SIMATIC S5 • 454 Digital Outputs

6ES5454-7LA11 SIMATIC S5 454 24 V 2 A Digital Output Module

Sixteen 24 V DC outputs rated at 2 A per channel, with four-channel optocoupler isolation groups and electronic short-circuit protection.

At a Glance

Brand Siemens
Model 6ES5454-7LA11
Product Type DC digital output module
Core Function PLC-controlled switching of 24 V DC loads
Application Digital load circuits in SIMATIC S5-115H systems

DC load control

Sixteen outputs switch 24 V DC loads with a rated 2 A channel current and a minimum high-state voltage of L+ minus 3 V.

Four-channel isolation groups

Optocouplers isolate groups of four outputs, with total group loading limited to 50% of the summed channel current ratings.

Electronic output protection

Electronic short-circuit protection and inductive cutoff voltage limitation support protected switching of connected DC loads.

Product Overview

6ES5454-7LA11 provides sixteen DC digital outputs in an S5-115H control system, with optocoupler isolation in four-channel groups.

The 2 A channel rating supports DC load switching, while the group current limit, lamp load limit and load-dependent switching frequency determine the practical circuit design.

Ordering focus: Match the 24 V DC supply, four-channel isolation groups and group load budget; output paralleling is not permitted.
Key Functions

DC load control

Sixteen outputs switch 24 V DC loads with a rated 2 A channel current and a minimum high-state voltage of L+ minus 3 V.

Four-channel isolation groups

Optocouplers isolate groups of four outputs, with total group loading limited to 50% of the summed channel current ratings.

Electronic output protection

Electronic short-circuit protection and inductive cutoff voltage limitation support protected switching of connected DC loads.

Official Specifications
Digital outputs 16
Rated load voltage 24 V DC
Permissible load voltage 20–30 V DC
Rated channel current 2 A
Isolation arrangement Optocouplers; groups of 4 outputs
Permissible group current loading 50% of the sum of the group channel current ratings
Minimum high-state voltage L+ minus 3 V
Maximum off-state leakage 1 mA
Maximum lamp load 10 W
Short-circuit protection Electronic
Output paralleling Not permitted
Inductive cutoff voltage limitation -15 V
Maximum resistive-load switching 100 Hz
Maximum inductive-load switching 0.27 Hz
Maximum field cable length 1,000 m shielded; 600 m unshielded
Internal 5 V current consumption 50 mA
Unloaded L+ current consumption 8.5 mA per group
Typical module power loss 20 W
Isolation test voltage 500 V AC
Weight Approximately 1.1 kg
Frequently Asked Questions

Can all four outputs in a group on 6ES5454-7LA11 carry their full 2 A rating?

The total group current is limited to 50% of the summed channel ratings, so the load must be distributed within that budget.

Can outputs on 6ES5454-7LA11 be paralleled to supply a larger load?

Parallel connection of the outputs is not permitted.

Can 6ES5454-7LA11 switch a 20 W signal lamp?

The specified maximum lamp load is 10 W.

Can 6ES5454-7LA11 switch an inductive load once per second?

The maximum switching frequency for an inductive load is 0.27 Hz.

Are the outputs on 6ES5454-7LA11 individually isolated?

Optocoupler isolation is provided in groups of four outputs rather than for each individual channel.

How much voltage headroom should I allow at a load driven by 6ES5454-7LA11?

The minimum high-state output voltage is the load supply voltage L+ minus 3 V.

What electronics supply current should I budget for 6ES5454-7LA11?

Allow 50 mA from the internal 5 V supply and 8.5 mA from L+ per group before adding the connected load currents.

Compatibility & Ordering Notes
Before ordering 6ES5454-7LA11: Match the 24 V DC supply, four-channel isolation groups and group load budget; output paralleling is not permitted.

Before installation

  • Wire the field circuits for a 24 V DC nominal supply within the 20–30 V permissible range.
  • Keep each four-channel group within its 50% summed-current loading limit.
  • Do not parallel output channels, and respect the 10 W lamp limit and 0.27 Hz inductive switching limit.
  • Include the module electronics current and approximately 20 W power loss in the cabinet supply and thermal calculations.
Hot Selling Models
HM250/300 128624
1734-Entr PN-138004
Z2FS6-2-43/2QV
3003923
P1KS003
ABB 2CDS253103R0164 S203-C16
ST4209X1004-KGRO3
60.13.9.220.0040
6EC1040-3A
ID211 CJ1W-ID211
PXL-C2-DC
WLL10-9103 1004543
8000-84049-3370500 Exact8 4xM8
R1083X12XX
3RF2320-1AA04

Get a Free Quote

Our representative will contact you soon.
Email
Name
Company Name
Message
0/1000
email goToTop

Evolo Automation is not an authorized distributor unless otherwise specified, representative, or affiliate of the manufacturer of this product. All trademarks and documents are the property of their respective owners and are provided for identification and informational.