Siemens 6SL3210-1PE12-3UL1 SINAMICS PM240-2 power module
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Select the compatible SINAMICS G120 control unit and configure the drive for the intended motor and duty profile.
- Provide the required air path for the 0.005 m³/s cooling airflow.
- Keep motor wiring within the 50 m shielded or 100 m unshielded cable limit.
- Use the FSA dimensions and IP20 construction when planning enclosure space and protection.
6SL3210-1PE12-3UL1 SINAMICS PM240-2 Power Module
FSA-frame power module for three-phase supplies of 380–480 V, rated at 0.75 kW for low overload or 0.55 kW for high overload.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6SL3210-1PE12-3UL1 |
| Typus Producti | Drive power module |
| Functio principalis | Variable-frequency motor power conversion |
| Applicatio | SINAMICS G120 modular drive systems |
Two overload duty profiles
Low-overload operation delivers 0.75 kW; high-overload operation delivers 0.55 kW with greater short-term overload capacity.
Variable motor frequency
The power module supports output frequency ranges up to 200 Hz in vector operation and up to 550 Hz in V/f operation.
Integratio FSA compacta
Stadium potentiae aer-coolatus IP20 utitur terminalibus vitarum infigendarum pro connexionibus lineae et motoris.
Product Overview
6SL3210-1PE12-3UL1 constituit stadium potentiae modularis actionis SINAMICS G120, quae convertit triphasicam 380–480 V intrantem in variabilem frequentionem motoris egredientem.
Suae valorationes parvae oneris et magnae oneris aptae sunt ad diversos profili oneris, dum habitaculum FSA compactum et refrigeratio aerea permittunt integrationem cum unitate controlis actionis electa.
Key Functions
Two overload duty profiles
Low-overload operation delivers 0.75 kW; high-overload operation delivers 0.55 kW with greater short-term overload capacity.
Variable motor frequency
The power module supports output frequency ranges up to 200 Hz in vector operation and up to 550 Hz in V/f operation.
Integratio FSA compacta
Stadium potentiae aer-coolatus IP20 utitur terminalibus vitarum infigendarum pro connexionibus lineae et motoris.
Official Specifications
| Tensio et frequencia intrantis | 3 AC 380–480 V ±10%; 47–63 Hz |
|---|---|
| Evaluatus Input Correntia | 2.90 A parvum onus; 2.60 A magnum onus |
| Potentia Output Notata | 0.75 kW parvum onus; 0.55 kW magnum onus |
| Currentis Output Aestimatus | 2.20 A parvum onus; 1.70 A magnum onus |
| Currentia maxima emissa | 3.40 A |
| Pulsus frequency | 4 kHz |
| Intervala frequentiarum output | vector 0–200 Hz; V/f 0–550 Hz |
| Cyclum pro onere parvo | 110% pro 57 s et 150% pro 3 s per 300 s |
| Cyclum pro onere magno | 150% pro 57 s et 200% pro 3 s per 300 s |
| Efficientia et Potentiae Amissio | 96%; 0.04 kW |
| Factores potentiae | λ = 0.85; cos φ = 0.95 |
| Fluxus aeris refrigerantis | 0.005 m³/s |
| Ambiens Operativa | −10 ad +40°C sub onere parvo; −10 ad +50°C sub onere magno |
| Altitudo Installationis Maxima | 1000 m |
| Humiditas relativa | 95% maximum, sine condensatione |
| Power-terminal conductor range | 1–2.5 mm², AWG 18–14 |
| Motor cable length | 50 m cum scuto; 100 m sine scuto |
| Enclosure and Frame | IP20 / UL apertus typus; FSA |
| Dimensiones et massa | 73 × 196 × 165 mm (latus × altus × profundus); 1.40 kg |
| Pressura porus acusticus | 72 dB ad 1 m |
Quaestiones Frequenter Rogatae
Utrum eligam rating de subcarricatura parva an subcarricatura magna pro 6SL3210-1PE12-3UL1?
Elige officium ex profilo oneris motoris, utendo 0.75 kW et 2.20 A pro subcarricatura parva aut 0.55 kW et 1.70 A pro subcarricatura magna.
Num 6SL3210-1PE12-3UL1 operare potest ex unica phasī?
Modulus potentiae requirit trīs phāsēs 380–480 V, intra ±10% tensionis nominālis.
Quōmodo temperātūra ambientis permissa variat secundum officium in 6SL3210-1PE12-3UL1?
The operating range is −10 to +40°C at low overload and −10 to +50°C at high overload.
What frequency ceiling applies when 6SL3210-1PE12-3UL1 runs vector control?
Vector operation extends to 200 Hz, while the V/f output range extends to 550 Hz.
How long may the motor cable connected to 6SL3210-1PE12-3UL1 be?
The cable limit is 50 m with shielding or 100 m without shielding.
Does 6SL3210-1PE12-3UL1 provide a closed enclosure for exposed installation?
The power stage has IP20 protection and UL open-type construction, so the installation must provide the required enclosure protection.
What overload can 6SL3210-1PE12-3UL1 deliver for a high-overload start?
High-overload duty permits 200% output current for 3 s and 150% for 57 s in a 300 s cycle.