Siemens SCALANCE XC208EEC 6GK5208-0BA00-2FC2 Managed Industrial Ethernet Switch
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Confirm that eight 10/100 Mbit/s copper ports meet the network design.
- Provide SELV power within the permitted voltage range and wire redundancy as required.
- Reserve cabinet space for the 60 × 147 × 125 mm housing.
- Match firmware and PROFINET device configuration to the automation project.
SIEMENS SCALANCE XC-200EEC
Siemens SCALANCE XC208EEC 6GK5208-0BA00-2FC2 Managed Industrial Ethernet Switch
6GK5208-0BA00-2FC2 is a SCALANCE XC208EEC switch with eight 10/100 Mbit/s RJ45 ports, coated electronics and an extended -40 °C to +70 °C operating range.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6GK5208-0BA00-2FC2 |
| Product Type | Managed Layer 2 Industrial Ethernet Switch |
| Core Function | Managed Fast Ethernet switching |
| Application | PROFINET industrial network cells |
Port Arrangement
Eight RJ45 Fast Ethernet ports plus one RJ11 serial diagnostics interface.
Power Architecture
Redundant 12–24 V DC input through a four-terminal block.
EEC Construction
Conformal-coated electronics for NAMUR NE21 industrial environments.
Product Overview
Siemens 6GK5208-0BA00-2FC2 is the SCALANCE XC208EEC managed Layer 2 switch for structured industrial Ethernet and PROFINET networks.
Its compact aluminum housing combines eight 10/100 Mbit/s ports, redundant low-voltage supply, a signaling contact, serial diagnostics and multiple rail or wall mounting options.
Key Functions
Managed Industrial Switching
Eight RJ45 ports support 10/100 Mbit/s links with half/full-duplex operation and MDI-X pinning.
Redundant Low-Voltage Input
A four-terminal power connector accepts 9.6 to 31.2 V DC SELV and supports redundant feeding.
Local Diagnostics and Signaling
An RJ11 serial diagnostics interface and a separately rated signaling contact support commissioning and fault indication.
Official Specifications
| Electrical Ethernet Ports | 8 × RJ45 with half/full duplex and MDI-X pinning |
|---|---|
| Ethernet Transmission Speed | 10/100 Mbit/s |
| Serial Diagnostics Interface | 1 × RJ11 |
| Rated Supply Voltage | 12–24 V DC |
| Permissible Supply Range | 9.6–31.2 V DC SELV |
| Supply Connector | 4-terminal block with redundant input |
| Current Consumption | 350 mA at 12 V DC; 175 mA at 24 V DC |
| Effective Power Loss | 4.2 W |
| Overvoltage Category | CAT II |
| Input Fuse Rating | 2.5 A / 125 V |
| Signaling Contact | 1 × 2-terminal block, 24 V DC, maximum 100 mA |
| Operating Temperature | -40 °C to +70 °C up to 2000 m altitude |
| Storage and Transport Temperature | -40 °C to +85 °C |
| Relative Humidity | Maximum 95% at 25 °C, non-condensing |
| Housing Construction | Powder-coated die-cast aluminum with PC-GF10 front cover |
| Printed Circuit Board | Conformal-coated |
| Protection Rating | IP20 |
| Dimensions | 60 × 147 × 125 mm |
| Weight | 520 g |
| Mean Time Between Failures | More than 48 years at 40 °C |
Frequently Asked Questions
Which network ports can I use on 6GK5208-0BA00-2FC2?
Use the eight RJ45 ports for 10 or 100 Mbit/s links with half/full duplex and MDI-X pinning.
What supply range is suitable for 6GK5208-0BA00-2FC2?
Provide 9.6 to 31.2 V DC SELV through the four-terminal redundant supply connector.
How can I access local diagnostics on 6GK5208-0BA00-2FC2?
Connect to the single RJ11 serial diagnostics interface.
What can the signaling contact switch on 6GK5208-0BA00-2FC2?
The contact is rated for 24 V DC with a maximum load of 100 mA.
Can I install 6GK5208-0BA00-2FC2 in a -40 °C cabinet?
The switch operates from -40 °C to +70 °C at altitudes up to 2000 m.
Which mounting methods are available for 6GK5208-0BA00-2FC2?
The enclosure supports wall mounting, DIN rail mounting, and S7-300 or S7-1500 mounting rails.
Why is 6GK5208-0BA00-2FC2 intended for extended-environment use?
The EEC version uses conformal-coated electronics and is designed for the specified extended temperature range.