Siemens 6ES7422-1FF00-0AA0 SM 422 8 DO 120/230 V AC 5 A
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use AC loads within 79–264 V and 47–63 Hz.
- Observe the 10 mA minimum load and the ambient-dependent combined-current limit.
- Use the specified quick-response 8 A replacement fuse.
- Remove the front connector before fuse replacement and retain the individual channel wiring.
6ES7422-1FF00-0AA0 SM 422 8 DO 120/230 V AC 5 A
An eight-channel AC output module with individually isolated 5 A outputs, channel fuses and status indication.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7422-1FF00-0AA0 |
| Product Type | AC actuator output electronics |
| Core Function | Switch isolated load circuits |
| Application | S7-400 automation racks |
Individual channel isolation
Each output is isolated from the other channels and from the backplane bus.
AC load switching
A 10 mA to 5 A permitted on-state load range supports AC actuators within the specified switching-frequency limits.
Serviceable output protection
Each output is protected by an 8 A, 250 V fuse and has a green status LED.
Product Overview
6ES7422-1FF00-0AA0 switches eight 120/230 V AC load circuits in an S7-400 rack, with electrical isolation in groups of one channel.
Each output has an 8 A fuse, while separate INTF and EXTF indicators distinguish an internal fuse fault from missing load voltage.
Key Functions
Individual channel isolation
Each output is isolated from the other channels and from the backplane bus.
AC load switching
A 10 mA to 5 A permitted on-state load range supports AC actuators within the specified switching-frequency limits.
Serviceable output protection
Each output is protected by an 8 A, 250 V fuse and has a green status LED.
Official Specifications
| Output channel count | 8, isolated in groups of 1 |
|---|---|
| Rated load voltage | 120/230 V AC |
| Permitted load voltage and frequency | 79–264 V AC; 47–63 Hz |
| On-state output current | 10 mA–5 A per channel |
| Maximum off-state residual current | 3.5 mA |
| Maximum combined output current | 24 A up to 40 °C; 16 A up to 60 °C without fan, 20 A with fan |
| Maximum output delay | 1 AC cycle for each switching direction with resistive load |
| Maximum lamp load | 100 W |
| Maximum switching frequency | Resistive: 10 Hz; inductive: 0.5 Hz; lamp: 1 Hz |
| Maximum actuator cable length | 600 m unshielded; 1,000 m shielded |
| Maximum backplane current at 5 V | 250 mA |
| Typical module power loss | 16 W |
| Permitted potential difference between groups | 500 V AC |
| Insulation strength | 4,000 V AC |
| Output short-circuit protection | 8 A, 250 V fuse per output |
| Fault indication | INTF red for fuse failure; EXTF red for missing load voltage |
| Channel indication | Green LED per output |
| Parallel output connection | Permitted for redundant control of the same load |
| Dimensions | 25 × 290 × 210 mm |
| Approximate mass | 800 g |
Frequently Asked Questions
Can I switch separate AC load circuits with 6ES7422-1FF00-0AA0?
The eight outputs are individually isolated in groups of one channel.
Will a 5 mA indicator operate within the load range of 6ES7422-1FF00-0AA0?
The permitted on-state current begins at 10 mA.
What should I inspect when the INTF LED lights on 6ES7422-1FF00-0AA0?
The red INTF indication identifies an output fuse failure.
Why is the EXTF indicator lit on 6ES7422-1FF00-0AA0?
The red EXTF indication signals that load voltage is missing.
Can I connect two outputs of 6ES7422-1FF00-0AA0 redundantly?
Redundant parallel control is possible when both outputs are connected to the same load.
Can all outputs of 6ES7422-1FF00-0AA0 carry 5 A continuously at 60 °C?
The combined output current at 60 °C is limited to 16 A without a fan module or 20 A with one.
What must I remove before changing an output fuse in 6ES7422-1FF00-0AA0?
Remove the front connector before changing a fuse.