siemens 6es7522 1bh01 0ab0 simatic s7 1500 dq16 24 v dc 0 5 a hf output module-0

For SIEMENS

Home >  Products >  For SIEMENS

Siemens 6ES7522-1BH01-0AB0 SIMATIC S7-1500 DQ16 24 V DC 0.5 A HF Output Module

Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months

  • Overview
  • Hot Selling Models
  • Recommended Products
Overview
SIMATIC S7-1500 / ET 200MP

6ES7522-1BH01-0AB0 SIMATIC S7-1500 DQ16 24 V DC 0.5 A HF Output Module

A 16-channel sourcing output module with two groups of eight, individual diagnostics, substitute values and actuator operating-cycle counters.

At a Glance

Brand Siemens
Model 6ES7522-1BH01-0AB0
Product Type High Feature digital output module
Core Function Transistor load switching with channel diagnostics
Application S7-1500 and ET 200MP I/O stations

Per-channel fault visibility

Wire-break and short-circuit diagnostics support field-circuit maintenance.

Actuator cycle tracking

Integrated operating-cycle counters support maintenance of connected actuators.

Synchronized output operation

Isochronous mode and prioritized startup support configured system timing.

Product Overview

6ES7522-1BH01-0AB0 provides sixteen configurable transistor outputs for an S7-1500 or ET 200MP station.

The High Feature module combines per-channel diagnostic indication and operating-cycle counting with group-based load supplies and support for isochronous operation.

Ordering focus: Match the station configuration, FS02 hardware state, load-group currents, front connector and required diagnostics.
Key Functions

Per-channel fault visibility

Wire-break and short-circuit diagnostics support field-circuit maintenance.

Actuator cycle tracking

Integrated operating-cycle counters support maintenance of connected actuators.

Synchronized output operation

Isochronous mode and prioritized startup support configured system timing.

Official Specifications
Nominal load supply 24 V DC; permitted range 20.4–28.8 V
Output arrangement 16 current-sourcing transistor outputs in 2 groups of 8
Output-current limits 0.5 A per channel; 4 A per group; 8 A per module, subject to installation limits
Maximum lamp load 5 W
Load resistance 48 Ω–12 kΩ
Signal-one output voltage At least L+ minus 0.8 V
Maximum off-state residual current 0.5 mA
Maximum switching delays 100 µs ON; 500 µs OFF with resistive load
Switching-frequency limits 100 Hz resistive; 0.5 Hz inductive DC-13; 10 Hz lamp load
Maximum output cable 1,000 m shielded; 600 m unshielded
Backplane power and typical loss 1.1 W from backplane; 2 W typical module loss
Maximum supply-current consumption 30 mA
Typical short-circuit response threshold 1 A; electronically clocked protection
Minimum isochronous timing TCO 70 µs; TDP bus cycle 250 µs
Isolation arrangement Groups of 8; channel-to-backplane isolation; no individual-channel isolation
Type-test isolation voltage 707 V DC
Diagnostic indications RUN, ERROR, MAINT, PWR, channel status and channel diagnostics
Firmware and identification Firmware V1.1.0; I&M0–I&M3
Operating ambient 0–60 °C for horizontal or vertical installation
Dimensions and approximate mass 35 × 147 × 129 mm (W × H × D); 230 g
Frequently Asked Questions

Can I parallel channels of 6ES7522-1BH01-0AB0 to increase output current?

Parallel connection for increasing current is not permitted.

Can 6ES7522-1BH01-0AB0 switch a digital input as a load?

The outputs are suitable for controlling a digital input.

Does 6ES7522-1BH01-0AB0 track switching cycles for connected actuators?

The module includes an integrated operating-cycle counter.

Will 6ES7522-1BH01-0AB0 provide a wire-break diagnostic?

Wire-break diagnostics are available.

Which STEP 7 generation can configure 6ES7522-1BH01-0AB0?

The module is configurable from TIA Portal V13 SP1.

Is the front connector included with 6ES7522-1BH01-0AB0?

A U-connector is included, but the front connector is supplied separately.

Can load groups on 6ES7522-1BH01-0AB0 take part in safety-related switching off?

From FS02, an appropriate safety-related tripping arrangement can achieve PL d, category 3 and SILCL 2 for the standard module.

Compatibility & Ordering Notes
Before ordering 6ES7522-1BH01-0AB0: Match the station configuration, FS02 hardware state, load-group currents, front connector and required diagnostics.

Before installation

  • Select the station configuration and engineering version for the module.
  • Check the 0.5 A channel, 4 A group and 8 A module limits together with installation conditions.
  • Provide the required front connector and configure diagnostics and substitute values for the field loads.
  • Use the appropriate safety-related tripping circuit when switching off standard load groups; the module is a standard DQ module.
Hot Selling Models
50/21(30)
FS-V12P
6ES7193-6BP00-0DA1 6ES7193-6PA00-0AA0
465682901600
1674300000
6FX1126-6BB00
26K-PA-1QE-S4-C
M-1400-004
D400/HS-F45-D-SS