Siemens 3RT2015-2BB41 SIRIUS 7A 24VDC Spring Contactor
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the voltage-specific AC-3 or AC-3e rating for the connected motor.
- Reserve 4 W for the DC coil and retain the A1–A2 control connection.
- Allow 6 mm side clearance to grounded or live parts even when adjacent contactors can be mounted side by side.
- Specify external short-circuit protection appropriate to the chosen coordination arrangement.
3RT2015-2BB41 SIRIUS 7A 24VDC Spring Contactor
A size S00 contactor with 7 A AC-3/AC-3e duty at 400 V, a 24 V DC coil, one NO auxiliary contact and spring-loaded terminals.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RT2015-2BB41 |
| Product Type | Compact power contactor |
| Core Function | Three-phase motor load switching |
| Application | Small motor control circuits |
3 kW at 400 V
AC-3 and AC-3e ratings support small motor starter duties.
24 V DC coil
The standard A1–A2 coil consumes 4 W during pickup and holding.
One NO auxiliary
An integrated normally open auxiliary contact serves the control circuit.
Product Overview
3RT2015-2BB41 combines three main NO power contacts and one instantaneous NO auxiliary contact in a compact S00 frame. It is rated 7 A and 3 kW at 400 V for AC-3 and AC-3e motor switching.
Spring-loaded terminals serve the main circuit, auxiliary circuit and coil connections. The 24 V DC coil uses a standard A1–A2 control arrangement, while the compact 45 mm width and 35 mm DIN-rail mounting suit small motor starter panels.
Key Functions
Control small motor feeders
The AC-3 and AC-3e ratings cover 7 A at 400 V and 3 kW motor duty, with voltage-specific current ratings for higher supply voltages.
Provide a control-circuit feedback path
The integrated instantaneous NO auxiliary contact is rated 10 A at 230 V AC-15 or 24 V DC-13.
Connect compact panel wiring
Spring-loaded terminals accept solid conductors up to 4 mm² and fine-stranded conductors up to 2.5 mm².
Official Specifications
| Main and auxiliary contacts | 3 NO main contacts; 1 NO instantaneous auxiliary contact |
|---|---|
| AC-3 and AC-3e current | 7 A at 400 V; 6 A at 500 V; 4.9 A at 690 V |
| AC-3 and AC-3e motor power | 1.5 kW at 230 V; 3 kW at 400 or 500 V; 4 kW at 690 V |
| AC-1 current up to 690 V | 18 A at 40 °C; 16 A at 60 °C |
| Coil supply and operating range | 24 V DC rated; 0.8–1.1 times rated voltage |
| Coil pickup and holding power | 4 W |
| Switching delays at DC | Closing: 30–100 ms; opening: 7–13 ms |
| Auxiliary-contact control duty | 10 A at 230 V AC-15; 10 A at 24 V DC-13 |
| Terminal design | Spring-loaded terminals for main, auxiliary and control circuits |
| Conductor cross-sections | Solid or stranded: 0.5–4 mm²; fine-stranded with or without ferrules: 0.5–2.5 mm² |
| Main and auxiliary insulation ratings | 690 V rated insulation voltage; 6 kV rated impulse withstand |
| Typical mechanical service life | 30 million operations for the contactor without an added auxiliary block |
| Maximum AC-3 and AC-3e switching frequency | 750 operations per hour |
| Mounting and frame | Size S00; screw or 35 mm DIN-rail mounting |
| Required side-by-side clearances | 10 mm in front, above and below; 0 mm at the sides between adjacent contactors |
| Operating and storage temperatures | Operation: −25 to +60 °C; storage: −55 to +80 °C |
| Maximum installation altitude | 2,000 m above sea level |
| Dimensions and net weight | 45 × 70 × 73 mm (W × H × D); 293.8 g |
Frequently Asked Questions
Can 3RT2015-2BB41 operate a 3 kW motor from a 400 V supply?
The AC-3 and AC-3e ratings are 3 kW and 7 A at 400 V.
What DC supply variation can the coil of 3RT2015-2BB41 tolerate?
The coil operates over 0.8 to 1.1 times its rated 24 V DC control supply.
How much coil power should I reserve for 3RT2015-2BB41?
The DC coil requires 4 W during both pickup and holding.
Can the built-in auxiliary contact of 3RT2015-2BB41 switch a 24 V DC control load?
The integrated NO auxiliary contact is rated 10 A at 24 V in DC-13 duty.
What flexible conductor size fits the spring terminals of 3RT2015-2BB41?
Fine-stranded conductors from 0.5 to 2.5 mm² are permitted with or without end processing.
How much time should a sequence allow for 3RT2015-2BB41 to open?
The DC opening delay is 7 to 13 ms, with an arcing time of 10 to 15 ms.
Can I place 3RT2015-2BB41 directly beside another contactor?
Side-by-side mounting permits zero side clearance between contactors while retaining 10 mm clearance in front, above and below.