GE Fanuc IC200CHS022E VersaMax Compact Box-Style I/O Carrier
Manufacturer: GE Fanuc
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: USA
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Match the installed I/O module and its mechanical keying assignment.
- Use a grounded, conductive 7.5 × 35 mm DIN rail.
- Add panel fixing when maximum vibration and shock resistance is required.
- Use 90 °C-rated copper conductors within the permitted occupancy and wire-size range.
- Apply the recommended terminal torque and remain within the per-point and common-connection current limits.
- Retract the wiring-card holder for system operation.
IC200CHS022E VersaMax Compact Box-Style I/O Carrier
A compact carrier with IEC box-style field terminals, mechanical module keying and integrated carrier-to-carrier backplane connections.
Ad Primum Aspectum
| Nota | GE Fanuc |
|---|---|
| Modellum | IC200CHS022E |
| Typus Producti | Compact box-terminal I/O carrier |
| Functio principalis | Providing field wiring and backplane connections |
| Applicatio | Compatible VersaMax I/O modules |
Compact terminal arrangement
Field wiring supports up to 32 I/O points and four common or power connections.
Collocatio moduli verticalis
Modulus I/O in rilum DIN montatur perpendiculariter.
Clavatura mechanica
Dialae clavationis portantis congruunt cum clavatione in parte inferiori moduli electi.
Product Overview
IC200CHS022E praebet vectorem connexionum et fixationis pro modulo VersaMax I/O compatibili in dispositione compacta cistulae-terminalis.
Connnectoria coniunctionis portantis ad portantem continuant planum dorsale sine cavis connexionis separatis, dum dialae clavationis, catenula moduli et sustentaculum cardinis flexibilem adiuvant compositionem et identificationem.
Key Functions
Circuitus in loco terminare
Dispositio cistulae-terminalis secundum normam IEC admittit unicum conductorem specificatum aut conductores copulatos pro punctis I/O et connexionibus communibus.
Planum dorsale VersaMax continuare
Connectoria coniunctionis portantes iungunt proximos portantes sine cavis additis plani dorsalis aut instrumentis.
Securare et identificare modulum installatum
Clavis mechanica et catenula moduli constituunt dispositionem montandi, et supportum articulatum retinet cartam electricam moduli.
Official Specifications
| Positiones Moduli I/O | 1 |
|---|---|
| Capacitas Connexionum in Campo | Usque ad 32 puncta I/O et 4 connexiones communes vel pro energia |
| Typus terminalis campī | Terminalia in forma cistulae secundum normam IEC |
| Intervallo Conductoris Singularis | Unus conductor solidus aut intortus AWG 14–22 per terminalem |
| Capacitas Conductoris Duplis | Duo conductores usque ad AWG 18 per terminalem, eadem magnitudine et specie |
| Temperatura specifika de evaluatio del filo de cuprum | 90 °C |
| Torque recomandatus terminalis | 0.37–0.45 ft·lb |
| Currente maximo per puncto de I/O | 2 A |
| Currente maximo per connexion de potentia o de terra | 8 A |
| Tensione maxima del portator | 264 V AC |
| Transiente de tensione permittite | Usque ad 300 V AC sine damno al portator |
| Dimensione del rail DIN | 7.5 × 35 mm |
| I/O-Modulus Orientatio | Perpendicularis ad raium DIN |
| Imago Supportis | 66.8 × 163.5 mm |
Quaestiones Frequenter Rogatae
Num raius DIN sub IC200CHS022E necessitat terram electricam?
Raius DIN conductivus, inpinguis, et resistens corrosioni debet esse electricus terratus pro protectione EMC.
Num licet duo diversa crassitudinis filorum in uno terminali IC200CHS022E ponere?
Duo fili in eodem terminali debent esse eiusdem crassitudinis et generis, cum maxima crassitudine AWG 18.
Quomodo I/O-modulus orientatur in IC200CHS022E?
Modulus verticaliter montatur, perpendiculariter ad railem DIN.
Quando IC200CHS022E in tabulam montandum est praeter usum raillis DIN?
Montationem in tabulam addere, ubi applicatio maximam resistentiam vibrationibus mechanicis et impulsibus postulat.
Quam torque ad constringendos terminales cistulae in IC200CHS022E uti debes?
Torque terminalis recommendatum est inter 0.37 et 0.45 ft·lb.
Quomodo clavem moduli in IC200CHS022E constituere possum?
Dialos clavium portantis ita regere, ut cum clavibus in parte inferiori moduli I/O electi congruant.
Ubi tenaculum cartae connexionalis in IC200CHS022E durante operatione ponendum est?
Tenaculum cartae connexionalis in positione retracta servare dum systema operatur.