Siemens SIMATIC PCS 7 6ES7650-1AA51-2XX0 8-Channel Analog Input MTA
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Match the ET 200M module to 6ES7331-7NF00-0AB0 at E-Stand 5 or higher.
- Provide one or two 21.6 to 28.8 V DC feeds according to the redundancy design.
- Set the current or voltage and isolation jumpers for the actual transmitter circuit.
- Check the approved fast-blow fuse value for every field channel.
- Confirm the correct J1 and J2 interconnecting cables before energizing.
Siemens · SIMATIC PCS 7
6ES7650-1AA51-2XX0 8-Channel Analog Input MTA
Siemens 6ES7650-1AA51-2XX0 is the SIMATIC PCS 7 eight-channel analog input Marshalled Termination Assembly for ET 200M installations, including channel fusing, transmitter power and HART service access.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7650-1AA51-2XX0 |
| Product Type | Analog Input Marshalled Termination Assembly |
| Core Function | Centralizes field-signal termination and channel-level transmitter power distribution |
| Application or Compatible Series | SIMATIC PCS 7 ET 200M with SM 331 analog input hardware |
Module Pairing
Connect to the ET 200M SM 331 analog input module 6ES7331-7NF00-0AB0 at E-Stand 5 or higher.
Power Arrangement
Use a single or redundant 21.6 to 28.8 V DC feed and monitor the supply indication.
Field Termination
Plan channel fusing, shield connections, pluggable terminals and per-channel HART access.
Product Overview
Siemens 6ES7650-1AA51-2XX0 is the SIMATIC PCS 7 eight-channel analog input Marshalled Termination Assembly for ET 200M installations, including channel fusing, transmitter power and HART service access.
Dual I/O-module connectors support a redundant ET 200M analog-input arrangement. Each field channel has its own fuse and green sensor-power indication. Pluggable power and field terminals, shield grounding and HART access simplify wiring and maintenance.
Key Functions
Redundant I/O Connectivity
Dual I/O-module connectors support a redundant ET 200M analog-input arrangement.
Channel-Level Power Protection
Each field channel has its own fuse and green sensor-power indication.
Serviceable Signal Marshalling
Pluggable power and field terminals, shield grounding and HART access simplify wiring and maintenance.
Official Specifications
| Analog Input Channels | 8 |
|---|---|
| Supported Signal Ranges | 1 to 5 V and 0/4 to 20 mA |
| Input Supply Range | 21.6 to 28.8 V DC |
| Supply-Feed Arrangement | Single or redundant feed |
| Maximum Inrush Current | 8.238 A including 8.16 A transmitter inrush |
| Maximum Normal Current Consumption | 0.265 A with all channels connected |
| Maximum Total Channel Current | 8.16 A |
| Standard Channel Fuse | 0.5 A fast-blow, Siemens spare A5E01568880 |
| Optional Channel Fuse | 1.5 A fast-blow, Siemens spare A5E01568886 |
| Terminal Wire Size | 24 to 14 AWG; 0.205 to 2.08 mm² |
| Mounting Rail | 35 mm deep top-hat DIN rail |
| Input-Power Indication | Green LED when input power is available |
| Channel-Power Indication | Green LED for sensor power on each channel |
| I/O Module Connections | Dual connectors for redundant operation |
| HART Service Access | Handheld-terminal connectivity on every channel |
| Shield Termination | Channel shield connections plus an earth-ground stud |
| Terminal Construction | Pluggable input-power and field terminations |
| Power-Monitor Provision | Optional plug-in available |
| Ambient Temperature | −25 to +60 °C |
| Relative Humidity | 5% to 95%, non-condensing |
Frequently Asked Questions
Which ET 200M input module can I pair with 6ES7650-1AA51-2XX0?
Pair it with the eight-channel SM 331 analog input module at article number 6ES7331-7NF00-0AB0 and hardware revision 5 or later.
Can 6ES7650-1AA51-2XX0 use redundant field-power feeds?
It accepts either one supply or two redundant supplies within the 21.6 to 28.8 V DC range.
Which field-signal ranges can 6ES7650-1AA51-2XX0 marshal?
The assembly supports 1 to 5 V and 0/4 to 20 mA analog input signals with channel jumpers set for the selected mode.
Can a technician connect a HART handheld communicator through 6ES7650-1AA51-2XX0?
Each channel provides access for a HART handheld terminal.
Which channel fuse should I fit in 6ES7650-1AA51-2XX0?
The standard choice is a 0.5 A fast-blow fuse, with a 1.5 A option where the approved circuit design requires it.
What mounting hardware is required for 6ES7650-1AA51-2XX0?
Install the assembly on a 35 mm deep top-hat DIN rail inside a cabinet that meets the stated environmental limits.
What changes when 6ES7650-1AA51-2XX0 replaces the earlier 6ES7650-1AA50-2XX0 version?
The functionality remains the same, while the later version uses an anthracite-gray housing.