- Set the overload-current response to the motor requirements within the 1.6–7 A adjustment range.
- Provide coordinated feeder short-circuit protection because the starter does not perform that function.
- Apply current derating and maintain the required mounting clearances.
- Validate the complete hardwired safety circuit for the required shutdown function.
3RM1107-1AA04 SIRIUS 3RM1 Fail-Safe Direct Motor Starter
Hybrid direct starter for 0.55–3 kW motors at 400 V, with a 1.6–7 A setting range, 24 V DC control and screw terminals.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RM1107-1AA04 |
| Product Type | Fail-safe direct motor starter |
| Core Function | Motor starting with electronic overload protection and safety-related shutdown |
| Application | Hardwired control of three-phase motors |
Hybrid direct switching
Starts the motor directly through a three-pole hybrid power circuit; reversing operation is not provided.
Electronic motor protection
The overload setting covers 1.6–7 A to match the connected motor current.
Safety-related shutdown
Safety-related switching off opens the load circuit with stop category 0; the complete safety function depends on the configured application.
Product Overview
3RM1107-1AA04 combines direct motor switching, solid-state overload protection and safety-related disconnection in a compact SIRIUS 3RM1 starter.
The hybrid three-pole power circuit is designed for direct starting, while current derating, external short-circuit protection and mounting clearances must be considered in the motor feeder.
Key Functions
Hybrid direct switching
Starts the motor directly through a three-pole hybrid power circuit; reversing operation is not provided.
Electronic motor protection
The overload setting covers 1.6–7 A to match the connected motor current.
Safety-related shutdown
Safety-related switching off opens the load circuit with stop category 0; the complete safety function depends on the configured application.
Official Specifications
| Rated main-circuit voltage | 48–500 V AC |
|---|---|
| Main-circuit frequency | 50 or 60 Hz |
| Adjustable overload-current range | 1.6–7 A |
| Motor power at 400 V, 50 Hz | 0.55–3 kW, three-phase |
| Rated operational current at 400 V | 7 A |
| Current derating by ambient temperature | 7 A at 40 °C; 6.1 A at 50 °C; 5.2 A at 55 °C; 4.6 A at 60 °C |
| Maximum starting current | 56 A |
| Control supply | 24 V DC nominal; permissible range 19.2–30 V DC |
| Control current | 13 mA standby; 57 mA during operation |
| Digital control input | 24 V DC; typical signal-1 current 8 mA |
| Auxiliary contact | 1 changeover contact; maximum 3 A AC-15 at 230 V or 1 A DC-13 at 24 V |
| Safety capability | SIL 3; Category 4 and PL e for the specified safety function |
| Safe state and stop category | Load circuit open; stop category 0 |
| Terminal arrangement | Screw terminals for main and control circuits |
| Maximum unshielded motor cable | 100 m |
| Mounting method | Screw fixing or snap-on mounting to a 35 mm DIN rail |
| Required vertical clearance | 50 mm above and below |
| Operating temperature | −25 to +60 °C with current derating |
| Dimensions (W × H × D) | 22.5 × 100 × 141.6 mm |
| Net weight | 0.275 kg |
Frequently Asked Questions
Can 3RM1107-1AA04 reverse a motor?
This direct starter does not provide reversing operation.
Does 3RM1107-1AA04 replace the feeder short-circuit protective device?
The starter has no short-circuit protection function, so the feeder requires an appropriately selected protective device.
Can 3RM1107-1AA04 carry 7 A continuously at 60 °C?
The operational-current rating falls to 4.6 A at 60 °C.
How much space is required above and below 3RM1107-1AA04?
Maintain 50 mm clearance above and below the starter.
Does fail-safe operation of 3RM1107-1AA04 require PROFIsafe communication?
The starter has no PROFIsafe or bus-communication function and uses its hardwired control circuits.
Which control voltage is required for 3RM1107-1AA04?
Use a nominal 24 V DC control supply within the permitted 19.2–30 V DC range.
What contact is available for external indication on 3RM1107-1AA04?
One auxiliary changeover contact is rated up to 3 A AC-15 at 230 V or 1 A DC-13 at 24 V.