Overview
- Match the complete SIKOSTART power-section order number and control-supply suffix.
- Keep the cooling-fan supply active for the specified run-on period after stopping.
- Record DIP-switch settings, control terminals and fault/status wiring before removal.
SIEMENS SIKOSTART
Siemens SIKOSTART 3RW3950-6DC48 Control Section for 3RW34 Soft Starters
230 V AC control section for compatible SIKOSTART 3RW34 soft starters used with three-phase induction motors.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 3RW3950-6DC48 |
| Product Type | Soft-starter control assembly |
| Core Function | Controls motor starting and stopping sequences |
| Application | SIKOSTART 3RW34..-0DC4 soft starters |
Compatibility Match
Use only with the specified 3RW34..-0DC4 soft-starter power section.
Control Wiring
Restore the control supply, start/stop circuit and status wiring exactly as recorded.
Cooling Sequence
Preserve the fan supply and required run-on time after the stop command.
Product Overview
This control section is intended for SIKOSTART 3RW34 soft starters with the matching -0DC4 control-supply version.
Within the supported 3RW34 system, DSP control and SCR phase control provide single-ramp starting, soft stopping and fault detection for three-phase induction motors.
Key Functions
Soft-Start Control
Controls the compatible SIKOSTART power section to reduce mechanical and electrical stress during motor acceleration.
Soft-Stop and Fault Handling
Provides the supported stop ramp and fault-detection functions of the 3RW34 system.
Cooling Coordination
Keeps the built-in fans energized for the required period after the ON command is removed.
Official Specifications
| Control Supply Voltage | 230 V AC |
|---|---|
| Motor Type | Three-phase AC induction motor |
| Control Method | Single-ramp phase control |
| Power-Switching Technology | SCR |
| Control Processing | DSP microprocessor |
| Start and Stop Functions | Soft start and soft stop parameters |
| Fault Monitoring | Integrated fault detection |
| Start/Stop Command Terminals | A1 and A2 |
| Cooling-Fan Supply Terminals | X1 and X2 |
| Required Fan Run-On After Stop | Approximately 60 minutes |
| Minimum Restart Delay if Fan Supply Is Removed at Stop | Approximately 3 hours |
| Packaging Dimensions | 231 × 55 × 165 mm |
| Net Weight | 0.335 kg |
Frequently Asked Questions
Which soft starters are compatible with 3RW3950-6DC48?
Use the control section with the matching SIKOSTART 3RW34..-0DC4 version.
What control voltage is required for 3RW3950-6DC48?
The control section is specified for 230 V AC.
Which terminals carry the start and stop command for 3RW3950-6DC48?
The ON command is connected through terminals A1 and A2 in the supported wiring arrangement.
Why must the fan supply remain energized after stopping 3RW3950-6DC48?
The built-in fans require an approximately 60-minute run-on period so the power electronics cool sufficiently.
What happens if I remove the fan supply immediately after stopping 3RW3950-6DC48?
The soft starter may require approximately three hours before it can restart at the specified ratings.
Can 3RW3950-6DC48 provide a soft-stop function?
Yes, the compatible SIKOSTART system includes adjustable soft-start and soft-stop parameters.
What should I label before replacing 3RW3950-6DC48?
Label the control supply, start/stop circuit, status contacts, fan supply and every terminal connection.