Siemens 6ES7430-2BA11 ET 200B 32-Channel Digital Input Electronics Block
Fabricator: Siemens
Condición: Nuevo
Plazo de Entrega: En Stock
Origo: Germania
Garantía: 12 Meses
Inscriptio electronica: [email protected]
whatsapp: +86-18150117685
- Conspectus
- Hot Selling Models
- Producta commendata
Conspectus
- Select the compatible ET 200B terminal block and retain the field-wiring arrangement.
- Match the station address and bus rate to the PROFIBUS master, including the IM308-B rate limit.
- Keep sensor supply current and two-wire sensor quiescent current within their respective limits.
- Apply the specified input thresholds and delay when choosing switches or proximity sensors.
6ES7430-2BA11 ET 200B 32-Channel Digital Input Electronics Block
A 32-input distributed I/O electronics block with DC field sensing, input-state indication and PROFIBUS diagnostics.
Ad Primum Aspectum
| Nota | Siemens |
|---|---|
| Modellum | 6ES7430-2BA11 |
| Typus Producti | Digital input electronics block |
| Functio principalis | Acquiring distributed switching signals |
| Applicatio | PROFIBUS-DP ET 200B stations |
Distributed field acquisition
Thirty-two inputs collect switching states from mechanical contacts or compatible two-wire sensors.
Communicatio PROFIBUS-DP
The bus interface supports FREEZE operation and the communication rates supported by the master.
Local operating indication
RUN, BF et LED de entrata praebent informationem de supplitu, de bus et de statu campo.
Product Overview
6ES7430-2BA11 colligit status digitales campo per coniunctionem bloci terminalis ET 200B.
Blocus electronicus communicat per PROFIBUS-DP, separat electricamente bus a circuitu interno et praebet indicationem localem RUN, faultus bus et status canalis.
Key Functions
Distributed field acquisition
Thirty-two inputs collect switching states from mechanical contacts or compatible two-wire sensors.
Communicatio PROFIBUS-DP
The bus interface supports FREEZE operation and the communication rates supported by the master.
Local operating indication
RUN, BF et LED de entrata praebent informationem de supplitu, de bus et de statu campo.
Official Specifications
| Numerus Ingressuum Digitalium | 32 |
|---|---|
| Supplitus logicus et sensorius nominalis | 24 V DC |
| Permissum Supplicationis Intervallum | 18.5–30.2 V DC |
| Transiens brevis supplitus | 35 V per minus quam 0,5 s |
| Current typicalis logicus | 70 mA |
| Maximum Sensor Supply Current | 1 A |
| Tensio in statu basso entratae | −30 pana la +5 V |
| Tensio in statu alto entratae | 13–30 V |
| Current in statu alto entratae | Typice 4 mA ad 24 V; minimum 2 mA |
| Morae Ingressus | 3 ms |
| Isolatio inter intratum et logicam | Nessuna isolazione galvanica |
| Isolatione de Bus | Isolatio galvanica ad SINEC L2-DP |
| Currens Quiescens Sensoris Duo-Filarii | Maximum 1.5 mA |
| Maxima longitudo cavi sensoris non scutati | 100 m |
| Velocitates Transmissionis PROFIBUS | 9.6, 19.2, 93.75, 187.5, 500, 1.500, 3.000, 6.000 et 12.000 kbaud |
| Functio controlus bus | FREEZE Capability |
| Perditio potentiæ typica | 4,8 W |
| Indicatio Diagnostica | LED viridis RUN, rubra BF et viridis status intrationis |
| Dimensiones EB et TB integrae | 235 × 130 × 60 mm (lat × alt × prof) |
| Massa EB et TB approximata | 800 g |
Quaestiones Frequenter Rogatae
Quae bloci terminalium cum 6ES7430-2BA11 coniungi possunt?
The ET 200B-32DI arrangement supports TB2/DC, TB2-4/DC, TB4/DC and TB4M/DC terminal blocks.
How much input filtering delay should I allow for 6ES7430-2BA11?
The standard 32DI electronics block has a specified input delay of 3 ms.
Can I connect two-wire proximity sensors to 6ES7430-2BA11?
Two-wire BERO sensors are permitted when their quiescent current does not exceed 1.5 mA.
Can I operate the supply of 6ES7430-2BA11 continuously at 35 V?
The continuous permitted supply range ends at 30.2 V and the 35 V allowance applies only for less than 0.5 s.
How far can I run unshielded sensor wiring from 6ES7430-2BA11?
The specified maximum unshielded sensor-cable length is 100 m.
Can 6ES7430-2BA11 communicate at 12 Mbaud when the master is an IM308-B?
Operation with IM308-B is limited to a maximum of 1,500 kbaud.
Are the field inputs of 6ES7430-2BA11 isolated from the internal electronics?
The inputs are not galvanically isolated from the internal electronics, while the PROFIBUS interface is isolated.