Siemens SIMOCODE-DP 3UF5011-3AN00-1 Motor Management Basic Unit
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the complete article number and hardware version on the installed device.
- Archive the existing project parameters and label all field connections before replacement.
- Verify the system interface, supply and environmental requirements before commissioning.
SIEMENS SIMOCODE-DP
Siemens SIMOCODE-DP 3UF5011-3AN00-1 Motor Management Basic Unit
SIMOCODE-DP 230 V basic unit with four optocoupler inputs, four relay outputs and PROFIBUS DP communication for motor feeders.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3UF5011-3AN00-1 |
| Product Type | Motor management and protection basic unit |
| Core Function | Monitors, protects and controls a motor feeder |
| Application | SIMOCODE-DP PROFIBUS motor management systems |
Exact Identification
Motor management and protection basic unit for the specified Siemens system.
Core Application
SIMOCODE-DP PROFIBUS motor management systems.
Configuration Focus
Confirm the complete basic-unit suffix, 230 V supply, motor current range, sensor arrangement, PROFIBUS connection and parameter set.
Product Overview
The SIMOCODE-DP basic unit combines motor feeder protection, control inputs, relay outputs and PROFIBUS DP communication.
The official Siemens manual illustrates this 230 V version with four 24 V DC optocoupler inputs, four output relays and a system interface for expansion and service devices.
Key Functions
Primary Function
Monitors, protects and controls a motor feeder.
System Integration
It links motor protection signals and relay outputs to PROFIBUS DP and the SIMOCODE system interface.
Commissioning Focus
Confirm the complete basic-unit suffix, 230 V supply, motor current range, sensor arrangement, PROFIBUS connection and parameter set.
Official Specifications
| Product System | SIMOCODE-DP |
|---|---|
| Device Role | Basic motor management unit |
| Supply Version | 230 V AC |
| Motor Current Range | 6.3 to 25 A |
| Digital Inputs | 4 optocoupler inputs |
| Input Voltage | 24 V DC, internally supplied or external |
| Relay Outputs | 4 |
| Fieldbus | PROFIBUS DP |
| PROFIBUS Connector | 9-pin Sub-D socket |
| Alternative Bus Connection | Pluggable terminal |
| System Interface | Includes RS232 |
| System Interface Devices | Expansion module, operator panel or PC |
| Status LEDs | Ready, Bus and General Fault |
| Local Control | Test / Reset |
| Reset Options | Parameterizable automatic reset and remote reset |
| Sensor Input | Thermistor detector or summation current transformer, version-dependent |
Frequently Asked Questions
What supply version is identified by 3UF5011-3AN00-1?
The illustrated basic unit is the 230 V AC version.
How many control inputs are available on 3UF5011-3AN00-1?
Four optocoupler inputs accept 24 V DC from the internal or an external supply.
How many relay outputs does 3UF5011-3AN00-1 provide?
Four relay outputs are available for the configured motor-control functions.
How does 3UF5011-3AN00-1 connect to PROFIBUS DP?
Use the 9-pin Sub-D interface or the supported pluggable bus terminal.
Which devices can use the system interface on 3UF5011-3AN00-1?
It can connect an expansion module, operator panel or service PC through the system interface.
Can 3UF5011-3AN00-1 be reset remotely?
Reset behavior is parameterizable and a remote reset can be initiated through the bus or an input.
What must be copied before replacing 3UF5011-3AN00-1?
Archive the motor protection parameters, input and output assignments, bus address and reset logic.