Overview
- Verify a compatible PCI or PCI-X host interface.
- Confirm the configured PROFIBUS data rate and station addresses.
- Back up communication settings before removing the installed card.
SIEMENS SIMATIC NET · PROFIBUS COMMUNICATION PROCESSOR
A5E00200965-02 CP 5614 A2 PROFIBUS PCI Communication Processor
Siemens A5E00200965-02 identifies a CP 5614 A2 communication processor that connects a PC to PROFIBUS and supports simultaneous DP master and DP slave communication.
At a Glance
| Brand | Siemens |
|---|---|
| Model | A5E00200965-02 |
| Product Type | CP 5614 A2 communication processor |
| Core Function | Connects a PC to PROFIBUS as DP master and DP slave |
| Application or Compatible Series | SIMATIC NET PROFIBUS PC communication |
Host Integration
Uses a PCI or PCI-X host interface for SIMATIC NET PC communication.
Dual PROFIBUS Role
Separate controllers support simultaneous DP master and DP slave operation.
Engineering Check
Match the host slot, PROFIBUS network and connector configuration before replacement.
Product Overview
The CP 5614 A2 is a SIMATIC NET communication processor for integrating an industrial PC into PROFIBUS networks. Its two network connectors and separate master and slave controllers support hierarchical network structures and program-controlled data transfer between the two communication paths.
The short PCI card supports plug-and-play operation, standard PROFIBUS transmission rates and a broad DP capacity. Replacement planning should preserve the host bus environment, PROFIBUS addressing, connector assignment and the existing SIMATIC NET configuration.
Key Functions
Simultaneous DP Operation
Operates as a DP master and DP slave through dedicated PROFIBUS controllers.
PC Network Connection
Provides a PCI or PCI-X interface for SIMATIC NET PROFIBUS communication.
Hierarchical Data Exchange
Transfers data under program control between master-side and slave-side networks.
Official Specifications
| Card Format | Short PCI PC card |
|---|---|
| Dimensions | 107 × 18 × 168 mm |
| Net Weight | 120 g |
| PCI Standard | PCI V2.2 with plug-and-play support |
| Rated Supply | 5 V DC; permissible range 4.75–5.25 V |
| Typical Slot Current | 0.9 A |
| Host Bus Interface | PCI or PCI-X, 3.3 V or 5 V, 32 bit, 33 or 66 MHz |
| PROFIBUS Connectors | Two 9-pin D-sub female connectors with screw locking |
| Physical Transmission | Electrically isolated RS-485 within SELV limits |
| Master Controller | ASPC2R ST E2a |
| Slave Controller | DPC31 |
| PROFIBUS Data Rate | 9.6 kbit/s to 12 Mbit/s |
| EMC Emission Class | Class B to EN 55022 and FCC Class B |
| Signal-Line Surge Immunity | ±2 kV to EN 61000-4-5 |
| Contact-Discharge Immunity | ±6 kV to IEC 61000-4-2 |
| Storage and Transport Temperature | −40 to +70 °C |
| Operating Relative Humidity | 85% at 30 °C, non-condensing |
| DP Slave Process Data | 244 bytes each for input, output and diagnostic data |
| DP Master Capacity | Up to 124 DP slaves |
| DPC2 Connections | Up to 56 |
Frequently Asked Questions
How should A5E00200965-02 be installed in an industrial PC?
Install the short PCI card in a compatible PCI or PCI-X slot, secure the bracket and connect the PROFIBUS cables only after the PC is isolated.
Which PROFIBUS data rates can A5E00200965-02 use?
The communication processor supports transmission rates from 9.6 kbit/s through 12 Mbit/s.
Can A5E00200965-02 operate as both a DP master and a DP slave?
The two-controller architecture allows simultaneous DP master and DP slave operation.
Which network connectors fit A5E00200965-02?
Use two 9-pin D-sub PROFIBUS connectors with screw locking for the network interfaces.
What should engineers back up before replacing A5E00200965-02?
Preserve the PC-station project, master and slave addresses, bus rates, connector assignments and SIMATIC NET access-point settings.
How much process data can A5E00200965-02 exchange through its slave interface?
The slave interface supports 244 bytes each of input data, output data and diagnostic data.
Which host-slot details matter when selecting A5E00200965-02?
Use a supported 32-bit PCI or PCI-X slot with the permitted 3.3 V or 5 V signaling and 33 or 66 MHz bus frequency.