Instantaneous Magnetic Trip 520 A
Icu at 240 and 400 V AC 100 kA
Ics 100 kA at 240 V AC; 50 kA at 400 V AC
UL 489 Breaking Capacity 65 kA at 480Y/277 V AC
Rated Insulation Voltage 1,000 V at pollution degree 3
Impulse Withstand Voltage 8 kV
Power Loss at Rated Current 18 W total; 6 W per pole
Contact Endurance 25,000 mechanical and electrical operating cycles typical
Protection IP20 front; IP00 terminals
Operating and Compensation Range −20 to +60 °C
Storage and Transport Temperature −50 to +80 °C
Required Clearance at 400 V 90 mm above and below; 10 mm at sides
Main Terminal Torque 4.5–6 N·m; 4 mm hexagonal socket
Maximum Installation Altitude 2,000 m
Dimensions (W × H × D) 70 × 170 × 176 mm
Net Weight 2.196 kg
Official source:Siemens product data sheet
Frequently Asked Questions

Is 3RV2742-5GD10 a UL 489 circuit breaker for system protection?

The device is approved as a system-protection circuit breaker to UL 489 and CSA C22.2 No. 5.

At what current does the magnetic release of 3RV2742-5GD10 respond?

The instantaneous short-circuit trip response is 520 A.

Does 3RV2742-5GD10 provide phase-failure or ground-fault detection?

The breaker does not provide phase-failure or ground-fault detection.

Can I add auxiliary status contacts to 3RV2742-5GD10?

Auxiliary-switch expansion is available, while no NO, NC or changeover auxiliary contacts are fitted in the base device.

What breaking capacity should I use for 3RV2742-5GD10 on a 480Y/277 V system?

The UL 489 rated short-circuit breaking capacity at 480Y/277 V AC is 65 kA.

How much free space is needed around 3RV2742-5GD10 at 400 V?

Allow 90 mm above and below and 10 mm at the sides from grounded or live parts.

Are the terminals of 3RV2742-5GD10 protected to the same level as its front?

The front is IP20 and the terminals are IP00.

Compatibility & Ordering Notes
Before ordering 3RV2742-5GD10: Match the 40 A rating and voltage-dependent breaking capacity to the protected system.

Before installation

  • Select the breaker for the actual circuit voltage, 40 A continuous load and available fault current.
  • Use the applicable Icu, Ics or UL 489 breaking capacity for the installation.
  • Maintain the specified clearances and tighten main terminal screws to 4.5–6 N·m.
  • Specify auxiliary switches separately when status signaling is required.
Hot Selling Models
TZ1LE024SEM4AS1
CTSM40L
WKN10/U BL/V0 57.510.0155.6
BMA040MDA0050
Allen-Bradley 140M-D8E-C16
3RT1026-1AL24
NCB40-FP-A2-P1-V1
XE020 71088
000-84060-0000000
13070-250
DBG60B-10 28229150.10.13
3321607
021-1BF00
OG0034 OGT-HB0A
MQDEC-830-12M23RA

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.