Siemens SIMATIC S7-400 CPU 416-2 Central Processing Unit 6ES7416-2XK02-0AB0
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the CPU in a compatible S7-400 rack with the required power supply and memory card.
- Preserve the STEP 7 hardware catalog entry, MPI address and PROFIBUS network configuration.
- Back up the program, data and load-memory contents before exchanging the controller.
SIEMENS · SIMATIC S7-400
6ES7416-2XK02-0AB0 SIMATIC S7-400 CPU 416-2 Central Processing Unit
The CPU 416-2 combines separate 0.8 MB code and data work-memory areas with integrated load memory, an MPI/DP interface and a second PROFIBUS DP interface.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7416-2XK02-0AB0 |
| Product Type | S7-400 CPU 416-2 central processing unit |
| Core Function | Executes large S7-400 control programs with integrated MPI/DP and PROFIBUS DP communication |
| Application or Compatible Series | SIMATIC S7-400 controller racks engineered with STEP 7 V5.2 or later |
Exact Identification
Match 6ES7416-2XK02-0AB0 character by character and confirm the complete SIMATIC S7-400 CPU 416-2 Central Processing Unit designation.
Interface Arrangement
Confirm the installed supply, ports, field connections and required accessories before wiring the replacement.
Configuration Check
Preserve the approved engineering project, network parameters and application data used by the installed system.
Product Overview
The CPU 416-2 combines separate 0.8 MB code and data work-memory areas with integrated load memory, an MPI/DP interface and a second PROFIBUS DP interface.
The controller provides 0.8 MB for code and 0.8 MB for data in its integrated work memory. The first interface supports MPI/DP communication and the second interface provides PROFIBUS DP connectivity. Bit and word instructions execute from 0.08 microseconds for time-critical automation tasks.
Key Functions
Large S7-400 Program Memory
The controller provides 0.8 MB for code and 0.8 MB for data in its integrated work memory.
Dual PROFIBUS-Capable Interfaces
The first interface supports MPI/DP communication and the second interface provides PROFIBUS DP connectivity.
Fast Logic Execution
Bit and word instructions execute from 0.08 microseconds for time-critical automation tasks.
Official Specifications
| Firmware Version | V3.1 |
|---|---|
| Engineering Baseline | STEP 7 V5.2 or later |
| Code Work Memory | 0.8 MB |
| Data Work Memory | 0.8 MB |
| Integrated Load RAM | 256 KB |
| Maximum FLASH Load Memory | 64 MB using a memory card |
| Maximum RAM Load Memory | 64 MB using a memory card |
| Battery Backup | All data supported |
| Minimum Bit and Word Operation Time | 0.08 µs |
| Minimum Integer-Math Operation Time | 0.48 µs |
| Maximum Data Blocks | 4095, with DB 0 reserved |
| Maximum Data Block Size | 64 KB |
| Maximum Function Blocks | 2048 |
| Maximum Functions | 2048 |
| Total I/O Address Area | 16 KB inputs and 16 KB outputs |
| Adjustable Process Image | Up to 16 KB inputs and 16 KB outputs |
| Available S7 Counters and Timers | 512 counters and 512 timers |
| Maximum Consistent Data | 244 bytes |
Frequently Asked Questions
Which STEP 7 baseline is required for 6ES7416-2XK02-0AB0?
Use STEP 7 V5.2 or a later compatible engineering release.
How is the work memory divided in 6ES7416-2XK02-0AB0?
The controller provides 0.8 MB for code and 0.8 MB for data.
What firmware level identifies 6ES7416-2XK02-0AB0?
The listed firmware version is V3.1.
Can 6ES7416-2XK02-0AB0 use both FLASH and RAM memory cards?
Yes; load memory can be expanded to 64 MB with either supported memory-card type.
How fast are basic bit and word operations on 6ES7416-2XK02-0AB0?
The minimum execution time for those operations is 0.08 microseconds.
How much process image can I configure on 6ES7416-2XK02-0AB0?
The adjustable process image supports up to 16 KB of inputs and 16 KB of outputs.
What should I back up before replacing 6ES7416-2XK02-0AB0?
Save the STEP 7 project, program, hardware configuration, memory-card contents and all MPI and PROFIBUS parameters.