Siemens 6ES7461-3AA01-0AA0 SIMATIC S7-400 IM 461-3 Receive Interface Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the receiver with the matching IM 460-3 sender and a suitable S7-400 expansion rack.
- Select 468-1 connection cables and keep the complete first-to-last interface line within 102.25 metres.
- Fit the correct terminating plug to X2 on the final receiver and match the configured distance to the actual cable arrangement.
- Set a valid rack number with the expansion-rack supply output off and include the receiver’s backplane current in the rack power budget.
6ES7461-3AA01-0AA0 SIMATIC S7-400 IM 461-3 Receive Interface Module
IM 461-3 receiver for distributed rack coupling up to 102.25 metres, with P-bus and C-bus transmission and DIP-switch rack addressing.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7461-3AA01-0AA0 |
| Product Type | Receive interface module |
| Core Function | Central-to-expansion rack interfacing |
| Application | Distributed S7-400 expansion racks |
Distributed rack data transfer
The IM 460-3 and IM 461-3 pair transmits the P-bus and C-bus to the expansion rack.
Chained interface connections
Upper X1 accepts the preceding interface cable and lower X2 connects the next receiver or the terminating plug.
Local commissioning indication
DIP-switch rack addressing and INTF/EXTF indicators assist setup and line-fault diagnosis.
Product Overview
6ES7461-3AA01-0AA0 links a distributed S7-400 expansion rack to the matching IM 460-3 send interface.
The receiver connects the preceding and following interface modules through its upper and lower front connectors, while local indicators and a hardware rack-number setting support commissioning and fault finding.
Key Functions
Distributed rack data transfer
The IM 460-3 and IM 461-3 pair transmits the P-bus and C-bus to the expansion rack.
Chained interface connections
Upper X1 accepts the preceding interface cable and lower X2 connects the next receiver or the terminating plug.
Local commissioning indication
DIP-switch rack addressing and INTF/EXTF indicators assist setup and line-fault diagnosis.
Official Specifications
| Backplane supply current | 5 V DC; 590 mA typical, 620 mA maximum |
|---|---|
| Power dissipation | 2.95 W typical; 3.10 W maximum |
| Maximum total line length | 102.25 m between the first and last interface modules |
| Front connections | Upper X1 input; lower X2 output or termination |
| Hardware rack-address range | 1–21, selected by DIP switch |
| Fault indicators | Red INTF for internal/address faults; red EXTF for external/line faults |
| Dimensions | 25 × 290 × 280 mm (W × H × D) |
| Approximate weight | 620 g |
Frequently Asked Questions
Which send interface should I pair with 6ES7461-3AA01-0AA0?
Use the IM 460-3 send interface, order number 6ES7460-3AA01-0AB0.
Where should I install the terminating connector on the last 6ES7461-3AA01-0AA0 in a line?
Fit terminating connector 6ES7461-3AA00-7AA0 to the lower X2 output of the last receiver.
Can I assign rack number zero or twenty-two to 6ES7461-3AA01-0AA0?
The permitted hardware rack-number range is one through twenty-one.
How should I set the configured line distance when using 6ES7461-3AA01-0AA0?
Set the distance longer than the actual sum of the cables in that line while keeping it as close to the actual length as possible.
Can I change the rack-number DIP switch of 6ES7461-3AA01-0AA0 while its rack is powered?
Switch the expansion-rack power-supply output off, set the number and switch the supply on again.
Does an EXTF indication on 6ES7461-3AA01-0AA0 always mean the receiver itself has failed?
EXTF can indicate a line fault such as missing termination, an uninitialized module or a switched-off central controller.
Can 6ES7461-3AA01-0AA0 carry communication-bus data as well as peripheral-bus data?
The receiver transmits both the C-bus and P-bus through the matched distributed connection.