Siemens 3RB3016-1TB0 SIRIUS 4–16 A Electronic Overload Relay
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a compatible S00 contactor and adjust the response to the motor rated current.
- Choose manual or automatic reset to match the machine restart sequence.
- Select the specified main-circuit fuse for type 1 or type 2 coordination.
- Maintain 6 mm side clearance and the specified screw-terminal torque.
3RB3016-1TB0 SIRIUS 4–16 A Electronic Overload Relay
A Class 10E electronic relay with a 4–16 A adjustment range, screw terminals and selectable manual or automatic reset.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RB3016-1TB0 |
| Product Type | Electronic overload relay |
| Core Function | Monitoring motor overload current |
| Application | Size S00 motor starter protection |
Adjust overload protection
The electronic release uses Class 10E tripping with a 4–16 A current setting.
Coordinate trip and indication
One NC auxiliary contact disconnects the contactor and one NO contact provides tripped indication.
Fit the starter assembly
The S00 relay mounts on a contactor and provides screw connections with removable auxiliary/control terminals.
Product Overview
3RB3016-1TB0 provides three-pole current-dependent overload protection in a compact size S00 starter assembly.
The relay mounts on a compatible contactor and separates the contactor-disconnection signal from the auxiliary indication of a tripped condition.
Key Functions
Adjust overload protection
The electronic release uses Class 10E tripping with a 4–16 A current setting.
Coordinate trip and indication
One NC auxiliary contact disconnects the contactor and one NO contact provides tripped indication.
Fit the starter assembly
The S00 relay mounts on a contactor and provides screw connections with removable auxiliary/control terminals.
Official Specifications
| Current Adjustment | 4–16 A |
|---|---|
| Trip Characteristic | Class 10E electronic release |
| Main Circuit | 3 poles; rated current 16 A |
| Rated Operating Voltage | Up to 690 V AC |
| Rated Frequency | 50–60 Hz |
| Motor Power at 400 and 500 V | 2.2–7.5 kW at 50 Hz |
| Motor Power at 690 V | 3–11 kW at 50 Hz |
| Auxiliary Contacts | 1 NC contactor-disconnection contact and 1 NO tripped-indication contact |
| AC-15 Auxiliary Ratings | 4 A at 24–125 V AC; 3 A at 230 V AC |
| DC-13 Auxiliary Ratings | 2 A at 24 V; 0.55 A at 60 V; 0.3 A at 110–125 V; 0.11 A at 220 V |
| Automatic-Reset Recovery | 3 min typical after an overload trip |
| Main-Circuit Fuse Coordination | Type 1: 50 A gG or 60 A RK5; type 2: 50 A gG or 60 A J |
| Auxiliary-Circuit Fuse | 6 A gG |
| Rated-Current Power Loss | 1.1 W total; 0.37 W per pole |
| Terminal Tightening Torque | 0.8–1.2 N·m for main and auxiliary screws |
| Operating and Compensation Range | −25 to +60 °C |
| Side Clearance | 6 mm from grounded and live parts |
| Front Protection | IP20; finger-safe from the front |
| Dimensions (W × H × D) | 45 × 79 × 73 mm |
| Net Weight | 0.219 kg |
Frequently Asked Questions
Can 3RB3016-1TB0 be set low enough for a motor rated at 3 A?
The minimum current setting is 4 A, so a 3 A motor falls below this relay’s adjustment range.
Can 3RB3016-1TB0 reset automatically after an overload event?
Automatic reset is available with a typical recovery time of three minutes.
How can 3RB3016-1TB0 provide a separate signal that a trip has occurred?
The normally open auxiliary contact is assigned to tripped indication.
What fuse is required for the auxiliary circuit of 3RB3016-1TB0?
The auxiliary switching circuit requires a 6 A gG fuse.
How much side clearance does 3RB3016-1TB0 need near grounded metal?
Keep 6 mm of clearance at the side from grounded or live parts.
Which screwdriver and torque should I use on 3RB3016-1TB0?
Use a Pozidriv PZ 2 screwdriver and tighten the main and auxiliary terminal screws to 0.8–1.2 N·m.
What UL full-load current applies to 3RB3016-1TB0 at 480 V or 600 V?
The specified full-load current for a three-phase AC motor is 16 A at both voltages.