Siemens SIMATIC S7-1500 6ES7511-1AK01-0AB0 CPU 1511-1 PN
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Install only in a compatible SIMATIC S7-1500 system with sufficient backplane and supply power.
- Match the AK01 hardware generation and installed firmware exactly.
- Use TIA Portal V14 or a later release that supports this hardware-catalog entry.
- Keep the SIMATIC Memory Card with its verified project and load-memory contents.
- Restore the PROFINET device name, IP configuration, port topology and IO-device relationships.
- Check the configured address areas, process-image partitions and retentive-data allocation.
- Do not substitute AK02 or AK03 specifications without a documented migration review.
Siemens · SIMATIC S7-1500
6ES7511-1AK01-0AB0 CPU 1511-1 PN
Siemens 6ES7511-1AK01-0AB0 is the SIMATIC S7-1500 CPU 1511-1 PN with separate 150 KB program and 1 MB data work-memory areas. Its integrated PROFINET interface provides two RJ45 ports with an internal switch for controller and device communication. This hardware generation is documented with firmware V2.0 and engineering in TIA Portal V14. The CPU requires a SIMATIC Memory Card, so firmware, hardware catalog, memory-card contents, network identity and project backup must be verified before replacement.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7511-1AK01-0AB0 |
| Product Type | SIMATIC S7-1500 Programmable Controller CPU |
| Core Function | Executes machine and process automation logic with integrated PROFINET communication |
| Application or Compatible Series | SIMATIC S7-1500 automation systems |
Exact CPU Revision
Match the AK01 hardware generation and installed firmware rather than transferring AK02 or AK03 performance data.
Memory and Project
Keep a verified TIA Portal backup and confirm the SIMATIC Memory Card before removing the controller.
PROFINET Commissioning
Record the device name, IP settings, both port assignments, topology and every IO-device relationship.
Product Overview
Siemens 6ES7511-1AK01-0AB0 is the SIMATIC S7-1500 CPU 1511-1 PN with separate 150 KB program and 1 MB data work-memory areas. Its integrated PROFINET interface provides two RJ45 ports with an internal switch for controller and device communication. This hardware generation is documented with firmware V2.0 and engineering in TIA Portal V14. The CPU requires a SIMATIC Memory Card, so firmware, hardware catalog, memory-card contents, network identity and project backup must be verified before replacement.
Processes Boolean, word, fixed-point and floating-point instructions with separate program and data work memory. Two RJ45 ports on one PROFINET interface support line and network topologies. The integrated display and operating keys support identification, status and commissioning tasks at the cabinet.
Key Functions
S7-1500 Program Execution
Processes Boolean, word, fixed-point and floating-point instructions with separate program and data work memory.
Integrated PROFINET Switch
Two RJ45 ports on one PROFINET interface support line and network topologies.
Local Display and Diagnostics
The integrated display and operating keys support identification, status and commissioning tasks at the cabinet.
Official Specifications
| Hardware and Firmware Baseline | Hardware functional status FS03; firmware V2.0 |
|---|---|
| Engineering Software | TIA Portal V14 |
| Supply Voltage | 24 V DC; permissible range 19.2 to 28.8 V |
| Power-Failure Buffering | 5 ms |
| Rated and Inrush Current | 0.7 A rated; 1.9 A inrush; I²t 0.02 A²s |
| Backplane and Incoming Power | 5.5 W backplane supply; 10 W incoming power |
| Typical Power Loss | 5.7 W |
| Program and Data Work Memory | 150 KB program; 1 MB data |
| Maximum Load Memory | 32 GB with SIMATIC Memory Card |
| Memory Card Slots | 1 SIMATIC Memory Card slot; card required |
| Bit, Word and Fixed-Point Times | 60 ns, 72 ns and 96 ns per instruction |
| Floating-Point Operation Time | 384 ns per instruction |
| Total Block Elements | Maximum 4,000 |
| Maximum Data Block Size | 1 MB; 64 KB for absolute-addressed blocks |
| S7 Counters and Timers | 2,048 counters and 2,048 timers |
| Maximum Retentive Data | 128 KB total; 88 KB usable for flags, timers, counters, data blocks and technology data |
| I/O Address Area | 32 KB inputs and 32 KB outputs |
| Process Image Partitions | 32 |
| PROFINET Physical Interface | 1 interface with 2 RJ45 ports and integrated switch |
| PROFINET IO Capacity | Maximum 128 IO devices; maximum 64 IRT devices |
Frequently Asked Questions
Which TIA Portal version is specified for 6ES7511-1AK01-0AB0?
Use TIA Portal V14 or a later release that retains the exact AK01 hardware-catalog entry.
Does 6ES7511-1AK01-0AB0 require a SIMATIC Memory Card?
Yes, the controller has one card slot and requires the card for operation.
How much work memory is available in 6ES7511-1AK01-0AB0?
The CPU provides 150 KB for the program and 1 MB for data.
How many PROFINET ports are built into 6ES7511-1AK01-0AB0?
The integrated interface has two RJ45 ports connected through an internal switch.
How many PROFINET IO devices can 6ES7511-1AK01-0AB0 control?
The documented maximum is 128 IO devices, including up to 64 IRT devices.
What supply should be provided for 6ES7511-1AK01-0AB0?
Use 24 V DC within the permissible 19.2 to 28.8 V range and account for the specified current and power demand.
What should I back up before replacing 6ES7511-1AK01-0AB0?
Save the TIA Portal project and record the firmware, memory-card contents, device name, IP parameters, topology and I/O assignments.