Overview
- Use an approved IM151-1 head station or IM151-7 CPU at the specified version level.
- Install the module on a 30 mm TM-E terminal module and preserve the required shield connections.
- Verify the load-cell signal range, load resistance and permitted cable distance.
- Back up the scale parameters and retain the ET 200S hardware configuration before replacement.
- Confirm whether RS232 commissioning, a TTY display or the SIWAREX IS interface is required.
Siemens · SIWAREX CS
7MH4910-0AA01 Calibratable Weighing Electronics
Siemens 7MH4910-0AA01 is SIWAREX CS calibratable weighing electronics for one scale in SIMATIC ET 200S, with RS232 for PC commissioning and a TTY output for a remote display.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 7MH4910-0AA01 |
| Product Type | Calibratable weighing electronics |
| Core Function | Processes one strain-gauge scale and transfers weight values into SIMATIC ET 200S |
| Application or Compatible Series | SIMATIC ET 200S with IM151-1 Basic, Standard or High Feature, or IM151-7 CPU |
ET 200S Integration
Use an approved IM151-1 head station or IM151-7 CPU and reserve 8 bytes in the peripheral range.
Scale Connection
Match the strain-gauge signal range, load-cell resistance and shielded wiring to the module limits.
Commissioning Interfaces
Use RS232 with SIWATOOL CS for setup and the passive TTY output for a compatible remote display.
Product Overview
Siemens 7MH4910-0AA01 is SIWAREX CS calibratable weighing electronics for one scale in SIMATIC ET 200S, with RS232 for PC commissioning and a TTY output for a remote display.
The module converts one load-cell signal at 50 Hz with 65,535-part internal resolution and a documented error limit of 0.05%. Three measuring ranges, configurable digital filtering and theoretical adjustment support static weighing and force-measurement tasks. An isolated RS232 port connects a commissioning PC, while the isolated TTY transmitter drives a compatible remote display.
Key Functions
High-Resolution Weight Acquisition
The module converts one load-cell signal at 50 Hz with 65,535-part internal resolution and a documented error limit of 0.05%.
Flexible Scale Adjustment
Three measuring ranges, configurable digital filtering and theoretical adjustment support static weighing and force-measurement tasks.
Integrated Setup and Display Links
An isolated RS232 port connects a commissioning PC, while the isolated TTY transmitter drives a compatible remote display.
Official Specifications
| Rated Supply Voltage | 24 V DC from PM-E power module |
|---|---|
| Static Supply Limits | 20.4 to 28.8 V DC |
| Dynamic Supply Limits | 18.5 to 30.2 V DC |
| Non-Periodic Overvoltage | 35 V DC for 500 ms with 50 s recovery |
| Maximum Current Consumption | 150 mA |
| Typical Power Loss | 5 W |
| ET 200S Backplane Current | Typically below 10 mA |
| Calibration Accuracy | Class III, 2000 d (pi = 0.4) |
| Error Limit | At most 0.05% at 20 °C ±10 K |
| Measurement Update Rate | 50 Hz |
| Internal Resolution | 65,535 parts |
| Load-Cell Signal Ranges | 0 to 1, 0 to 2 and 0 to 4 mV/V |
| Load-Cell Excitation | Typically 6 V DC, maximum 68 mA |
| Permitted Load-Cell Resistance | 87 to 4010 Ω with the module or SIWAREX IS interface |
| Low-Pass Filter Cutoff | 0.05 to 5 Hz |
| Average Filter Length | 2 to 255 measured values at 20 ms per value |
| RS232 Interface | 9600 baud, 8 data bits, even parity, 1 stop bit, 15 m maximum, 500 V DC isolation |
| TTY Interface | Passive TxD at 9600 baud, 8E1, 125 m maximum at 20 mA, 25 mA maximum loop current, 500 V DC isolation |
| Module Dimensions | 30 × 80 × 50 mm |
| Technical Weight | 75 g |
Frequently Asked Questions
Which ET 200S head stations can I use with 7MH4910-0AA01?
Use an IM151-1 Basic, Standard or High Feature head station, or an IM151-7 CPU at the specified version level.
How do I connect a commissioning PC to 7MH4910-0AA01?
Connect the PC to the isolated RS232 interface and use SIWATOOL CS for scale setup and diagnostics.
Can 7MH4910-0AA01 drive a remote weight display?
The passive TTY transmitter is intended for a compatible remote display and supports a maximum line length of 125 m at 20 mA.
Which load-cell signals can 7MH4910-0AA01 measure?
The module provides selectable ranges of 0 to 1, 0 to 2 and 0 to 4 mV/V for strain-gauge load cells.
What should I preserve when replacing 7MH4910-0AA01?
Save the scale parameters, record the terminal wiring and retain the ET 200S hardware configuration before removing the module.
Which terminal module is required for 7MH4910-0AA01?
Install it on a 30 mm TM-E terminal module such as 6ES7193-4CG20-0AA0 and maintain the specified shielding connections.
Can 7MH4910-0AA01 be used in hazardous areas?
The module can be used in Zone 2 under the stated installation conditions, while Zone 1 load cells require the optional SIWAREX IS interface.