- Use the module only in the dedicated synchronization interfaces of a compatible SIMATIC S7-1500H or S7-1500HF CPU.
- Install four identical modules for a two-CPU system with two optical synchronization links.
- Select the longer-distance synchronization-module variant when the required patch-cable run exceeds 200 m.
SIEMENS · SIMATIC S7-1500H
6ES7960-1CB00-0AA5 Synchronization Module for Patch Cables up to 200 m
The 6ES7960-1CB00-0AA5 is a pluggable fiber-optic synchronization module for SIMATIC S7-1500H and S7-1500HF CPU pairs using patch cables up to 200 m.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7960-1CB00-0AA5 |
| Product Type | Fiber-optic CPU synchronization submodule |
| Core Function | Links the two CPUs of a redundant S7-1500H or S7-1500HF system through the dedicated synchronization paths |
| Application or Compatible Series | SIMATIC S7-1500H and S7-1500HF redundant controller systems |
Exact Identification
Match 6ES7960-1CB00-0AA5 character by character before replacement.
Interface Check
Confirm the installed supply, terminals, network and field wiring.
Project Backup
Preserve the validated configuration and application data before exchange.
Product Overview
The 6ES7960-1CB00-0AA5 is a pluggable fiber-optic synchronization module for SIMATIC S7-1500H and S7-1500HF CPU pairs using patch cables up to 200 m.
Two optical synchronization paths maintain the data exchange required by a redundant H-system CPU pair. The module installs directly in the dedicated synchronization interfaces of a compatible H or HF CPU. This article is the synchronization-module version specified for patch-cable runs up to 200 m.
Key Functions
Dual-Link CPU Synchronization
Two optical synchronization paths maintain the data exchange required by a redundant H-system CPU pair.
Pluggable Fiber-Optic Interface
The module installs directly in the dedicated synchronization interfaces of a compatible H or HF CPU.
Defined 200 m Variant
This article is the synchronization-module version specified for patch-cable runs up to 200 m.
Official Specifications
| Maximum Patch-Cable Length | 200 m |
|---|---|
| Transmission Medium | Fiber optic |
| CPU Synchronization Paths | 2 per redundant CPU pair |
| Synchronization Interfaces per CPU | 2 |
| Modules Installed per CPU | 2 |
| Modules Required per Redundant CPU Pair | 4 |
| CPU 1517H-3 PN Order Number | 6ES7517-3HP00-0AB0 |
| CPU 1517H-4 PN Order Number | 6ES7517-4HQ10-0AB0 |
| CPU 1518HF-4 PN Order Numbers | 6ES7518-4JP00-0AB0 and 6ES7518-4JT10-0AB0 |
| Net Weight | 0.086 lb (approximately 39 g) |
| Supply Unit | 1 piece |
Frequently Asked Questions
Which cable distance is suitable for 6ES7960-1CB00-0AA5?
Use this variant for a fiber-optic synchronization patch-cable run of up to 200 m.
Where is 6ES7960-1CB00-0AA5 installed in the redundant controller?
Install one module in each of the two dedicated synchronization interfaces on every compatible H or HF CPU.
How many 6ES7960-1CB00-0AA5 modules are needed for one redundant CPU pair?
A complete two-link CPU pair uses four modules, with one module at each end of both optical paths.
Can 6ES7960-1CB00-0AA5 replace a longer-distance synchronization-module variant?
No, select the matching 1FB00 or 1FE00 variant when the specified fiber run exceeds 200 m.
How should the fiber links for 6ES7960-1CB00-0AA5 be routed?
Route the two optical paths within the 200 m limit and protect the connectors and fiber from contamination and excessive bending.
What should be recorded before replacing 6ES7960-1CB00-0AA5?
Record the CPU position, synchronization-interface position and optical-link assignment before removing the module.
What should be tested after installing 6ES7960-1CB00-0AA5?
Confirm that both synchronization links are healthy and that the redundant CPU pair returns to the intended operating state.