Siemens 6SL3211-0AB12-5UB0 SINAMICS G110 0.25 kW USS Inverter
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use a motor matched to the 0.25 kW drive power and 1.7 A output current.
- Configure the USS link and digital inputs for the selected command and setpoint sources.
- Select an external EMC filter when required for the installation.
- Observe motor-cable limits, thermal derating and the recommended 10 A mains fuse.
6SL3211-0AB12-5UB0 SINAMICS G110 0.25 kW USS Inverter
A 0.25 kW unfiltered G110 inverter with single-phase 200–240 V input and an RS485 USS interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SL3211-0AB12-5UB0 |
| Product Type | Variable-frequency inverter |
| Core Function | Controlling an induction motor |
| Application | Compact variable-speed drive systems |
Control motor speed
Linear, quadratic and programmable multipoint V/f characteristics support different motor-load requirements.
Communicate over USS
The serial interface uses RS485 with the USS protocol.
Configure local control signals
Three programmable digital inputs and one optically isolated transistor output support control-circuit integration.
Product Overview
6SL3211-0AB12-5UB0 provides adjustable-frequency motor control using the USS communication version of the SINAMICS G110.
The frame A drive supports configurable digital control signals, selectable V/f characteristics and an optional Basic Operator Panel for local operation.
Key Functions
Control motor speed
Linear, quadratic and programmable multipoint V/f characteristics support different motor-load requirements.
Communicate over USS
The serial interface uses RS485 with the USS protocol.
Configure local control signals
Three programmable digital inputs and one optically isolated transistor output support control-circuit integration.
Official Specifications
| Rated Motor Power | 0.25 kW |
|---|---|
| Mains Supply | Single-phase 200–240 V AC, ±10% |
| Input Frequency | 47–63 Hz |
| Rated Output Current | 1.7 A |
| Input Current | 4.5 A at 230 V nominal input |
| Output Frequency | 0–650 Hz |
| Control Characteristics | Linear, quadratic or programmable multipoint V/f |
| Overload Cycle | 150% rated output current for 60 s, then 85% for 240 s |
| Pulse Frequency | 8 kHz standard; adjustable 2–16 kHz in 2 kHz steps |
| Serial Interface | RS485 USS |
| Digital Inputs | 3 configurable PNP inputs; maximum 30 V |
| Digital Output | 1 optically isolated NPN output; 24 V DC, 50 mA resistive load |
| Integrated EMC Filter | None |
| Maximum Motor Cable Length | 25 m shielded; 50 m unshielded |
| Recommended Mains Fuse | 10 A; Siemens 3NA3803 |
| Power and PE Terminal Torque | 0.96 N·m for frame A M3.5 screws |
| Operating Temperature | −10 to +40 °C; up to +50 °C with derating |
| Protection | IP20 |
| Dimensions (W × H × D) | 90 × 150 × 116 mm |
| Approximate Weight | 0.7 kg without options |
Frequently Asked Questions
Can 6SL3211-0AB12-5UB0 run from a single-phase 230 V mains connection?
The supply input accepts single-phase 200–240 V AC with a ±10% tolerance.
Can I send speed commands to 6SL3211-0AB12-5UB0 through RS485?
This version supports serial control over the USS protocol.
Does 6SL3211-0AB12-5UB0 have the analog version’s 0–10 V setpoint input?
This article is the USS version rather than the analog-input version.
Must I add an EMC filter when the installation requires filtered operation with 6SL3211-0AB12-5UB0?
This unfiltered version requires a suitable external filter when the installation needs additional EMC filtering.
Can I fit a local keypad to 6SL3211-0AB12-5UB0?
A Basic Operator Panel is available as an optional accessory.
How far can I run a shielded motor cable from 6SL3211-0AB12-5UB0?
The maximum shielded motor-cable length is 25 m.
Can 6SL3211-0AB12-5UB0 supply a brief motor overload during acceleration?
The overload cycle permits 150% of rated output current for 60 seconds followed by 240 seconds at 85%.