Specifications

Parameter

Value

Part Number

TC-215-02-8M5

Part Name

I/O Companion Slot Cable

Cable Length

8.5 m

Voltage Rating

24/120 V

Cable Type

Internal 40-channel output to FTA (integral power)

Insulation Material

Low smoke zero halogen (LSZH)

Connector Type (Chassis End)

96-pin C-type connector (Type C)

Connector Type (FTA End)

96-pin R-type connector (Type R)

Description

TC-215-02-8M5 I/O Companion Slot Cable is a high-reliability industrial interface cable designed for connecting digital output modules to Field Termination Assemblies (FTA) in safety-critical control systems. It provides a stable and secure pathway for signal transmission and integrated power distribution between system chassis and field-side termination equipment.

Applications
Petrochemical Plants: LSZH insulation improves fire safety by reducing toxic gas risk in harsh environments.
Thermal Power Plants: High-density channels support DCS control with stable electrical signal transmission.
Pharmaceutical Plants: Non-corrosive materials help maintain cleanroom safety and environmental compliance.
LNG Processing Plants: Integrated FTA power ensures stable long-distance monitoring and control operation.
Automotive Plants: Durable multi-channel design supports reliable signal linking in assembly and coating systems.
Troubleshooting

Signal Attenuation or Interruption: Check if the 96-pin Type C connector on the rack end or the Type R connector on the FTA end is loose. Reconnect and tighten them.

Channel Short Circuit/Open Circuit: Use a multimeter to measure the impedance of the corresponding pins on channel 40. If insulation is damaged, replace the cable immediately.

FTA Power Supply Abnormality: Check the 24V/120V power module at the input end and confirm that the Integral Power pins integrated into the cable are not burnt.

FAQ

Q1: Can TC-215-02-8M5 transmit 24V and 120V signals simultaneously under 40-channel full load?
A: Yes. It supports parallel transmission of 24V/120V signals with internal channel isolation.

Q2: Can the 96-pin R-type connector of TC-215-02-8M5 be field reworked if FTA mismatch occurs?
A: No. It is factory-terminated and must not be modified to avoid damaging power integrity.

Q3: What is the fire safety advantage of LSZH insulation in TC-215-02-8M5?
A: It produces very low smoke and no toxic halogen gases during fire conditions.

Q4: How to identify insertion direction at the chassis end of TC-215-02-8M5?
A: The chassis side uses a 96-pin C-type connector, matched with an R-type FTA end.

Q5: Does the 40-channel design of TC-215-02-8M5 include Integral Power conductors?
A: Yes. Power lines are integrated within the 40-channel structure for FTA output.