- Use the rack and power-supply arrangement intended for redundant operation.
- Budget both backplane output currents and provide the required 200 mA base load on 5 V.
- Reserve two rack slots and connect the protective conductor.
- Match the optional backup batteries and the controller backup settings to the installation.
6ES7407-0KR00-0AA0 S7-400 PS 407 10 A Redundant Power Supply
A redundant-use PS 407 supply with universal AC/DC mains input, 5 V/10 A and 24 V/1 A backplane outputs, occupying two rack slots.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7407-0KR00-0AA0 |
| Product Type | Rack power-supply module |
| Core Function | Supplies the rack backplane |
| Application | S7-400 redundant power arrangements |
Redundant rack supply
Two suitable redundant power-supply modules support a rack power arrangement intended to improve controller availability.
Two backplane voltages
The module supplies up to 10 A at 5 V DC and up to 1 A at 24 V DC to the rack backplane.
Mains and backup support
A 20 ms mains-buffering time and an optional two-battery arrangement support the controller’s power and backup requirements.
Product Overview
6ES7407-0KR00-0AA0 supplies the S7-400 backplane and is designed for redundant use.
A compatible two-supply rack arrangement can maintain power when one supply is unavailable, while the module provides mains buffering, output short-circuit protection and optional battery backup.
Key Functions
Redundant rack supply
Two suitable redundant power-supply modules support a rack power arrangement intended to improve controller availability.
Two backplane voltages
The module supplies up to 10 A at 5 V DC and up to 1 A at 24 V DC to the rack backplane.
Mains and backup support
A 20 ms mains-buffering time and an optional two-battery arrangement support the controller’s power and backup requirements.
Official Specifications
| AC input range | 85–264 V AC; nominal 120/230 V AC |
|---|---|
| DC input range | 88–300 V DC; nominal 120/230 V DC |
| AC frequency | 47–63 Hz; nominal 50/60 Hz |
| Rated AC input current | 0.9 A at 120 V; 0.5 A at 230 V |
| Rated DC input current | 1 A at 110 V; 0.5 A at 230 V |
| Maximum inrush current | 18 A |
| 5 V backplane output | Maximum 10 A; minimum base load 200 mA |
| 24 V backplane output | Maximum 1 A; no-load operation permitted |
| Mains buffering | 20 ms |
| Output protection | Short-circuit protected |
| Typical active input power | 97.5 W |
| Typical power loss | 22.4 W |
| Optional backup batteries | 2 × lithium AA, 3.6 V / 1.9 Ah |
| Rack occupation | 2 slots |
| Electrical isolation | Primary to secondary |
| Protection class | Class I with protective conductor |
| Connection conductors | 3 × 1.5 mm² solid or ferruled stranded; cable diameter 3–9 mm |
| Dimensions | 50 × 290 × 217 mm |
| Approximate weight | 1360 g |
Frequently Asked Questions
Can 6ES7407-0KR00-0AA0 accept either an AC or DC mains source?
The module accepts 85–264 V AC or 88–300 V DC within its specified universal-input ranges.
How many 6ES7407-0KR00-0AA0 modules are used in a redundant rack arrangement?
A redundant arrangement uses two suitable redundant power-supply modules in a compatible rack.
Does the 5 V output of 6ES7407-0KR00-0AA0 require a minimum load?
The 5 V backplane output requires a base load of 200 mA.
What current can I budget on the 24 V backplane output of 6ES7407-0KR00-0AA0?
The 24 V DC backplane output is rated for a maximum of 1 A.
How much rack space should I reserve for 6ES7407-0KR00-0AA0?
Reserve two rack slots for the 50 mm-wide power-supply module.
Which batteries are specified as an option for 6ES7407-0KR00-0AA0?
The optional backup arrangement uses two lithium AA batteries rated at 3.6 V and 1.9 Ah.
What conductor size is specified at the mains connector of 6ES7407-0KR00-0AA0?
Use three 1.5 mm² solid or ferruled stranded conductors with a cable outside diameter of 3–9 mm.