- Confirm that the installed rack is SIMATIC S7-400 and provides one suitable supply slot.
- Keep plant DC within the 19.2 to 72 V static and 18.5 to 75.5 V dynamic ranges.
- Keep calculated 5 V and 24 V rack loads below 4 A and 0.5 A.
- Provide the protective conductor and 3 × 1.5 mm² termination required by the cabinet design.
- Ensure the upstream supply accommodates the 18 A, 20 ms inrush pulse.
- Keep ambient temperature within 0 to 60 °C and allow for 16 W of power loss.
- Match optional batteries to the current exact-revision Siemens value and maintenance plan.
Siemens · SIMATIC S7-400 PS 405/407
6ES7405-0DA02-0AA0 PS 405 4 A DC Power Supply Module
Siemens 6ES7405-0DA02-0AA0 is the single-slot PS 405 4 A supply for SIMATIC S7-400 racks. It accepts nominal 24 V, 48 V or 60 V DC plant power and provides isolated, short-circuit-protected backplane power with power-failure buffering and optional battery support.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7405-0DA02-0AA0 |
| Product Type | PS 405 Power Supply Module |
| Core Function | Converts plant DC input into regulated S7-400 rack operating power |
| Application or Compatible Series | SIMATIC S7-400 and the PS 405/407 power-supply family |
DC Input Window
Check both the static and dynamic input-voltage limits against the plant DC system and transient behavior.
Rack Load Budget
Add the 5 V and 24 V backplane demands of every installed S7-400 module before selecting the 4 A supply.
Backup and Protection
Plan optional battery retention, protective-earth connection, isolation and short-circuit behavior as one supply-system design.
Product Overview
Siemens 6ES7405-0DA02-0AA0 is the single-slot PS 405 4 A supply for SIMATIC S7-400 racks. It accepts nominal 24 V, 48 V or 60 V DC plant power and provides isolated, short-circuit-protected backplane power with power-failure buffering and optional battery support.
Operates from nominal 24 V, 48 V or 60 V DC sources and generates the rack’s regulated DC rails. Maintains output for more than 20 ms at a one-second repeat rate and meets NAMUR NE 21 buffering guidance. Provides primary-to-secondary separation, Class I protective-earth construction and short-circuit-protected outputs.
Key Functions
Multi-Rating DC Conversion
Operates from nominal 24 V, 48 V or 60 V DC sources and generates the rack’s regulated DC rails.
Power-Failure Bridging
Maintains output for more than 20 ms at a one-second repeat rate and meets NAMUR NE 21 buffering guidance.
Isolated Protected Distribution
Provides primary-to-secondary separation, Class I protective-earth construction and short-circuit-protected outputs.
Official Specifications
| Static Permissible Input Range | 19.2 to 72 V DC |
|---|---|
| Dynamic Permissible Input Range | 18.5 to 75.5 V DC |
| Rated Input Current | 2 A at 24 V DC; 1 A at 48 V DC; 0.8 A at 60 V DC |
| Maximum Inrush Current | 18 A peak; 20 ms full width at half maximum |
| Rated Output Voltages | 5.1 V DC and 24 V DC |
| Maximum Output Current | 4 A on the 5 V rail; 0.5 A on the 24 V rail |
| Power-Failure Stored-Energy Time | More than 20 ms at a 1 s repeat rate; meets NAMUR NE 21 |
| Typical Active Power Input | 48 W at 24 V DC |
| Typical Power Loss | 16 W |
| Maximum Backup Current When Unpowered | 100 µA |
| Optional Backup Batteries | 2 × lithium AA, 3.6 V/2.2 Ah in the current Siemens technical data |
| Required Rack Slots | 1 |
| Primary-to-Secondary Isolation | Yes |
| Equipment Protection Class | Class I with protective conductor |
| Overvoltage Category | II |
| Pollution Degree | 2 |
| Test Voltages | 700 V DC secondary-to-PE; 2,200 V DC primary-to-secondary/PE |
| Electrical Connection | 3 × 1.5 mm² solid or stranded conductors with end sleeves; 3 to 9 mm external cable diameter |
| Operating Ambient Temperature | 0 to 60 °C |
| Physical Data | 25 × 290 × 217 mm (W × H × D); approximately 760 g |
Frequently Asked Questions
Which DC supply voltages can feed 6ES7405-0DA02-0AA0?
The module accepts nominal 24 V, 48 V or 60 V DC within a static range of 19.2 to 72 V DC.
How much rack current can 6ES7405-0DA02-0AA0 deliver?
It supplies up to 4 A on the 5 V backplane rail and 0.5 A on the 24 V rail.
Can 6ES7405-0DA02-0AA0 bridge a brief input-voltage dip?
The stored-energy reserve holds the outputs for more than 20 ms at a one-second repeat rate and meets NAMUR NE 21.
Which backup batteries should I fit in 6ES7405-0DA02-0AA0?
Current Siemens technical data specifies two lithium AA cells rated 3.6 V and 2.2 Ah each.
How much rack space does 6ES7405-0DA02-0AA0 require?
The supply occupies one 25 mm-wide rack slot.
Which power cable can I terminate on 6ES7405-0DA02-0AA0?
Use three 1.5 mm² solid or stranded conductors with end sleeves and an overall cable diameter of 3 to 9 mm.
What should I compare before replacing 6ES7405-0DA02-0AA0?
Match the 24/48/60 V DC input class, 4 A backplane rating, single-slot form, protective-earth arrangement and rack load budget.