Overview
- Use the matching RF170C electronics and ET 200pro station assembly.
- Select reader cables with the correct 8-pin M12 pin assignment.
- Tighten the four front mounting screws and M12 connector fastenings to 1.5 Nm.
- Close every unused M12 socket with a sealing cap.
- Apply the reader-dependent RS-422 or RS-232 cable limit.
- Isolate the supply or remove the connection module before wiring.
6GT2002-1HD00 SIMATIC RF170C Reader Connection Block
An RF170C connection block with two 8-pin M12 reader sockets, mounted on the separate RF170C communication module.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GT2002-1HD00 |
| Product Type | Reader connection block for the RF170C communication module |
| Core Function | Connects reader cables to the RF170C electronics module |
| Application | ET 200pro distributed RFID and identification stations |
Reader cable connections
Two M12 sockets, X1 and X2, accept reader connecting cables.
Separate connection block
The block mounts on the RF170C communication module and is ordered separately.
Sealed field installation
Unused M12 sockets require sealing caps to maintain the assembly protection degree.
Product Overview
6GT2002-1HD00 is the reader connection block for an RF170C identification station in the SIMATIC ET 200pro system.
The block mounts on the communication electronics and provides two 8-pin M12 round sockets for reader cables; it is a separate ordering item from the RF170C communication module.
Key Functions
Reader cable termination
Sockets X1 and X2 provide the connection points for two reader cables using 8-pin M12 connectors.
Modular station assembly
The connection block plugs into the RF170C communication module and is secured to the rack by four front screws.
Protected field connections
Sealing unused round sockets with M12 caps preserves the specified IP65, IP66 or IP67 protection of the installed assembly.
Official Specifications
| Reader socket arrangement | Two sockets, X1 and X2 |
|---|---|
| Reader connector type | 8-pin M12 round sockets |
| Connection block dimensions (W × H × D) | 90 × 130 × 60 mm |
| Approximate connection block weight | 500 g |
| Mounting fasteners | Four front cross-head screws |
| Mounting screw and M12 connector tightening torque | 1.5 Nm for each specified screw or knurled connector fastening |
| Self-assembled reader cable | Shielded flexible 7-core copper cable; conductor cross-section ≤0.75 mm² |
| RF170C RS-422 cable limit | 50 m for all reader configurations; up to 1,000 m depending on reader and current consumption |
| RF170C RS-232 cable limit | 30 m; reduced to 5 m when the reader uses the RF170C 5 V supply |
| RF170C assembly operating ambient temperature | −25 to +55 °C |
| RF170C assembly storage and transport temperature | −40 to +70 °C |
| Installed assembly protection | IP67; unused M12 sockets must be closed with sealing caps |
Frequently Asked Questions
Is 6GT2002-1HD00 the RF170C electronics module or the reader connection block?
This order number identifies the connection block, which is supplied separately from the RF170C communication electronics.
Which reader connectors are provided by 6GT2002-1HD00?
The connection block provides two 8-pin M12 sockets designated X1 and X2.
How is 6GT2002-1HD00 secured after plugging it into the communication module?
Secure the block to the rack with its four front cross-head screws tightened to 1.5 Nm.
What should be done with an unused reader socket on 6GT2002-1HD00?
Close the unused socket with an M12 sealing cap to maintain the installed assembly protection degree.
Which cable construction is permitted when making a reader lead for 6GT2002-1HD00?
Use a shielded flexible seven-core copper cable with conductors no larger than 0.75 mm² and the matching eight-pin M12 connector.
Can a reader connected through 6GT2002-1HD00 always use the maximum RS-232 cable length?
The general RS-232 limit is 30 m, but it falls to 5 m when the reader is powered from the RF170C 5 V output.
May 6GT2002-1HD00 be wired while the supply remains energized?
Switch off the supply voltage or remove the connection module before starting the wiring work.