Conspectus
- Interfacies PROFIBUS supportatae includunt IM151-1 STANDARD ab 6ES7151-1AA03-0AB0 et IM151-1 FO STANDARD ab 6ES7151-1AB02-0AB0.
- Pro IM151-1 HIGH FEATURE, utere 6ES7151-1BA01-0AB0 vel superiore cum firmware V2.1.3 vel superiore.
- Interfacies PN supportatae incipiunt ab 6ES7151-3AA20-0AB0, 6ES7151-3BA20-0AB0 aut 6ES7151-3BB21-0AB0 cum firmware V4.0.1 vel superiore.
- Elige modulum terminalis TM-E15C, TM-E15S aut TM-E15N supportatum et praebere necessarias connexiones M ad reditum.
- Non coniungere outputs in parallel ad augendum capacitatem currentis, et considera impulsum supply-on in circuitibus sensibilibus ad impulsus.
6ES7132-4BF00-0AA0 SIMATIC ET 200S 8DO DC24V/0.5A Output Module
Eight 24 V DC outputs in a 15 mm electronic module, with 0.5 A rated channel current, channel short-circuit protection and a 4 A module total.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7132-4BF00-0AA0 |
| Typus Producti | Digital output electronic module |
| Functio principalis | Switching DC actuators and indicator loads |
| Applicatio | ET 200S distributed I/O stations |
Actuator channels
Eight outputs drive solenoid valves, DC contactors and indicator lights.
Load selection
Resistive, inductive and lamp loads have different switching-frequency limits.
Terminal planning
Circuits actuator duo-filum posse requirere terminales M addititionales aut modulos distributionis potentialis.
Product Overview
6ES7132-4BF00-0AA0 Praebet octo outputs electronicos pro commutando oneribus campi DC in statione ET 200S, cum corrente nominali 0.5 A per output et summa maxima 4 A per modulum.
Modulus operatio isochrona sustinet et indicatorem status viridem praebet pro singulis canalibus, dum selectio actuactorum rationem habere debet frequentionem commutationis, potentiam lampadis et percolationem in statu off.
Key Functions
Commuta plures species actuactorum.
Outputs operant valves solenoidales, contactores DC et lampadas indicativas, cum protectione electronica contra circuitus breves in singulis canalibus.
Adaptare velocitatem commutationis ad onus.
Frequento commutationis permittitur est 100 Hz pro oneribus resistivis, 2 Hz pro oneribus inductivis et 10 Hz pro oneribus lampadarum.
Concordare reditus onerum et commutationem supply.
Provide separate M connection points for two-wire loads and account for an approximately 50 μs high pulse when a mechanical contact applies the load supply.
Official Specifications
| Output channels | 8 |
|---|---|
| Alimentatio oneris nominalis | 24 V DC ab modulo potentiae |
| Output Current Limits | 0.5 A rated per channel; 7 mA–0.6 A permissible range; 4 A total per module |
| ON-State Output Voltage | At least L+ minus 1 V |
| Maximum OFF-State Residual Current | 0.3 mA |
| Resistive-Load Output Delays | 0 to 1: 300 μs maximum; 1 to 0: 600 μs maximum |
| Intervalum Resistentiae Onus | 48 Ω–3,4 kΩ |
| Maxima onus lampadis | 5 w |
| Switching Frequency by Load | 100 Hz resistive; 2 Hz inductive; 10 Hz lamp |
| Tutela circuiti brevis | Electronic per channel; typical response threshold 1.5 A |
| Currentia de supply sine onus maximum | 5 mA per canallem |
| Dissipatio Energiae Typica | 1.5 W |
| Allocatio adressuum output | 1 octetum |
| Longitudo datorum parametrorum | 3 octeta |
| Longitudo Maxima Cavi | 600 m non scutata; 1000 m scutata |
| Dispositio isolationis | Canalis isolati ab omni bus retroplanaris; nullum isolamentum inter canales |
| Differentia Potentialis Inter-Circuitus Permissa | 75 V CC ou 60 V CA |
| Testis voltagii isolationis | 500 V DC |
| Largor del modulo e peso approximative | 15 mm; 40 g |
| Diagnostica et Status | LED viridis pro singulo output; nullae functiones diagnosticas |
Quaestiones Frequenter Rogatae
Num possum duo canales 6ES7132-4BF00-0AA0 in parallelum coniungere ad maiorem actuatorem excitandum?
Output paralleli uti possunt ad controllem redunantem oneris intra modulum, sed non ad augendum potestatem output.
Cur fortasse numerator altius velocitatis impulsum detegit dum 6ES7132-4BF00-0AA0 potestatem oneris accipit?
Applicatio supply 24 V DC oneris per contactum mechanicum impulsum altum circa 50 μs in output producere potest.
Necessene est terminalia additiva reditus pro actuaturis duorum filorum ad 6ES7132-4BF00-0AA0 connexis?
Additional M terminals are required when the selected terminal-base arrangement does not provide enough return connections for the loads.
How often can 6ES7132-4BF00-0AA0 switch a solenoid compared with a resistive load?
The switching-frequency limit is 2 Hz for inductive loads and 100 Hz for resistive loads.
Will 6ES7132-4BF00-0AA0 provide an electronic fault message for a failed output?
The module has channel status LEDs but does not provide diagnostic functions.
What lamp power can I connect to a channel of 6ES7132-4BF00-0AA0?
The maximum lamp load is 5 W per output.
Which interface firmware is needed for 6ES7132-4BF00-0AA0 with IM151-1 HIGH FEATURE?
The supported IM151-1 HIGH FEATURE arrangement starts at 6ES7151-1BA01-0AB0 with firmware V2.1.3.