Siemens 6ES7430-2BA11 ET 200B 32-Channel Digital Input Electronics Block
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Select the compatible ET 200B terminal block and retain the field-wiring arrangement.
- Match the station address and bus rate to the PROFIBUS master, including the IM308-B rate limit.
- Keep sensor supply current and two-wire sensor quiescent current within their respective limits.
- Apply the specified input thresholds and delay when choosing switches or proximity sensors.
6ES7430-2BA11 ET 200B 32-Channel Digital Input Electronics Block
A 32-input distributed I/O electronics block with DC field sensing, input-state indication and PROFIBUS diagnostics.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7430-2BA11 |
| Product Type | Digital input electronics block |
| Core Function | Acquiring distributed switching signals |
| Application | PROFIBUS-DP ET 200B stations |
Distributed field acquisition
Thirty-two inputs collect switching states from mechanical contacts or compatible two-wire sensors.
PROFIBUS-DP communication
The bus interface supports FREEZE operation and the communication rates supported by the master.
Local operating indication
RUN, BF and input LEDs provide supply, bus and field-state information.
Product Overview
6ES7430-2BA11 collects digital field states through an ET 200B terminal-block assembly.
The electronics block communicates on PROFIBUS-DP, separates the bus electrically from the internal circuit and provides local RUN, bus-fault and channel-state indication.
Key Functions
Distributed field acquisition
Thirty-two inputs collect switching states from mechanical contacts or compatible two-wire sensors.
PROFIBUS-DP communication
The bus interface supports FREEZE operation and the communication rates supported by the master.
Local operating indication
RUN, BF and input LEDs provide supply, bus and field-state information.
Official Specifications
| Digital input count | 32 |
|---|---|
| Rated logic and sensor supply | 24 V DC |
| Permitted supply range | 18.5–30.2 V DC |
| Short supply transient | 35 V for less than 0.5 s |
| Typical logic current | 70 mA |
| Maximum sensor supply current | 1 A |
| Input low-state voltage | −30 to +5 V |
| Input high-state voltage | 13–30 V |
| Input high-state current | Typically 4 mA at 24 V; minimum 2 mA |
| Input delay | 3 ms |
| Input-to-logic isolation | No galvanic isolation |
| Bus isolation | Galvanic isolation to SINEC L2-DP |
| Two-wire sensor quiescent current | Maximum 1.5 mA |
| Maximum unshielded sensor cable | 100 m |
| PROFIBUS transmission rates | 9.6, 19.2, 93.75, 187.5, 500, 1,500, 3,000, 6,000 and 12,000 kbaud |
| Bus control function | FREEZE capability |
| Typical power loss | 4.8 W |
| Diagnostic indication | Green RUN, red BF and green input-state LEDs |
| Complete EB and TB dimensions | 235 × 130 × 60 mm (W × H × D) |
| Approximate EB and TB mass | 800 g |
Frequently Asked Questions
Which terminal blocks can be paired with 6ES7430-2BA11?
The ET 200B-32DI arrangement supports TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC terminal blocks.
How much input filtering delay should I allow for 6ES7430-2BA11?
The standard 32DI electronics block has a specified input delay of 3 ms.
Can I connect two-wire proximity sensors to 6ES7430-2BA11?
Two-wire BERO sensors are permitted when their quiescent current does not exceed 1.5 mA.
Can I operate the supply of 6ES7430-2BA11 continuously at 35 V?
The continuous permitted supply range ends at 30.2 V and the 35 V allowance applies only for less than 0.5 s.
How far can I run unshielded sensor wiring from 6ES7430-2BA11?
The specified maximum unshielded sensor-cable length is 100 m.
Can 6ES7430-2BA11 communicate at 12 Mbaud when the master is an IM308-B?
Operation with IM308-B is limited to a maximum of 1,500 kbaud.
Are the field inputs of 6ES7430-2BA11 isolated from the internal electronics?
The inputs are not galvanically isolated from the internal electronics, while the PROFIBUS interface is isolated.