Overview
- Match the Basic BF00 article and its firmware capability in the project.
- Use CC01 identification and a BU type A0 terminal base.
- Provide AUX terminals for three-wire sensors or external terminals for four-wire sensors.
- Do not assign counter, oversampling or channel-fault diagnostics to this Basic module.
- Keep two-wire sensor quiescent current within 2 mA.
- Size the internally supplied sensor load within the 700 mA limit.
6ES7131-6BF00-0AA0 SIMATIC ET 200SP DI 8x24VDC BA Input Module
An eight-input Basic module for 24 V DC PNP signals, with selectable filtering, a one-byte input image and module-level supply diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7131-6BF00-0AA0 |
| Product Type | Basic digital input module |
| Core Function | Acquires binary sensor states |
| Application | ET 200SP stations using A0 BaseUnits |
Basic process-data image
Eight channel states occupy one input byte.
Sensor wiring options
A0 bases provide one- and two-wire connections, with AUX bases for three-wire sensors.
Supply monitoring
PWR and DIAG indicators distinguish supply and module status.
Product Overview
6ES7131-6BF00-0AA0 provides eight P-reading inputs for the ET 200SP Basic configuration.
Its input characteristic accepts IEC 61131 types 1, 2 and 3, while selectable filtering and supply-voltage monitoring support straightforward sensor acquisition without counter or oversampling operation.
Key Functions
Acquire the eight binary channels
Each channel contributes one bit to the one-byte input area.
Set the input filter for the sensor
The available filter settings range from no configured delay through 20 ms, with an additional cable-dependent delay.
Monitor the module supply
Supply-voltage diagnostics and the PWR/DIAG indicators are available, while wire-break and short-circuit diagnostic messages are not provided.
Official Specifications
| Digital Input Circuit | 8 P-reading channels; IEC 61131 types 1, 2 and 3 |
|---|---|
| Module Supply Voltage | 24 V DC nominal; 19.2–28.8 V DC |
| Module Current Consumption | 8 mA rated without sensor supply; 70 mA maximum with all inputs supplied internally |
| Sensor-Supply Rating | 24 V DC, 700 mA maximum, with short-circuit protection |
| Input Voltage Thresholds | Signal 0: −30 to +5 V; signal 1: +11 to +30 V |
| Typical Input Current at Signal 1 | 6.8 mA |
| Configurable Input Delay | None, 0.05, 0.1, 0.4, 0.8, 1.6, 3.2, 12.8 or 20 ms, plus 30–500 µs depending on cable length |
| Maximum Two-Wire Sensor Quiescent Current | 2 mA |
| Input Address Space | 1 byte |
| Typical Power Loss | 1.6 W at 24 V with eight inputs supplied internally |
| Maximum Cable Length | 1,000 m shielded; 600 m unshielded |
| Isolation Test Voltage | 707 V DC |
| Channel Separation | No isolation between channels; isolation from the backplane bus |
| Status Indicators | Green PWR and channel LEDs; green/red DIAG LED |
| Overall Dimensions | 15 × 73 × 58 mm (W × H × D) |
| Approximate Weight | 28 g |
Frequently Asked Questions
Can 6ES7131-6BF00-0AA0 take the place of a high-speed counter input module?
The Basic module supports digital-input operation but has no counter or oversampling mode.
Which BaseUnit should I choose for three-wire sensors on 6ES7131-6BF00-0AA0?
Use a BU type A0 with AUX terminals for the three-wire connection.
Can I connect four-wire sensors directly to 6ES7131-6BF00-0AA0 without extra terminals?
The four-wire connection uses a BU type A0 together with external terminals.
Will 6ES7131-6BF00-0AA0 report a broken sensor wire or short circuit as a diagnostic message?
The module provides supply-voltage monitoring but does not provide wire-break or short-circuit diagnostic messages.
How much PLC input memory does 6ES7131-6BF00-0AA0 consume?
The eight input states occupy one byte.
Which two-wire sensor leakage limit applies to 6ES7131-6BF00-0AA0?
The permissible quiescent current is 2 mA maximum.
Can I configure 6ES7131-6BF00-0AA0 in STEP 7 TIA Portal V13 SP1?
The module is configurable in STEP 7 TIA Portal from V13 SP1.