Siemens QBM81-3 Differential Pressure Switch, 20–300 Pa
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use air or nonaggressive gases within the permissible pressure and temperature limits.
- Prefer vertical mounting for direct correspondence with the calibrated scale.
- Mount above the pressure takeoff points and route tubing upward without loops.
- Observe contact voltage, resistive or inductive current ratings and external protection requirements.
- Use the supplied FK-PZ3 kit or select additional duct probes separately.
QBM81-3 Differential Pressure Switch, 20–300 Pa
An adjustable 20–300 Pa pressure switch for air and nonaggressive gases, supplied with a mounting bracket, duct adaptors and tubing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | QBM81-3 |
| Product Type | Adjustable differential pressure switch |
| Core Function | Switches an electrical contact in response to air-pressure difference |
| Application | HVAC air-filter, airflow and fan-belt monitoring |
Low-pressure switching
Set the upper switching point within the 20–300 Pa range.
Changeover contact
A single-pole changeover switch provides lower- and higher-pressure contact states.
Duct connection kit
Two duct adaptors and 2 m of tubing are supplied with the switch.
Product Overview
QBM81-3 uses a spring-loaded diaphragm to operate a changeover contact when the pressure difference reaches the selected switching point.
The switch supports filter and airflow supervision in ventilation systems and can detect a torn fan belt through the associated change in pressure; the setpoint knob is located beneath the cover.
Key Functions
Adjustable pressure supervision
An engraved scale and setpoint knob allow the upper switching point to be selected between 20 and 300 Pa.
Filter and fan monitoring
Connect the positive port upstream and the negative port downstream of a filter, or use the fan-side pressure connections for airflow monitoring.
Automatic contact reset
The single-pole changeover mechanism resets automatically and has a factory-set switching differential.
Official Specifications
| Adjustable pressure range | 20–300 Pa (0.2–3 mbar) |
|---|---|
| Switch construction | Single-pole changeover; multi-layer contact |
| Minimum contact load | 0.01 A at 24 V AC/DC |
| Maximum resistive contact load | 5 A at 250 V AC |
| Maximum inductive contact load | 3 A at 250 V AC; cos φ > 0.6 |
| Switching differential and reset | Factory-set differential; automatic reset |
| Mechanical switching life | More than 1,000,000 cycles |
| Switching-point reproducibility | Better than ±2.5 Pa over the 20–300 Pa range |
| Maximum unilateral overload at −30 to +75 °C | 7,500 Pa |
| Maximum unilateral overload at −30 to +85 °C | 5,000 Pa |
| Housing protection | IP54 |
| Operating ambient temperature | −30 to +85 °C |
| Storage temperature | −40 to +85 °C |
| Ambient humidity | Less than 90% RH, non-condensing |
| Electrical connection | Three screw terminals; PG11 cable gland |
| Pressure connection outside diameter | 6.2 mm |
| Housing and cover materials | Glass-fiber-reinforced polycarbonate housing; polycarbonate cover |
| Diaphragm material | Silicone, low-swell and emission-free |
| Horizontal mounting setpoint shift | Cover upward: +11 Pa; cover downward: −11 Pa |
| Weight including packaging | 0.19 kg with mounting bracket |
Frequently Asked Questions
Which pressure range can be adjusted on QBM81-3?
The upper switching point is adjustable from 20 to 300 Pa using the knob beneath the cover.
How should the two pressure lines be connected to QBM81-3 for filter monitoring?
Connect the higher-pressure port upstream of the filter and the lower-pressure port downstream.
Will horizontal installation change the setpoint of QBM81-3?
Relative to the vertically calibrated scale, the switching point rises by 11 Pa with the cover upward and falls by 11 Pa with the cover downward.
Can the pressure tubing for QBM81-3 be longer than two metres?
Longer tubing is permitted, but tubing beyond two metres increases the response time.
Which duct connection parts are delivered with QBM81-3?
The supplied connection kit contains two duct adaptors, four fixing screws and two metres of tubing.
Does QBM81-3 need an external protective device for its supply wiring?
External preliminary protection is required because the switch has no internal fuse.
Which contact pair indicates the higher-pressure state on QBM81-3?
Terminals 1 and 3 close for the higher-pressure state, while terminals 1 and 2 correspond to the lower-pressure state.