SIEMENS SIMATIC S7-1500 - Programmable logic controller CPU
6ES7516-3AN00-0AB0 SIMATIC S7-1500 CPU 1516-3 PN/DP
Siemens specifies a CPU 1516-3 PN/DP with separate program and data work memory, two PROFINET interfaces and one PROFIBUS interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7516-3AN00-0AB0 |
| Product Type | Programmable logic controller CPU |
| Core Function | High-performance PLC processing with PROFINET and PROFIBUS connectivity |
| Application or Compatible Series | SIMATIC S7-1500 automation systems |
Product Overview
Siemens specifies a CPU 1516-3 PN/DP with separate program and data work memory, two PROFINET interfaces and one PROFIBUS interface.
Official Siemens documentation identifies the product for SIMATIC S7-1500 automation systems. Selection and commissioning should follow the documented electrical, interface, memory, environmental and mechanical values shown below.
Key Functions
High-Speed Processing
The controller provides 10 ns bit and 12 ns word execution performance.
Three Network Interfaces
Two PROFINET interfaces and one PROFIBUS interface support flexible topology planning.
Integrated Diagnostics Display
The front display and TIA Portal integration support commissioning and diagnostics.
Official Specifications
| Hardware Functional Status | FS05 |
|---|---|
| Firmware Version | V1.8 |
| TIA Portal Integration | V13 SP1 Update 4 or higher |
| Display Diagonal | 6.1 cm |
| Supply Range | 19.2 to 28.8 V DC |
| Typical Power Loss | 7 W |
| Work Memory | 1 MB program; 5 MB data |
| SIMATIC Memory Card Capacity | Up to 32 GB |
| Bit / Word Operation Time | 10 ns / 12 ns |
| Fixed / Floating-Point Operation Time | 16 ns / 64 ns |
| PROFINET Interfaces | 2; first interface has a 2-port switch |
| PROFIBUS Interfaces | 1; up to 12 Mbit/s |
| Maximum Connections | 256 via CPU interfaces and connected CPs/CMs |
| Retentive Data Area | Maximum 512 KB |
| Dimensions | 70 x 147 x 129 mm |
| Approximate Weight | 845 g |
Frequently Asked Questions
Which memory card must be fitted before commissioning 6ES7516-3AN00-0AB0?
A SIMATIC Memory Card must be installed before the user program can be loaded.
What 24 V DC supply range should be provided for 6ES7516-3AN00-0AB0?
The permissible supply range is 19.2 to 28.8 V DC.
How does 6ES7516-3AN00-0AB0 connect to a PROFINET network?
The first PROFINET interface includes an integrated two-port switch, and a second Ethernet interface provides an additional network connection.
Can 6ES7516-3AN00-0AB0 communicate with existing PROFIBUS equipment?
One PROFIBUS interface is available with a transmission rate of up to 12 Mbit/s.
Which TIA Portal release can configure 6ES7516-3AN00-0AB0?
Configuration is supported from STEP 7 in TIA Portal V13 SP1 Update 4 or higher.
What can technicians check locally on 6ES7516-3AN00-0AB0?
The front display and six operating keys support local status viewing and basic operation.
What is the minimum isochronous cycle supported by 6ES7516-3AN00-0AB0?
The minimum supported cycle for an isochronous OB6x organization block is 375 microseconds.
Compatibility & Ordering Notes
Compatibility Checklist for 6ES7516-3AN00-0AB0
- Match SIMATIC S7-1500 CPU 1516-3 PN/DP and the full article number character by character.
- Verify firmware version: V1.8.
- Confirm typical power loss: 7 W.