Siemens 6SL3210-1KE17-5UF1 SINAMICS G120C 3 kW PROFINET Inverter
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Choose the overload duty before comparing motor power and current ratings.
- Use the unfiltered variant within the required installation EMC design.
- Power-terminal conductor sizes are 1.00–2.50 mm²; signal conductors are 0.15–1.50 mm².
- Keep braking-resistor wiring within 15 m and provide the housing PE connection at its M4 screw.
6SL3210-1KE17-5UF1 SINAMICS G120C 3 kW PROFINET Inverter
An unfiltered G120C rated at 3 kW in low-overload duty or 2.2 kW in high-overload duty, with PROFINET and EtherNet/IP communication.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6SL3210-1KE17-5UF1 |
| Product Type | Compact frequency inverter |
| Core Function | Regulating AC motor speed |
| Application | Low- and high-overload drive applications |
Select the appropriate duty rating
Low-overload operation is rated at 3 kW, while high-overload operation is rated at 2.2 kW with a different short-duration overload profile.
Integrate network and machine signals
PROFINET and EtherNet/IP are available together with discrete I/O, a differential analog input and a non-isolated analog output.
Control without encoder feedback
Sensorless vector control and several V/f methods are available, while encoder-based vector and torque-control modes are not provided.
Product Overview
6SL3210-1KE17-5UF1 provides a compact three-phase motor drive for a 380–480 V mains supply. Its low- and high-overload ratings allow the selected drive duty to follow the load cycle rather than one undifferentiated power figure.
The inverter combines industrial-network communication with digital and analog machine signals, a motor-temperature input and sensorless control methods. An integrated fan cools the FSA housing, while the unfiltered input variant requires the installation EMC arrangement to be selected separately.
Key Functions
Select the appropriate duty rating
Low-overload operation is rated at 3 kW, while high-overload operation is rated at 2.2 kW with a different short-duration overload profile.
Integrate network and machine signals
PROFINET and EtherNet/IP are available together with discrete I/O, a differential analog input and a non-isolated analog output.
Control without encoder feedback
Sensorless vector control and several V/f methods are available, while encoder-based vector and torque-control modes are not provided.
Official Specifications
| Mains input | 3-phase 380–480 V AC, +10% / −20%; 47–63 Hz |
|---|---|
| Rated input current | 9.50 A low overload; 8.20 A high overload |
| Low-overload output rating | 3.00 kW; 7.30 A output current at 440–480 V |
| High-overload output rating | 2.20 kW; 5.60 A output current at 440–480 V |
| Maximum output current | 11.20 A |
| Low-overload cycle | 150% of base current for 3 s, then 110% for 57 s, in a 300 s cycle |
| High-overload cycle | 200% of base current for 3 s, then 150% for 57 s, in a 300 s cycle |
| Output frequency ranges | 0–240 Hz vector control; 0–550 Hz V/f control |
| Pulse frequency | 4 kHz |
| Digital input resources | 6 standard digital inputs; 1 fail-safe digital input |
| Digital output resources | 1 changeover relay and 1 transistor output, each 30 V DC / 0.5 A resistive |
| Analog input | 1 differential input, 10-bit resolution |
| Analog output | 1 non-isolated output |
| Motor-temperature sensing | PTC, KTY or Thermo-Click; ±5 °C accuracy |
| Efficiency and power loss | 97% efficiency; 97.8 W power loss |
| EMC filter configuration | Unfiltered |
| Cooling and airflow requirement | Integrated fan; 0.005 m³/s |
| Operating environment | −10 to +40 °C; maximum 95% RH at 40 °C without condensation or icing |
| Maximum motor cable length | 150 m, shielded or unshielded |
| Mechanical construction | FSA; IP20 / UL open type; 73 × 196 × 200 mm; 1.70 kg |
Frequently Asked Questions
Should I select the 3 kW or 2.2 kW rating for 6SL3210-1KE17-5UF1?
Use the 3 kW rating for low-overload duty and the 2.2 kW rating for high-overload duty.
Can 6SL3210-1KE17-5UF1 communicate with an EtherNet/IP controller?
The inverter supports EtherNet/IP as well as PROFINET.
Does 6SL3210-1KE17-5UF1 include an integrated mains EMC filter?
This inverter variant is unfiltered.
Can I use encoder-based vector control with 6SL3210-1KE17-5UF1?
Encoder-based vector control is not available, although sensorless vector control is supported.
Which motor-temperature sensors can connect to 6SL3210-1KE17-5UF1?
The temperature input accepts PTC, KTY and Thermo-Click sensors.
What load cycle applies to high-overload operation of 6SL3210-1KE17-5UF1?
High-overload duty permits 200% base current for 3 seconds followed by 150% for 57 seconds within a 300-second cycle.
How long can the motor cable be with 6SL3210-1KE17-5UF1?
The maximum motor cable length is 150 m for either shielded or unshielded cable.