Overview
Place of Origin: |
USA |
Brand Name: |
ICS TRIPLEX |
Model Number: |
T9833 |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
5-7 days |
Payment Terms: |
T/T |
Supply Ability: |
In stock |
Specifications
|
Model |
T9833 |
|
Product Type |
Analog Input Termination Assembly |
|
Channels |
16 Channel TMR |
|
Input Type |
4–20 mA / 0–20 mA industrial signal |
|
Isolation |
Full electrical isolation |
|
Per Channel Fuse |
50 mA slow-blow miniature fuse |
|
Supply Voltage |
24 VDC (18–32 VDC range) |
|
Channel Isolation Voltage |
±1.5 kVDC withstand for 1 minute |
|
Supported Input Modules |
Up to 3 × T9431 / T9432 Analog Input Modules |
|
System Type |
TMR (Triple Modular Redundant) |
Description
The ICS Triplex T9833 Analog Input Termination Assembly is a high-performance industrial module. It is used in collecting and processing analog signals, ensuring precise control and monitoring across various industrial applications.
Applications
Petroleum Refineries: Connects furnace temperature, reactor pressure, and tank level signals.
LNG Plants: Connects desulfurization pressure, cryogenic temperature, and flow signals.
Thermal Power Plants: Transmits steam pressure, feedwater flow, and turbine vibration data.
Metallurgy and Steel Plants: Collects cooling water flow, furnace thermocouple, and tapping temperature signals.
Advantage
The core advantage of the T9833: Triple Module Redundancy (TMR)
“Two Out of Three” voting mechanism: Distributes one field signal to three input modules; CPU compares data in real time and isolates any faulty module, using the remaining two for decision output.
Zero handover disturbance: Maintains continuous parallel operation; even with single or dual module failure, system keeps uninterrupted computing with zero switching disturbance.
FAQ
Q: How many T9431 or T9432 analog input modules can be installed in the T9833?
A: Up to 3 modules.
Q: What type of analog signals can be received by the T9833?
A: 4–20 mA or 0–20 mA industrial signals.
Q: How many TMR input channels does the T9833 provide?
A: 16 TMR channels.
Q: What fuse is used per channel in the T9833?
A: 50 mA slow-blow micro fuse.
Q: What is the power supply specification and allowed range for the T9833?
A: 24 VDC nominal, 18–32 VDC operating range.