Siemens 6ES7461-0AA00-7AA0 S7-400 IM 461-0 Terminating Connector
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Identify the last expansion rack on the line.
- Use the lower front connection of the last receive interface.
- Keep the IM 460-0/IM 461-0 local line within its 5 m total-length limit.
- Use the separate terminating-connector variants specified for other receive interfaces.
6ES7461-0AA00-7AA0 S7-400 IM 461-0 Terminating Connector
The line-end terminating connector for an IM 461-0 receive interface in a local S7-400 expansion arrangement.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7461-0AA00-7AA0 |
| Product Type | Bus terminating connector |
| Core Function | Termination of a local expansion line |
| Application | IM 461-0 receive-interface installations |
Last expansion rack
Termination is fitted at the end of the expansion line.
Lower front connection
The connector occupies the lower front connection of the final receive interface.
Correct interface variant
The terminating connector is assigned to the IM 461-0 receive interface.
Product Overview
6ES7461-0AA00-7AA0 terminates a local expansion line that ends at an IM 461-0 receive interface. The compact connector is an accessory for the SIMATIC S7-400 expansion system, rather than an additional receive interface module.
The final expansion rack on a line must carry the appropriate terminator at the lower front connection of its receive interface. Intermediate racks remain connected through the expansion cabling, while unused send-interface connections do not require termination.
Key Functions
Complete the expansion-line end
The connector provides the required termination at the final expansion rack of an IM 461-0 line.
Preserve the connection arrangement
Install the terminating connector in the lower front connection of the last receive interface.
Match the receive-interface variant
Use the terminating connector assigned to IM 461-0 when maintaining the local S7-400 expansion arrangement.
Official Specifications
| Approximate connector weight | 80 g |
|---|---|
| Operating temperature (S7-400 system) | 0 to +60 °C |
| Maximum temperature change (S7-400 system) | 10 °C per hour |
| Relative humidity (S7-400 system) | Maximum 95% at +25 °C, non-condensing |
| Operating air pressure (S7-400 system) | 795–1080 hPa, corresponding to an elevation of −1000 to +2000 m |
| Vibration qualification (S7-400 system) | IEC 60068-2-6; 0.075 mm amplitude at 10 ≤ f < 58 Hz and 1 g acceleration at 58 ≤ f < 500 Hz |
| Shock qualification (S7-400 system) | IEC 60068-2-29; half-sine pulses, 10 g peak for 6 ms, 100 shocks in each of three mutually perpendicular axes |
| Degree of protection (S7-400 system) | IP20 to IEC 60529; no water ingress protection |
Frequently Asked Questions
Where should I fit 6ES7461-0AA00-7AA0 in an S7-400 expansion line?
Fit the connector in the lower front connection of the receive interface in the last expansion rack on the line.
Does every intermediate rack need 6ES7461-0AA00-7AA0?
Termination is required at the last expansion rack of a line rather than at each intermediate rack.
Should I use 6ES7461-0AA00-7AA0 to close an unused send-interface connection?
Unused front connections of a send interface do not require termination.
Which receive-interface variant is assigned to 6ES7461-0AA00-7AA0?
The terminating connector is assigned to the IM 461-0 receive interface.
Does an IM 461-1 installation require 6ES7461-0AA00-7AA0?
The IM 461-1 receive interface does not require a terminator.
What total local-line length applies when using 6ES7461-0AA00-7AA0 with IM 460-0 and IM 461-0?
The maximum total line length for that local connection is 5 m.
Can 6ES7461-0AA00-7AA0 replace a missing receive-interface module?
The part is a terminating connector and does not replace the IM 461-0 receive interface.