Siemens SIMATIC S7-400 6ES7412-2XG00-0AB0 CPU 412-2
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Use the CPU only in a compatible SIMATIC S7-400 rack with a suitable system power supply.
- Engineer the exact XG00 hardware generation from STEP 7 V5.2 or a later release that retains support for it.
- Match the installed CPU firmware because Siemens communication-processor compatibility tables distinguish V3.0, V3.1 and V3.1.3 states.
- Preserve the X1 MPI/DP and X2 PROFIBUS DP operating modes, addresses and transmission rates.
- Keep each PROFIBUS segment at or below the 12 Mbit/s interface limit.
- Confirm the FLASH or RAM memory-card type and do not exceed 64 MB.
- Check the 5 V backplane current budget against the typical 1.5 A and maximum 1.6 A CPU demand.
- Verify every attached communication processor against the exact CPU firmware using the applicable Siemens compatibility table.
- Do not transfer performance or memory values from the XG04, XJ05 or XK07 successors to this XG00 execution.
- Restore and test the archived project, DP configuration and process-image assignments before returning the system to service.
Siemens · SIMATIC S7-400
6ES7412-2XG00-0AB0 CPU 412-2 Central Processing Unit
Siemens 6ES7412-2XG00-0AB0 is a SIMATIC S7-400 CPU 412-2 central processing unit with separate 72 KB code and 72 KB data work-memory areas. It provides one integrated MPI/PROFIBUS DP interface and one additional integrated PROFIBUS DP interface for controller, engineering and distributed-I/O communication. This XG00 hardware generation is specified with firmware V3.1 and engineering from STEP 7 V5.2. Later CPU 412-2 order numbers such as XG04, XJ05 and XK07 belong to different firmware and performance generations, so replacement requires a project, memory-card, communication and rack-power review rather than suffix substitution.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7412-2XG00-0AB0 |
| Product Type | Modular Programmable Logic Controller CPU |
| Core Function | Executes the automation program and coordinates central and distributed process I/O |
| Application or Compatible Series | SIMATIC S7-400 automation systems |
Exact CPU Generation
Match the complete XG00 suffix and firmware V3.1 because later CPU 412-2 revisions have different order numbers and resources.
Project and Memory Baseline
Archive the STEP 7 project and record the installed FLASH or RAM memory card before removing the CPU.
Network and Rack Check
Record both interface roles, PROFIBUS addresses, baud rates, slave configuration and S7-400 rack power loading.
Product Overview
Siemens 6ES7412-2XG00-0AB0 is a SIMATIC S7-400 CPU 412-2 central processing unit with separate 72 KB code and 72 KB data work-memory areas. It provides one integrated MPI/PROFIBUS DP interface and one additional integrated PROFIBUS DP interface for controller, engineering and distributed-I/O communication. This XG00 hardware generation is specified with firmware V3.1 and engineering from STEP 7 V5.2. Later CPU 412-2 order numbers such as XG04, XJ05 and XK07 belong to different firmware and performance generations, so replacement requires a project, memory-card, communication and rack-power review rather than suffix substitution.
Combines an MPI/DP port with a second dedicated DP port, both using isolated RS485 physical layers. Provides independent 72 KB work-memory areas for code and data plus integrated RAM load memory. Executes bit, word and fixed-point operations from 0.2 microseconds and floating-point operations from 0.6 microseconds.
Key Functions
Dual Integrated PROFIBUS Interfaces
Combines an MPI/DP port with a second dedicated DP port, both using isolated RS485 physical layers.
Separated Program and Data Memory
Provides independent 72 KB work-memory areas for code and data plus integrated RAM load memory.
Deterministic S7-400 Processing
Executes bit, word and fixed-point operations from 0.2 microseconds and floating-point operations from 0.6 microseconds.
Official Specifications
| Firmware Version | V3.1 |
|---|---|
| Engineering Software | STEP 7 V5.2 or higher |
| Integrated Work Memory | 72 KB for code and 72 KB for data |
| Integrated Load Memory | 256 KB RAM |
| Memory Card Expansion | Up to 64 MB FLASH or up to 64 MB RAM |
| Bit, Word and Fixed-Point Operation Time | Minimum 0.2 microseconds |
| Floating-Point Operation Time | Minimum 0.6 microseconds |
| Available S7 Counters and Timers | 256 counters and 256 timers |
| Total I/O Address Area | 4 KB inputs and 4 KB outputs |
| Configurable Process Image | Up to 4 KB inputs and 4 KB outputs; preset 128 bytes each |
| Partial Process Images | Maximum 8 |
| Maximum Consistent Data | 244 bytes |
| Digital Channel Capacity | 32768 inputs and 32768 outputs |
| Analog Channel Capacity | 2048 inputs and 2048 outputs |
| Integrated Communication Ports | One MPI/DP and one PROFIBUS DP interface; isolated RS485; up to 12 Mbit/s |
| S7 Connection Resources | 16 across integrated interfaces and communication processors |
| Backplane Current at 5 V DC | Typically 1.5 A; maximum 1.6 A |
| Power Loss | Typically 7.5 W |
| Mounting Size and Slot Requirement | 25 x 290 x 219 mm; one S7-400 slot |
| Approximate Weight | 0.72 kg |
Frequently Asked Questions
Which STEP 7 version should I use for 6ES7412-2XG00-0AB0?
Use STEP 7 V5.2 or a later release that still supports this CPU generation and firmware.
How much work memory is available in 6ES7412-2XG00-0AB0?
The CPU provides 72 KB for code and a separate 72 KB area for data.
Which network interfaces are built into 6ES7412-2XG00-0AB0?
The first isolated RS485 interface can operate as MPI or PROFIBUS DP, while the second isolated RS485 interface is for PROFIBUS DP.
Can I replace 6ES7412-2XG00-0AB0 directly with an XG04, XJ05 or XK07 CPU?
No, treat each later suffix as a different hardware and firmware generation and validate the project, memory card, interfaces and supported functions before migration.
Which memory card capacity can I use with 6ES7412-2XG00-0AB0?
The load memory can be expanded with a FLASH or RAM memory card up to 64 MB.
What rack-power values should I check for 6ES7412-2XG00-0AB0?
Allow for approximately 1.5 A and no more than 1.6 A from the 5 V S7-400 backplane, with typical power loss of 7.5 W.
What should I save before replacing 6ES7412-2XG00-0AB0?
Save the complete STEP 7 project and record the firmware, memory-card type, rack slot, interface modes, bus addresses, transmission rates and connected DP stations.