Siemens SIMATIC ET 200X 6ES7144-1GB31-0XB0 EM 144 AI 2 Analog Input Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use only in an approved SIMATIC ET 200X station configuration.
- Maintain the specified shielded-cable routing and 30 m maximum length.
- Restore every channel range, limit and diagnostic parameter before process operation.
Siemens · SIMATIC ET 200X
6ES7144-1GB31-0XB0 EM 144 AI 2 ±20 mA Analog Input Module
Siemens 6ES7144-1GB31-0XB0 is the SIMATIC ET 200X EM 144 analog input module with two ±20 mA current channels, 12-bit-plus-sign resolution, diagnostics, limit monitoring and hardware interrupts.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7144-1GB31-0XB0 |
| Product Type | Rugged two-channel analog current input module |
| Core Function | Measures two bipolar current signals in an ET 200X field station |
| Application or Compatible Series | SIMATIC ET 200X analog measurement systems |
Signal Range
Match both channels to the configured ±20 mA current range.
Shielding
Retain the documented shield connection and maximum cable length.
Alarm Parameters
Restore channel limits, diagnostics and hardware-interrupt settings.
Product Overview
Siemens 6ES7144-1GB31-0XB0 is the SIMATIC ET 200X EM 144 analog input module with two ±20 mA current channels, 12-bit-plus-sign resolution, diagnostics, limit monitoring and hardware interrupts.
Acquires two independent ±20 mA analog process signals. Detects configured short circuit, wire break, overflow and underflow conditions. Generates channel alarms for configured measurement limits and events.
Key Functions
Two Bipolar Current Inputs
Acquires two independent ±20 mA analog process signals.
Diagnostic Monitoring
Detects configured short circuit, wire break, overflow and underflow conditions.
Limit and Hardware Alarms
Generates channel alarms for configured measurement limits and events.
Official Specifications
| Analog Input Channels | 2 |
|---|---|
| Input Signal Range | ±20 mA |
| Input Resistance | 25 Ω |
| Transmitter Connection | Four-wire transmitter |
| Conversion Resolution | 12 bits plus sign |
| Overrange | 17.5% |
| Integration Time | 16.7 or 20 ms |
| Interference Suppression | 50 or 60 Hz |
| Shielded Cable Length | Maximum 30 m |
| Operational Error Limit | 1.2% |
| Channel Isolation | Inputs not galvanically isolated from each other |
| Diagnostics | Short circuit, wire break, overflow and underflow |
| Limit Monitoring | Configurable |
| Hardware Interrupt | Configurable |
| Status Indication | Red SF group-error LED |
Frequently Asked Questions
Which current signals can I connect to 6ES7144-1GB31-0XB0?
Use two compatible bipolar current signals within the configured ±20 mA range.
What resolution does 6ES7144-1GB31-0XB0 provide?
The converter resolves the measured value with 12 bits plus sign.
How long may the field cable be for 6ES7144-1GB31-0XB0?
Use shielded analog cable no longer than 30 m.
Can 6ES7144-1GB31-0XB0 report a broken signal wire?
The module supports wire-break and short-circuit diagnostics for the configured channel.
How do I reduce mains-frequency interference on 6ES7144-1GB31-0XB0?
Set the integration and interference-suppression parameters for the applicable 50 or 60 Hz environment.
What should I save before replacing 6ES7144-1GB31-0XB0?
Record the channel ranges, limit values, alarm settings, cable shields and terminal assignments.
What should I verify after installing 6ES7144-1GB31-0XB0?
Check both measured currents, scaling, diagnostics, limit alarms and the SF indicator.