Overview
- Confirm the permitted country setting and approved antenna for the installation.
- Record the wireless security profile and PROFIBUS network parameters.
- Check equipotential bonding between the supply, antenna ground and PROFIBUS equipment.
SIEMENS SIMATIC NET
Siemens SIMATIC NET 6GK1417-5AB00 IWLAN/PB Link PN IO Gateway
Compact IWLAN/PB Link PN IO gateway with IEEE 802.11a/b/g/h/i wireless support and PROFIBUS rates up to 12 Mbit/s.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GK1417-5AB00 |
| Product Type | IWLAN to PROFIBUS network gateway |
| Core Function | Links PROFIBUS devices through an industrial wireless LAN |
| Application | SIMATIC NET IWLAN and PROFIBUS DP networks |
Exact Identification
IWLAN to PROFIBUS network gateway for the specified Siemens system.
Core Application
SIMATIC NET IWLAN and PROFIBUS DP networks.
Configuration Focus
Verify the complete order number, country-specific radio approval, antenna, firmware, PROFIBUS baud rate and 24 V DC supply arrangement.
Product Overview
The IWLAN/PB Link PN IO forms a network transition between Industrial Wireless LAN and PROFIBUS.
The hardware version covered by the official instructions provides one R-SMA antenna socket, one 9-pin PROFIBUS D-sub interface and redundant 24 V DC supply inputs.
Key Functions
Primary Function
Links PROFIBUS devices through an industrial wireless LAN.
System Integration
It combines one R-SMA IWLAN antenna interface with one 9-pin PROFIBUS connector.
Commissioning Focus
Verify the complete order number, country-specific radio approval, antenna, firmware, PROFIBUS baud rate and 24 V DC supply arrangement.
Official Specifications
| Device Type | IWLAN/PB Link PN IO |
|---|---|
| Covered Hardware Version | 04 |
| Covered Firmware | V1.3 or later |
| Wireless Standards | IEEE 802.11a/b/g/h/i |
| Wireless Data Rate | 1 to 54 Mbit/s |
| PROFIBUS Data Rate | 9.6 kbit/s to 12 Mbit/s |
| PROFIBUS Segment Length | 20 m maximum without repeater |
| Wireless Interface | R-SMA antenna socket |
| PROFIBUS Interface | 9-pin D-sub socket |
| Supply Voltage | 20.4 to 28.8 V DC, two inputs |
| Typical Current Consumption | Approximately 0.3 A at 24 V DC |
| Power Loss | 6.5 W |
| Dimensions | 90 x 132 x 75 mm |
| Weight | Approximately 300 g |
| Operating Temperature | 0 to +60 °C |
| Storage / Transport Temperature | -40 to +70 °C |
| Relative Humidity | Up to 95% at 25 °C |
| Operating Altitude | Up to 2000 m |
Frequently Asked Questions
What network transition does 6GK1417-5AB00 provide?
It connects a PROFIBUS segment to an Industrial Wireless LAN infrastructure.
Which antenna connection is used by 6GK1417-5AB00?
The wireless interface uses an R-SMA socket for a suitable approved antenna.
What PROFIBUS rates can 6GK1417-5AB00 handle?
Supported rates extend from 9.6 kbit/s up to 12 Mbit/s.
Does 6GK1417-5AB00 accept redundant power feeds?
Yes, the device provides two isolated supply inputs within the specified 24 V DC range.
Which radio standards are available on 6GK1417-5AB00?
The supported set includes IEEE 802.11a, b, g, h and i.
How should country settings be handled on 6GK1417-5AB00?
Select the actual country of operation so the radio configuration complies with local approvals.
What must be archived before replacing 6GK1417-5AB00?
Record the wireless profile, PROFIBUS parameters, firmware level and device addressing.