Siemens 6SL3210-1PE12-3UL1 SINAMICS PM240-2 Power Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the compatible SINAMICS G120 control unit and configure the drive for the intended motor and duty profile.
- Provide the required air path for the 0.005 m³/s cooling airflow.
- Keep motor wiring within the 50 m shielded or 100 m unshielded cable limit.
- Use the FSA dimensions and IP20 construction when planning enclosure space and protection.
6SL3210-1PE12-3UL1 SINAMICS PM240-2 Power Module
Frame FSA power module for 380–480 V three-phase supplies, rated 0.75 kW at low overload or 0.55 kW at high overload.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SL3210-1PE12-3UL1 |
| Product Type | Drive power module |
| Core Function | Variable-frequency motor power conversion |
| Application | SINAMICS G120 modular drive systems |
Two overload duty profiles
Low-overload operation provides 0.75 kW, while high-overload operation provides 0.55 kW with a higher short-term overload allowance.
Variable motor frequency
The power module supports output frequency ranges up to 200 Hz in vector operation and 550 Hz in V/f operation.
Compact FSA integration
The IP20 air-cooled power stage uses plug-in screw terminals for line and motor connections.
Product Overview
6SL3210-1PE12-3UL1 forms the power stage of a modular SINAMICS G120 drive, converting a three-phase 380–480 V input into a variable-frequency motor output.
Its low-overload and high-overload ratings suit different load profiles, while a compact FSA housing and air cooling allow integration with the selected drive control unit.
Key Functions
Two overload duty profiles
Low-overload operation provides 0.75 kW, while high-overload operation provides 0.55 kW with a higher short-term overload allowance.
Variable motor frequency
The power module supports output frequency ranges up to 200 Hz in vector operation and 550 Hz in V/f operation.
Compact FSA integration
The IP20 air-cooled power stage uses plug-in screw terminals for line and motor connections.
Official Specifications
| Input voltage and frequency | 3 AC 380–480 V ±10%; 47–63 Hz |
|---|---|
| Rated input current | 2.90 A low overload; 2.60 A high overload |
| Rated output power | 0.75 kW low overload; 0.55 kW high overload |
| Rated output current | 2.20 A low overload; 1.70 A high overload |
| Maximum output current | 3.40 A |
| Pulse frequency | 4 kHz |
| Output frequency ranges | 0–200 Hz vector; 0–550 Hz V/f |
| Low-overload cycle | 110% for 57 s and 150% for 3 s per 300 s |
| High-overload cycle | 150% for 57 s and 200% for 3 s per 300 s |
| Efficiency and power loss | 96%; 0.04 kW |
| Power factors | λ = 0.85; cos φ = 0.95 |
| Cooling airflow | 0.005 m³/s |
| Operating ambient | −10 to +40°C low overload; −10 to +50°C high overload |
| Maximum installation altitude | 1000 m |
| Relative humidity | 95% maximum, without condensation |
| Power-terminal conductor range | 1–2.5 mm², AWG 18–14 |
| Motor cable length | 50 m shielded; 100 m unshielded |
| Enclosure and frame | IP20 / UL open type; FSA |
| Dimensions and mass | 73 × 196 × 165 mm (W × H × D); 1.40 kg |
| Acoustic pressure | 72 dB at 1 m |
Frequently Asked Questions
Should I choose the low-overload or high-overload rating of 6SL3210-1PE12-3UL1?
Select the duty from the motor load profile, using 0.75 kW and 2.20 A for low overload or 0.55 kW and 1.70 A for high overload.
Can 6SL3210-1PE12-3UL1 operate from a single-phase supply?
The power module requires a three-phase 380–480 V supply within ±10% of the rated voltage.
How does the permitted ambient temperature change with duty on 6SL3210-1PE12-3UL1?
The operating range is −10 to +40°C at low overload and −10 to +50°C at high overload.
What frequency ceiling applies when 6SL3210-1PE12-3UL1 runs vector control?
Vector operation extends to 200 Hz, while the V/f output range extends to 550 Hz.
How long may the motor cable connected to 6SL3210-1PE12-3UL1 be?
The cable limit is 50 m with shielding or 100 m without shielding.
Does 6SL3210-1PE12-3UL1 provide a closed enclosure for exposed installation?
The power stage has IP20 protection and UL open-type construction, so the installation must provide the required enclosure protection.
What overload can 6SL3210-1PE12-3UL1 deliver for a high-overload start?
High-overload duty permits 200% output current for 3 s and 150% for 57 s in a 300 s cycle.