Overview

Place of Origin:

USA

Brand Name:

Bently Nevada

Model Number:

3300/01

Packaging Details:

Original new Factory Sealed

Delivery Time:

5-7 days

Payment Terms:

T/T

Supply Ability:

In stock

Quick Detail

System Function

Centralized rack interface, operator interaction, buffered signals on front panel

Optional Interface

Optional serial interface capability

Contact Closure Inputs

Rack Inhibit, Alarm Reset, Trip Multiply

Power Supply

Accepts regulated DC voltage from rack power supply

Nominal Power Consumption

2 W; 3.6 W with serial interface option

Input Impedance

10 kΩ

Output Impedance

100 Ω

Operating Temperature

0°C to +65°C (+32°F to +149°F)

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Relative Humidity

Up to 95% non-condensing

Serial Interface Address Setting

8 switches, up to 256 addresses

Serial Interface Baud Rate

Configurable, up to 9600 baud

Dimension:

2.5x12.8x4cm

Weight:

0.26 kg

Description

The 3300/01 System Monitor is designed for centralized rack control and operator interaction in industrial automation monitoring systems. The 3300/01 System Monitor integrates buffered transducer signals directly on the front panel, eliminating the need for external keypads or connector cards. With nominal power consumption of 2 W, or 3.6 W when equipped with the serial interface option, the 3300/01 System Monitor operates efficiently within standard rack power supplies.

The 3300/01 System Monitor supports contact closure inputs for Rack Inhibit, Alarm Reset, and Trip Multiply through rear panel terminals, enabling direct control of protection functions. Input impedance is 10 kΩ and output impedance is 100 Ω, supporting accurate signal transmission within the rack. Operating temperature ranges from 0°C to +65°C, with storage from -40°C to +85°C and humidity up to 95% non-condensing.

With optional serial interface capability, the 3300/01 System Monitor provides configurable baud rates up to 9600, selectable CRC or BCC message checking, and up to 256 addresses via 8 switches, supporting Allen Bradley or Modicon protocol selection for automated machinery monitoring.

Applications

Adjust alarm setpoints with 8 bit to 12 bit internal conversion
The 3300/01 System Monitor converts 8 bit input data into a 12 bit internal value, allowing finer alarm adjustment steps directly from the front panel. With 10 kΩ input impedance and 100 Ω output impedance, the 3300/01 System Monitor maintains accurate signal transfer while operators modify alarm limits using the Up and Down controls.

Transmit rack data to PLC systems at up to 9600 baud
The 3300/01 System Monitor supports configurable baud rates up to 9600 and allows up to 256 device addresses via 8 hardware switches. This enables the 3300/01 System Monitor to communicate vibration and process values to Allen Bradley or Modicon PLC platforms using CRC or BCC message checking.

Provide buffered signal outputs for field diagnostics
The 3300/01 System Monitor delivers buffered transducer signals on the front panel, allowing technicians to connect test equipment without affecting rack circuits. With nominal power consumption of 2 W, or 3.6 W with serial interface installed, the 3300/01 System Monitor supports continuous monitoring in multi-slot racks.

Specifications

Message Checking

CRC or BCC selectable (Allen Bradley supports CRC/BCC; Modicon supports CRC only)

Parity and Stop Bit Selection

Configurable via 2 switches

Protocol Selection

Allen Bradley or Modicon selectable by switch

BCD Switch Option

Binary Coded Decimal formatting available for Allen Bradley protocol

Data Format

8-bit value converted to 12-bit internal value; optional BCD conversion

Front Panel Controls

Up/Down alarm setpoint adjustment; Alarm Reset switch

Rear Panel Connections

Terminals for Rack Inhibit, Trip Multiply, Alarm Reset

Rear Panel Ports

2 receptacles for Communications Processor; 2 receptacles for Serial Interface

Competitive Advantage

Reduce rack power load to 2 W to 3.6 W per module
The 3300/01 System Monitor operates at 2 W under standard configuration and 3.6 W with serial interface, enabling installation of multiple 3300/01 System Monitor units without exceeding rack power supply limits.

Support up to 256 communication addresses in one rack system
Using 8 address switches, the 3300/01 System Monitor allows 256 selectable nodes, enabling large distributed monitoring systems controlled by multiple 3300/01 System Monitor modules.

Operate within 0°C to +65°C and store at -40°C to +85°C
The 3300/01 System Monitor functions across industrial temperature ranges and withstands storage extremes, allowing deployment of the 3300/01 System Monitor in control rooms and field enclosures.

Select protocol and message verification through hardware switches
The 3300/01 System Monitor provides CRC or BCC checking and Allen Bradley or Modicon protocol selection via switch settings, enabling the 3300/01 System Monitor to connect directly to different PLC communication standards without firmware modification.