Overview
Place of Origin: |
Sweden |
Brand Name: |
ABB |
Model Number: |
AI895 3BSC690086R1 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Model: |
AI895 3BSC690086R1 |
|
Type: |
Analog Input Module |
|
Dimensions: |
4.5 x 10.5 x 12 cm |
|
Weight: |
0.24 kg |
|
Signal Type: |
Unipolar, single-ended |
|
Signal Range: |
4–20 mA |
|
Number of Channels: |
8 |
|
HART Support: |
Yes |
|
SOE Support: |
No |
|
Redundancy: |
No |
|
High Integrity: |
No |
|
Intrinsic Safety: |
Yes |
|
Mechanical System: |
S800 |
|
Resolution: |
12-bit |
|
Isolation: |
Groupwise isolated from ground |
|
Under/Over Range: |
1.5 / 22 mA |
|
Accuracy: |
Typical 0.05%, Max 0.1% |
|
Temperature Drift: |
Typical 100 ppm/°C |
|
Input Filter (0–90% rise): |
20 ms |
|
Current Limiting: |
Built-in transmitter power limiting |
|
CMRR (50/60 Hz): |
>80 dB |
|
NMRR (50/60 Hz): |
>10 dB |
|
Rated Insulation Voltage: |
50 V |
|
Dielectric Test Voltage: |
500 VAC |
|
Power Dissipation: |
4.75 W |
|
Current Consumption (+5V Modulebus): |
Typical 130 mA |
|
Current Consumption (+24V External): |
Typical 270 mA, Max <370 mA |
Description
The AI895 3BSC690086R1 Analog Input Module can directly interface 2-wire transmitters and with a particular connection it can also interface 4-wire transmitters without losing the HART capability. The AI895 Analog Input Module has 8 channels. The module includes Intrinsic Safety protection components on each channel for connection to process equipment in hazardous areas without the need for additional external devices. Each channel can power and monitor a two-wire process transmitter and HART communication. The input voltage drop of the current input is typically 3 V, PTC included. The transmitter supply for each channel is able to provide at least 15 V at a 20 mA loop current to power Ex certified process transmitters and is limited to 23 mA in overload conditions.
TU890 and TU891 Compact MTU can be used with this module and it enables two wire connections to the process devices without additional terminals. TU890 for Ex applications and TU891 for non Ex applications.
Environment and certification
|
CE Mark: |
Yes |
|
Electrical Safety: |
EN 61010-1, EN 61010-2-201 |
|
Hazardous Location: |
ATEX/IECEx Zone 2 with interface to Zone 0, cFMus C1 Div 2 / Zone 2 with interface to C1, C2, C3 Div 1 / Zone 0 |
|
Marine Certification: |
ABS, BV, DNV, LR |
|
Operating Temperature: |
0 to +55 °C (+32 to +131 °F) |
|
Storage Temperature: |
-40 to +70 °C (-40 to +158 °F) |
|
Pollution Degree: |
Degree 2, IEC 60664-1 |
|
Corrosion Protection: |
ISA-S71.04: G3 |
|
Relative Humidity: |
5 to 95 %, non-condensing |
|
Max Ambient Temperature: |
55 °C (131 °F), for vertical mounting in compact MTU 40 °C (104 °F) |
|
Protection Class: |
IP20 according to IEC 60529 |
|
Mechanical Operating Conditions: |
IEC/EN 61131-2 |
|
EMC: |
EN 61000-6-4, EN 61000-6-2 |
|
Overvoltage Categories: |
IEC/EN 60664-1, EN 50178 |
|
Equipment Class: |
Class I according to IEC 61140 (earth protected) |
|
RoHS Compliance: |
EU RoHS, UAE RoHS, CN RoHS |
|
WEEE Compliance: |
DIRECTIVE/2012/19/EU |
Applications
Oil refineries: Pressure and level transmitter access in flammable and explosive zones (Zone 0/1).
Offshore oil production plants: Intrinsically safe instrument signal acquisition at oil and gas wellheads and storage tanks.
Chemical additive plants: Flow and temperature transmission in explosion-proof areas surrounding reactors.
Natural gas receiving plants (LNG): Intelligent instrument monitoring of unloading arms and storage tank areas.
Agrochemical plants: Explosion-proof instrument integration for production lines involving flammable solvents.
Explosives/powder manufacturing plants: Intrinsically safe isolation and transmission of sensors in high-risk production workshops.
Features and benefits
8 channels for 4...20 mA, single ended unipolar inputs.
HART communication.
1 group of 8 channels isolated from ground.
Power and monitor for Ex certified two-wire transmitters.
Non energy-storing analog inputs for externally powered sources.
Diagnostics
Front LED’s: F(ault), R(un), W(arning), Tx (HART communiation)
Supervision: Internal process supply
Compatibility
Use with MTU: TU890, TU891 or TU891Z
Keying code: AE
FAQ
Q: What is the AI895 3BSC690086R1?
A: It is a Analog Input Module.
Q: Can it connect to a 4-wire transmitter?
A: Yes. Although the AI880A is primarily designed for 2-wire transmitters, it can also be connected to 4-wire instruments using specific wiring methods (using an external power supply) while maintaining HART communication functionality.
Q: Is there a redundant model of the AI895 3BSC690086R1?
A: Redundancy is not supported. The AI895 3BSC690086R1 module is designed for non-redundant applications (Redundancy: No). If the system requires redundancy, a redundant module solution from another S800 series must be selected.
Q: How to Check Price and Availability for AI895 3BSC690086R1?
A: Please contact John Yang for sales at +86-18150117685 or request a quote.