Siemens 3RB3016-1SB0 SIRIUS 3–12 A Electronic Overload Relay
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Set the current response to suit the motor rated current within the 3–12 A range.
- Use a compatible size S00 contactor and the designated contactor-mounting arrangement.
- Choose the specified main-circuit fuse for type 1 or type 2 coordination and protect auxiliary contacts with a 6 A gG fuse.
- Select manual or automatic reset deliberately and allow for the automatic-reset recovery time.
3RB3016-1SB0 SIRIUS 3–12 A Electronic Overload Relay
A Class 10E electronic overload relay with a 3–12 A setting range, contactor mounting and manual or automatic reset.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RB3016-1SB0 |
| Product Type | Electronic overload relay |
| Core Function | Protecting motors against overload |
| Application | Size S00 motor starter assemblies |
Set motor protection
The electronic overload release has a continuously adjustable 3–12 A response range and Class 10E tripping.
Integrate trip signaling
One NC auxiliary contact disconnects the contactor and one NO contact signals the tripped state.
Choose reset behavior
The relay supports manual or automatic reset and has temperature compensation from −25 to +60 °C.
Product Overview
3RB3016-1SB0 provides current-dependent electronic overload protection for a three-phase motor starter.
The size S00 device mounts on a compatible S00 contactor and provides separate contacts for contactor disconnection and tripped indication.
Key Functions
Set motor protection
The electronic overload release has a continuously adjustable 3–12 A response range and Class 10E tripping.
Integrate trip signaling
One NC auxiliary contact disconnects the contactor and one NO contact signals the tripped state.
Choose reset behavior
The relay supports manual or automatic reset and has temperature compensation from −25 to +60 °C.
Official Specifications
| Current Adjustment Range | 3–12 A |
|---|---|
| Trip Class | Class 10E |
| Main Circuit | 3 poles; rated operating current 12 A |
| Rated Operating Voltage | Up to 690 V AC |
| Rated Frequency | 50–60 Hz |
| Motor Power at 400 and 500 V | 1.5–5.5 kW at 50 Hz |
| Motor Power at 690 V | 2.2–7.5 kW at 50 Hz |
| Auxiliary Contacts | 1 NC for contactor disconnection and 1 NO for tripped indication |
| Auxiliary AC-15 Ratings | 4 A at 24–125 V AC; 3 A at 230 V AC |
| Auxiliary DC-13 Ratings | 2 A at 24 V DC; 0.55 A at 60 V DC; 0.3 A at 110–125 V DC; 0.11 A at 220 V DC |
| Automatic-Reset Recovery | 3 min typical after overload tripping |
| Main-Circuit Fuse Coordination | Type 1: 50 A gG or 45 A RK5; type 2: 50 A gG or 45 A J |
| Auxiliary Contact Protection | 6 A gG fuse |
| Power Loss at Rated Current | 0.6 W total; 0.2 W per pole |
| Terminal Arrangement | Screw terminals for main and auxiliary circuits; removable auxiliary/control terminal |
| Terminal Tightening Torque | 0.8–1.2 N·m for main and auxiliary contacts |
| Operating and Compensation Range | −25 to +60 °C |
| Front Protection | IP20; finger-safe from the front |
| Mounting and Dimensions | Contactor mounting, size S00; 45 × 79 × 73 mm |
| Net Weight | 0.213 kg |
Frequently Asked Questions
Will 3RB3016-1SB0 cover a motor with a 9 A rated current?
The adjustable overload response range is 3–12 A.
Which contactor size is appropriate for mounting 3RB3016-1SB0?
The relay is intended for mounting on a size S00 contactor.
Which trip class does 3RB3016-1SB0 use for motor starting?
The electronic overload release uses Class 10E tripping.
Which auxiliary contact on 3RB3016-1SB0 should open the contactor circuit?
Use the normally closed auxiliary contact for contactor disconnection and the normally open contact for tripped indication.
How long is the typical recovery period with automatic reset on 3RB3016-1SB0?
The typical recovery time after an overload trip is three minutes in automatic-reset mode.
Can 3RB3016-1SB0 replace the main-circuit short-circuit protective device?
Separate short-circuit protection is required using the specified fuse and coordination arrangement.
Does the overload setting of 3RB3016-1SB0 remain temperature-compensated in a 50 °C cabinet?
Temperature compensation covers the −25 to +60 °C operating range.