Siemens 6SN1114-0NB00-0AA2 SIMODRIVE 611 Universal PROFIBUS-DP2 Option Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use control-board software version 3.1 or later for the DP2 option.
- Set P0918 for the slave address, P0700 for the required drive operating mode and P0875 for slave activation.
- Tighten the option retaining and shield-contact screws to no more than 0.8 Nm.
- Keep the master and all bus participants at the same transmission rate, applying the 1.5 Mbaud limit when OLP optical link plugs are fitted.
6SN1114-0NB00-0AA2 SIMODRIVE 611 Universal PROFIBUS-DP2 Option Module
PROFIBUS-DP2 option for cyclic drive data, acyclic parameter access and commissioning through SimoCom U.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SN1114-0NB00-0AA2 |
| Product Type | PROFIBUS-DP2 option board |
| Core Function | Drive communication with a PROFIBUS DP master |
| Application | SIMODRIVE 611 universal control boards |
Cyclic command exchange
PKW and PZD communication carries drive parameters, commands and operating feedback between the drive and DP master.
Acyclic engineering access
DP/V1 services and SimoCom U over PROFIBUS provide parameter and commissioning access alongside process communication.
Automatic bus-rate detection
The slave detects the configured PROFIBUS transmission rate at power-on, while its front diagnostic LED indicates communication state.
Product Overview
6SN1114-0NB00-0AA2 connects a SIMODRIVE 611 universal control board to a PROFIBUS DP master as a slave station, carrying cyclic process data and parameter traffic through the drive communication interface.
The DP2 option uses a DPC31 ASIC without a PLL and supports control-board software from version 3.1; its communication capabilities include acyclic DP/V1 access and SimoCom U operation over PROFIBUS.
Key Functions
Cyclic command exchange
PKW and PZD communication carries drive parameters, commands and operating feedback between the drive and DP master.
Acyclic engineering access
DP/V1 services and SimoCom U over PROFIBUS provide parameter and commissioning access alongside process communication.
Automatic bus-rate detection
The slave detects the configured PROFIBUS transmission rate at power-on, while its front diagnostic LED indicates communication state.
Official Specifications
| Communication ASIC | DPC31 without PLL |
|---|---|
| Cyclic data channels | PKW parameter channel and PZD process data |
| Acyclic communication | DP/V1 services |
| Electrical bus rates | 9.6, 19.2, 93.75, 187.5 and 500 kbaud; 1.5, 3, 6 and 12 Mbaud |
| Transmission-rate selection | Automatic detection at power-on |
| Optical link plug limit | 1.5 Mbaud maximum with OLP optical link plugs |
| Drive bus connection | X423 PROFIBUS connector |
| Local diagnostic indication | Bicolor LED for option activation and cyclic communication status |
Frequently Asked Questions
Can 6SN1114-0NB00-0AA2 replace an older DP1 option?
The DP2 board can replace a DP1 option when the SIMODRIVE control board runs software version 3.1 or later.
Which drive data can I exchange cyclically through 6SN1114-0NB00-0AA2?
The connection provides PKW parameter traffic and PZD process data for drive commands and feedback.
Can I commission the drive through 6SN1114-0NB00-0AA2 using SimoCom U?
SimoCom U can communicate with the drive over PROFIBUS through the DP2 option.
How is the bus transmission rate selected on 6SN1114-0NB00-0AA2?
The option automatically detects the PROFIBUS transmission rate when power is applied.
Will an optical link plug retain the 12 Mbaud capability of 6SN1114-0NB00-0AA2?
An OLP optical link plug limits the connection to a maximum of 1.5 Mbaud.
Where do I assign the PROFIBUS station address for 6SN1114-0NB00-0AA2?
Set the slave address with drive parameter P0918 and align it with the master configuration.
What should I inspect if 6SN1114-0NB00-0AA2 has no cyclic communication?
Inspect the slave address, bus connection, termination and connected bus cables when the option is enabled but cyclic data exchange is absent.