Siemens 6ES7132-4BF00-0AA0 SIMATIC ET 200S 8DO DC24V/0.5A Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Supported PROFIBUS interfaces include IM151-1 STANDARD from 6ES7151-1AA03-0AB0 and IM151-1 FO STANDARD from 6ES7151-1AB02-0AB0.
- For IM151-1 HIGH FEATURE, use 6ES7151-1BA01-0AB0 or higher with firmware V2.1.3 or higher.
- Supported PN interfaces start at 6ES7151-3AA20-0AB0, 6ES7151-3BA20-0AB0 or 6ES7151-3BB21-0AB0 with firmware V4.0.1 or higher.
- Choose a supported TM-E15C, TM-E15S or TM-E15N terminal module and provide the required M return connections.
- Do not parallel outputs to increase current capacity, and consider the supply-on pulse in pulse-sensitive circuits.
6ES7132-4BF00-0AA0 SIMATIC ET 200S 8DO DC24V/0.5A Output Module
Eight 24 V DC outputs in a 15 mm electronic module, with 0.5 A rated channel current, channel short-circuit protection and a 4 A module total.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7132-4BF00-0AA0 |
| Product Type | Digital output electronic module |
| Core Function | Switching DC actuators and indicator loads |
| Application | ET 200S distributed I/O stations |
Actuator channels
Eight outputs drive solenoid valves, DC contactors and indicator lights.
Load selection
Resistive, inductive and lamp loads have different switching-frequency limits.
Terminal planning
Two-wire actuator circuits may require additional M terminals or potential-distribution modules.
Product Overview
6ES7132-4BF00-0AA0 provides eight electronic outputs for switching DC field loads in an ET 200S station, with 0.5 A rated current at each output and a maximum total of 4 A per module.
The module supports isochronous operation and provides a green status indicator for each channel, while actuator selection must account for switching frequency, lamp power and off-state leakage.
Key Functions
Switch several actuator types
The outputs operate solenoid valves, DC contactors and indicator lamps, with electronic short-circuit protection on each channel.
Match switching rate to the load
The permitted switching frequency is 100 Hz for resistive loads, 2 Hz for inductive loads and 10 Hz for lamp loads.
Coordinate load returns and supply switching
Provide separate M connection points for two-wire loads and account for an approximately 50 μs high pulse when a mechanical contact applies the load supply.
Official Specifications
| Output Channels | 8 |
|---|---|
| Rated Load Supply | 24 V DC from the power module |
| Output Current Limits | 0.5 A rated per channel; 7 mA–0.6 A permissible range; 4 A total per module |
| ON-State Output Voltage | At least L+ minus 1 V |
| Maximum OFF-State Residual Current | 0.3 mA |
| Resistive-Load Output Delays | 0 to 1: 300 μs maximum; 1 to 0: 600 μs maximum |
| Load Resistance Range | 48 Ω–3.4 kΩ |
| Maximum Lamp Load | 5 W |
| Switching Frequency by Load | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp |
| Short-Circuit Protection | Electronic per channel; typical response threshold 1.5 A |
| Maximum No-Load Supply Current | 5 mA per channel |
| Typical Power Dissipation | 1.5 W |
| Output Address Allocation | 1 byte |
| Parameter Data Length | 3 bytes |
| Maximum Cable Length | 600 m unshielded; 1000 m shielded |
| Isolation Arrangement | Channels isolated from backplane bus; no channel-to-channel isolation |
| Permissible Inter-Circuit Potential Difference | 75 V DC or 60 V AC |
| Insulation Test Voltage | 500 V DC |
| Module Width and Approximate Weight | 15 mm; 40 g |
| Diagnostics and Status | Green LED per output; no diagnostic functions |
Frequently Asked Questions
Can I parallel two channels of 6ES7132-4BF00-0AA0 to power a larger actuator?
Parallel outputs may be used for redundant load control within the module, but they must not be used to increase output power.
Why might a high-speed counter detect a pulse when 6ES7132-4BF00-0AA0 receives load power?
Applying the 24 V DC load supply through a mechanical contact can produce an approximately 50 μs high signal at the outputs.
Do two-wire actuators connected to 6ES7132-4BF00-0AA0 need extra return terminals?
Additional M terminals are required when the selected terminal-base arrangement does not provide enough return connections for the loads.
How often can 6ES7132-4BF00-0AA0 switch a solenoid compared with a resistive load?
The switching-frequency limit is 2 Hz for inductive loads and 100 Hz for resistive loads.
Will 6ES7132-4BF00-0AA0 provide an electronic fault message for a failed output?
The module has channel status LEDs but does not provide diagnostic functions.
What lamp power can I connect to a channel of 6ES7132-4BF00-0AA0?
The maximum lamp load is 5 W per output.
Which interface firmware is needed for 6ES7132-4BF00-0AA0 with IM151-1 HIGH FEATURE?
The supported IM151-1 HIGH FEATURE arrangement starts at 6ES7151-1BA01-0AB0 with firmware V2.1.3.