GE Fanuc IC200CHS022E VersaMax Compact Box-Style I/O Carrier
Manufacturer: GE Fanuc
Condition: Brand New
Lead Time: In Stock
Origin: USA
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the installed I/O module and its mechanical keying assignment.
- Use a grounded, conductive 7.5 × 35 mm DIN rail.
- Add panel fixing when maximum vibration and shock resistance is required.
- Use 90 °C-rated copper conductors within the permitted occupancy and wire-size range.
- Apply the recommended terminal torque and remain within the per-point and common-connection current limits.
- Retract the wiring-card holder for system operation.
IC200CHS022E VersaMax Compact Box-Style I/O Carrier
A compact carrier with IEC box-style field terminals, mechanical module keying and integrated carrier-to-carrier backplane connections.
At a Glance
| Brand | GE Fanuc |
|---|---|
| Model | IC200CHS022E |
| Product Type | Compact box-terminal I/O carrier |
| Core Function | Providing field wiring and backplane connections |
| Application | Compatible VersaMax I/O modules |
Compact terminal arrangement
Field wiring supports up to 32 I/O points and four common or power connections.
Vertical module placement
The I/O module mounts perpendicular to the DIN rail.
Mechanical keying
The carrier’s keying dials match the keying on the underside of the selected module.
Product Overview
IC200CHS022E provides the wiring and mounting carrier for a compatible VersaMax I/O module in the compact box-terminal arrangement.
Carrier-to-carrier mating connectors continue the backplane without separate connection cables, while the keying dials, module latch and hinged wiring-card holder support assembly and identification.
Key Functions
Terminate the field circuits locally
The IEC box-terminal arrangement accepts the specified single conductor or paired-conductor wiring for the I/O points and common connections.
Continue the VersaMax backplane
Mating connectors join the neighboring carriers without additional backplane cables or tools.
Secure and identify the installed module
Mechanical keying and the module latch establish the mounting arrangement, and the hinged holder retains the module’s wiring card.
Official Specifications
| I/O-Module Positions | 1 |
|---|---|
| Field-Wiring Capacity | Up to 32 I/O points and 4 common or power connections |
| Field-Terminal Type | IEC box-style terminals |
| Single-Conductor Range | One solid or stranded AWG 14–22 conductor per terminal |
| Two-Conductor Capacity | Two conductors up to AWG 18 per terminal, of the same size and type |
| Specified Copper-Wire Temperature Rating | 90 °C |
| Recommended Terminal Torque | 0.37–0.45 ft·lb |
| Maximum Current per I/O Point | 2 A |
| Maximum Current per Power or Ground Connection | 8 A |
| Maximum Carrier Voltage | 264 V AC |
| Permitted Voltage Transient | Up to 300 V AC without carrier damage |
| DIN-Rail Size | 7.5 × 35 mm |
| I/O-Module Orientation | Perpendicular to the DIN rail |
| Carrier Footprint | 66.8 × 163.5 mm |
Frequently Asked Questions
Does the DIN rail under IC200CHS022E need an electrical ground?
The conductive, unpainted, corrosion-resistant DIN rail must be electrically grounded for EMC protection.
May I put two different wire sizes in one terminal on IC200CHS022E?
Two wires in the same terminal must have the same size and type, with a maximum size of AWG 18.
How is the I/O module oriented on IC200CHS022E?
The module mounts vertically, perpendicular to the DIN rail.
When should I panel-mount IC200CHS022E in addition to using the DIN rail?
Add panel mounting when the application requires maximum resistance to mechanical vibration and shock.
What tightening torque should I use for the box terminals on IC200CHS022E?
The recommended terminal torque is 0.37 to 0.45 ft·lb.
How do I set the module keying on IC200CHS022E?
Set the carrier’s keying dials to match the keys on the underside of the selected I/O module.
Where should the wiring-card holder on IC200CHS022E sit during operation?
Keep the wiring-card holder in its retracted position during system operation.