Overview
- Use in a supported S5-115U, S5-135U or S5-155U system.
- Match the exact CP 5431 FMS/DP article number.
- Preserve the COM 5431 FMS/DP project and station database.
- Confirm the electrical or optical PROFIBUS topology.
- Verify the required 5 V supply when a BT12M is installed.
- Restore all FMS connections, DP assignments and bus timing.
- Treat migration to newer hardware as a separately engineered conversion.
Siemens · SIMATIC NET / SIMATIC S5
6GK1543-1AA01 CP 5431 FMS/DP PROFIBUS Processor
Siemens 6GK1543-1AA01 is the SIMATIC NET CP 5431 FMS/DP communications processor for PROFIBUS integration of compatible SIMATIC S5 systems. It provides PROFIBUS master functions, FMS data exchange and an integrated optical interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GK1543-1AA01 |
| Product Type | SIMATIC S5 PROFIBUS Communication Processor |
| Core Function | Connects SIMATIC S5 controllers to PROFIBUS FMS and DP networks |
| Application or Compatible Series | SIMATIC S5-115U, S5-135U and S5-155U systems |
Exact FMS/DP Identity
Match the complete 1AA01 article number and do not substitute another CP 5431 execution.
S5 System Check
Confirm the installed S5-115U, S5-135U or S5-155U rack and the assigned processor slot.
Project Preservation
Back up the COM 5431 FMS/DP configuration, station addresses, bus timing and application connections.
Product Overview
Siemens 6GK1543-1AA01 is the SIMATIC NET CP 5431 FMS/DP communications processor for PROFIBUS integration of compatible SIMATIC S5 systems. It provides PROFIBUS master functions, FMS data exchange and an integrated optical interface.
Controls compatible PROFIBUS stations from a SIMATIC S5 automation system. Transfers structured application data through PROFIBUS FMS services. Supports optical network integration with the compatible PROFIBUS optical components.
Key Functions
PROFIBUS Master Operation
Controls compatible PROFIBUS stations from a SIMATIC S5 automation system.
FMS Structured Data Exchange
Transfers structured application data through PROFIBUS FMS services.
Integrated Optical Connection
Supports optical network integration with the compatible PROFIBUS optical components.
Official Specifications
| Communication Protocols | PROFIBUS FMS and PROFIBUS DP |
|---|---|
| PROFIBUS Role | Master |
| Compatible Controller Families | SIMATIC S5-115U, S5-135U and S5-155U |
| Engineering Package | COM 5431 FMS/DP |
| Optical Interface | Integrated |
| Compatible Optical Component | PROFIBUS optical link plug |
| Bus Terminal Compatibility | BT12M when its required 5 V supply is available |
| BT12M Supply Requirement | 90 mA at 5 V |
| Data Service | FMS transfer of structured data in a system-neutral format |
| Lower-Layer Access | FDL free layer-2 access for applicable S5 communication programs |
Frequently Asked Questions
Which SIMATIC S5 systems can use 6GK1543-1AA01?
The processor is intended for compatible S5-115U, S5-135U and S5-155U stations.
Which engineering package configures 6GK1543-1AA01?
Use COM 5431 FMS/DP and retain the complete original station project.
Can 6GK1543-1AA01 operate as a PROFIBUS master?
Yes, the processor provides master communication for supported FMS and DP configurations.
Does 6GK1543-1AA01 support optical PROFIBUS cabling?
Yes, an integrated optical interface supports the approved optical network components.
What must be checked before connecting a BT12M to 6GK1543-1AA01?
Confirm that the interface can provide the required 90 mA at 5 V for the bus terminal.
What project data should I save before replacing 6GK1543-1AA01?
Back up addresses, bus timing, FMS connections, DP assignments and application data mappings.
Can a modern PROFIBUS card replace 6GK1543-1AA01 directly?
No, migration requires new hardware integration, engineering conversion and validation of every FMS or DP connection.