Siemens 6ES5454-7LA11 SIMATIC S5 454 24 V 2 A Digital Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Wire the field circuits for a 24 V DC nominal supply within the 20–30 V permissible range.
- Keep each four-channel group within its 50% summed-current loading limit.
- Do not parallel output channels, and respect the 10 W lamp limit and 0.27 Hz inductive switching limit.
- Include the module electronics current and approximately 20 W power loss in the cabinet supply and thermal calculations.
6ES5454-7LA11 SIMATIC S5 454 24 V 2 A Digital Output Module
Sixteen 24 V DC outputs rated at 2 A per channel, with four-channel optocoupler isolation groups and electronic short-circuit protection.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES5454-7LA11 |
| Product Type | DC digital output module |
| Core Function | PLC-controlled switching of 24 V DC loads |
| Application | Digital load circuits in SIMATIC S5-115H systems |
DC load control
Sixteen outputs switch 24 V DC loads with a rated 2 A channel current and a minimum high-state voltage of L+ minus 3 V.
Four-channel isolation groups
Optocouplers isolate groups of four outputs, with total group loading limited to 50% of the summed channel current ratings.
Electronic output protection
Electronic short-circuit protection and inductive cutoff voltage limitation support protected switching of connected DC loads.
Product Overview
6ES5454-7LA11 provides sixteen DC digital outputs in an S5-115H control system, with optocoupler isolation in four-channel groups.
The 2 A channel rating supports DC load switching, while the group current limit, lamp load limit and load-dependent switching frequency determine the practical circuit design.
Key Functions
DC load control
Sixteen outputs switch 24 V DC loads with a rated 2 A channel current and a minimum high-state voltage of L+ minus 3 V.
Four-channel isolation groups
Optocouplers isolate groups of four outputs, with total group loading limited to 50% of the summed channel current ratings.
Electronic output protection
Electronic short-circuit protection and inductive cutoff voltage limitation support protected switching of connected DC loads.
Official Specifications
| Digital outputs | 16 |
|---|---|
| Rated load voltage | 24 V DC |
| Permissible load voltage | 20–30 V DC |
| Rated channel current | 2 A |
| Isolation arrangement | Optocouplers; groups of 4 outputs |
| Permissible group current loading | 50% of the sum of the group channel current ratings |
| Minimum high-state voltage | L+ minus 3 V |
| Maximum off-state leakage | 1 mA |
| Maximum lamp load | 10 W |
| Short-circuit protection | Electronic |
| Output paralleling | Not permitted |
| Inductive cutoff voltage limitation | -15 V |
| Maximum resistive-load switching | 100 Hz |
| Maximum inductive-load switching | 0.27 Hz |
| Maximum field cable length | 1,000 m shielded; 600 m unshielded |
| Internal 5 V current consumption | 50 mA |
| Unloaded L+ current consumption | 8.5 mA per group |
| Typical module power loss | 20 W |
| Isolation test voltage | 500 V AC |
| Weight | Approximately 1.1 kg |
Frequently Asked Questions
Can all four outputs in a group on 6ES5454-7LA11 carry their full 2 A rating?
The total group current is limited to 50% of the summed channel ratings, so the load must be distributed within that budget.
Can outputs on 6ES5454-7LA11 be paralleled to supply a larger load?
Parallel connection of the outputs is not permitted.
Can 6ES5454-7LA11 switch a 20 W signal lamp?
The specified maximum lamp load is 10 W.
Can 6ES5454-7LA11 switch an inductive load once per second?
The maximum switching frequency for an inductive load is 0.27 Hz.
Are the outputs on 6ES5454-7LA11 individually isolated?
Optocoupler isolation is provided in groups of four outputs rather than for each individual channel.
How much voltage headroom should I allow at a load driven by 6ES5454-7LA11?
The minimum high-state output voltage is the load supply voltage L+ minus 3 V.
What electronics supply current should I budget for 6ES5454-7LA11?
Allow 50 mA from the internal 5 V supply and 8.5 mA from L+ per group before adding the connected load currents.