Siemens C79458-L8001-A77 SIMATIC NET CP 5614 PROFIBUS Communication Card
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Retain the full C79458-L8001-A77 hardware identifier when ordering.
- Match the DP-Base, DP-Lib, FMS or S7 application interface before replacement.
- Allow for the 124-slave limit and the per-slave process-data lengths.
- Include the required software licenses in the order scope.
SIEMENS SIMATIC NET
C79458-L8001-A77 SIMATIC NET CP 5614 PROFIBUS Communication Card
PROFIBUS DP master and slave communication for PC applications, with direct process-image access and a separate slave function.
At a Glance
| Brand | Siemens |
|---|---|
| Model | C79458-L8001-A77 |
| Product Type | CP 5614 communication card |
| Core Function | PC communication with PROFIBUS DP networks |
| Compatible Series / Application | Industrial PC and PROFIBUS DP systems |
DP master
Connect certified PROFIBUS DP slaves to a PC application.
DP slave
Integrate the PC with a certified upstream DP master.
Software matching
Choose DP-Base or the licensed communication package required by the application.
Product Overview
C79458-L8001-A77 provides CP 5614 communication functions for PROFIBUS PC applications, combining DP master operation with a DP slave section.
The DP-Base interface gives applications access to process data, while optional DP, FMS and S7 software packages support their respective communication services.
Key Functions
Master and slave integration
The DP master works with certified DP slaves, and the slave section can connect to certified DP master stations.
Process-image access
PC applications can read the process image at up to 3 Kbytes/ms and write at up to 8 Kbytes/ms.
Bus parameter adaptation
The DP slave section can adapt to the bus parameters of an existing attached PROFIBUS network.
Official Specifications
| PROFIBUS transmission rates | 9.6, 19.2, 45.45, 93.75, 187.5 and 500 kbit/s; 1.5, 3, 6 and 12 Mbit/s |
|---|---|
| DP slave capacity | Up to 124 slaves |
| DP data lengths per slave | Up to 244 bytes each for inputs, outputs and diagnostics |
| Concurrent DPC1 jobs | One read/write job per slave |
| Concurrent DPC2 connections | Up to 48 read/write connections |
| Process-image read performance | 3 Kbytes/ms |
| Process-image write performance | 8 Kbytes/ms |
| Average signal propagation | 50 µs plus bus propagation time |
| Maximum slave signal propagation | 100 µs plus bus propagation time |
| Parallel CP operation | Up to four CP 5613/CP 5614 modules |
| Parallel protocol operation | Up to two protocols |
Frequently Asked Questions
Can I connect C79458-L8001-A77 to an existing PROFIBUS master?
The DP slave section can operate with certified DP masters and adapt to the attached network’s bus parameters.
How many field devices can I address from C79458-L8001-A77?
The DP master supports up to 124 DP slaves.
Do I need a separate license for DP-Base operation with C79458-L8001-A77?
DP operation through the DP-Base programming interface and purely FDL operation do not require a product license.
Which optional software needs licensing for C79458-L8001-A77?
The DP-5613, FMS-5613 and S7-5613 products require their respective licenses.
Can several applications use C79458-L8001-A77 in one PC?
Supported software versions allow several application programs to use the same CP simultaneously.
How much cyclic data can each slave exchange through C79458-L8001-A77?
Each slave can have up to 244 input bytes and 244 output bytes.
Can I run more than one protocol on C79458-L8001-A77?
A maximum of two communication protocols can operate simultaneously.