- Overview
- Specifications
- Description
- Applications
- Notable Features
- FAQ
- Recommended Products
Overview
Place of Origin: |
USA |
Brand Name: |
HONEYWELL |
Model Number: |
8C-TAIXA1 51307127-175 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Parameter |
Value |
|
Part Number |
8C-TAIXA1 51307127-175 |
|
Part Type |
Analog Input Module |
|
Dimensions |
12 x 6.5 x 14.5 cm |
|
Weight |
0.26 kg |
|
Redundancy |
Non-redundant |
|
Coating |
Yes |
|
Input Type |
Current (2-wire or self-powered transmitters) |
|
Input Channels |
16 channels (single-ended type) |
|
A/D Converter Resolution |
16-bit |
|
Input Range |
4–20 mA (through 250 Ω) |
|
Voltage Rating |
24 V DC |
|
Module Current Rating |
110 mA |
|
Common Mode Rejection Ratio (DC to 60 Hz, 500 Ω imbalance) |
70 dB |
|
Common Mode Voltage (DC to 60 Hz) |
-6 to +5 V peak |
|
Normal Mode Rejection Ratio (60 Hz) |
19 dB |
|
Normal Mode Filter Response |
Single-pole RC, -3 dB @ 6.5 Hz |
|
Maximum Normal Mode Input |
±30 V |
|
Crosstalk (DC to 60 Hz, channel-to-channel) |
-60 dB |
|
Maximum Input Voltage (no damage) |
±30 V |
|
Input Scan Rate |
50 ms |
|
Hardware Accuracy (23.5°C ±2°C) |
±0.075% of full scale |
|
Hardware Accuracy (0 to 60°C) |
±0.15% of full scale |
|
Galvanic Isolation |
1000 VAC RMS or ±1000 VDC |
|
Isolation Technique |
ICoupler (in IOM) |
|
Transmitter Field Power Conditioning |
Individually protected current limiting circuits (no fuse required) |
|
Module Removal/Insertion Under Power |
Supported |
Description
The Honeywell 8C-TAIXA1 51307127-175 is an Analog Input Module in Honeywell systems. This module connects to and receives continuous current signals generated by industrial transmitters in the factory field. It provides an electrical interface for compatible plug-in electronic modules, allowing the introduction of process variable electrical signals acquired by field transmitters into the system without requiring an external power distribution panel.
Applications
Fine Chemical Plants: Monitor level and pressure signals in corrosive environments.
Seawater Desalination Plants: Reduce salt-fog interference for accurate signal transmission.
Food & Beverage Plants: Use low-power operation for compact sterile production areas.
Large Water Treatment Plants: Simplify maintenance and tolerate transmitter short circuits.
Notable Features
Extensive self-diagnostics
Optional redundancy
HART-capable, multivariable devices
Fast loop scan
Internal or external field power selection
On board excitation power (no need for marshalling power)
Suitable for Configure / Status for HART Device
Galvanic Isolation
FAQ
Q: What channels does 8C-TAIXA1 51307127-175 have and does it support redundancy?
A: 16 single-ended channels, non-redundant, coated.
Q: What is the accuracy and scan rate of 8C-TAIXA1 51307127-175?
A: Ambient accuracy ±0.075% F.S., scan rate 50 ms (16-bit ADC).
Q: What signal range and operating voltage does 8C-TAIXA1 51307127-175 support?
A: Only supports 4–20 mA current, operating voltage 24 V DC (current 110 mA).
Q: What isolation withstand voltage and technology does 8C-TAIXA1 51307127-175 use?
A: Withstand voltage 1000 VAC RMS / ±1000 VDC, using iCoupler isolation technology.
Q: Does 8C-TAIXA1 51307127-175 require fuses for field power and does it support hot swapping?
A: Equipped with individual current limiting protection, no fuse required, supports live hot swapping.