SIMATIC S7-400

6ES7407-0KR00-0AA0 S7-400 PS 407 10 A Redundant Power Supply

A redundant-use PS 407 power supply with universal AC/DC mains input, 5 V/10 A and 24 V/1 A backplane outputs, occupying two rack slots.

Ad Primum Aspectum

Nota Siemens
Modellum 6ES7407-0KR00-0AA0
Typus Producti Modulo de alimentatione electrica pro catena
Functio principalis Supplies the rack backplane
Applicatio S7-400 redundant power arrangements

Redundant rack supply

Two suitable redundant power-supply modules support a rack power arrangement intended to improve controller availability.

Two backplane voltages

The module supplies up to 10 A at 5 V DC and up to 1 A at 24 V DC to the rack backplane.

Mains and backup support

A 20 ms mains-buffering time and an optional two-battery arrangement support the controller’s power and backup requirements.

Product Overview

6ES7407-0KR00-0AA0 supplies the S7-400 backplane and is designed for redundant use.

A compatible two-supply rack arrangement can maintain power when one supply is unavailable, while the module provides mains buffering, output short-circuit protection and optional battery backup.

Focus ordinandi: Match the redundant-capable rack, two-slot space, universal input supply and the 5 V and 24 V backplane load budgets.
Key Functions

Redundant rack supply

Two suitable redundant power-supply modules support a rack power arrangement intended to improve controller availability.

Two backplane voltages

The module supplies up to 10 A at 5 V DC and up to 1 A at 24 V DC to the rack backplane.

Mains and backup support

A 20 ms mains-buffering time and an optional two-battery arrangement support the controller’s power and backup requirements.

Official Specifications
Intervalum Tensionis Alternantis Ingressus 85–264 V AC; nominal 120/230 V AC
Intervalum Tensionis Directae Ingressus 88–300 V DC; nominal 120/230 V DC
AC Frequens 47–63 Hz; nominalis 50/60 Hz
Rated AC input current 0.9 A at 120 V; 0.5 A at 230 V
Rated DC input current 1 A at 110 V; 0.5 A at 230 V
Maxima Currus Inrumpens 18 A
5 V Backplane Output Maximum 10 A; minimum base load 200 mA
24 V backplane output Maximum 1 A; no-load operation permitted
Custodia Rete Electrici 20 ms
Tutela Exitus Tutelatus contra curtum circuitum
Potenza di ingresso attiva tipica 97.5 W
Perditio potentiæ typica 22.4 W
Batteriae auxiliares optionales 2 × lithium AA, 3.6 V / 1.9 Ah
Rack occupation 2 loca
Isolatio Electrica Primarius ad secundarium
Classis Protectionis Classis I cum conductore protectivo
Connection conductors 3 × 1.5 mm² solid or ferruled stranded; cable diameter 3–9 mm
Dimensiones 50 × 290 × 217 mm
Pondus Approximatum 1360 g
Quaestiones Frequenter Rogatae

Can 6ES7407-0KR00-0AA0 accept either an AC or DC mains source?

The module accepts 85–264 V AC or 88–300 V DC within its specified universal-input ranges.

How many 6ES7407-0KR00-0AA0 modules are used in a redundant rack arrangement?

A redundant arrangement uses two suitable redundant power-supply modules in a compatible rack.

Does the 5 V output of 6ES7407-0KR00-0AA0 require a minimum load?

The 5 V backplane output requires a base load of 200 mA.

What current can I budget on the 24 V backplane output of 6ES7407-0KR00-0AA0?

The 24 V DC backplane output is rated for a maximum of 1 A.

How much rack space should I reserve for 6ES7407-0KR00-0AA0?

Reserve two rack slots for the 50 mm-wide power-supply module.

Which batteries are specified as an option for 6ES7407-0KR00-0AA0?

The optional backup arrangement uses two lithium AA batteries rated at 3.6 V and 1.9 Ah.

What conductor size is specified at the mains connector of 6ES7407-0KR00-0AA0?

Use three 1.5 mm² solid or ferruled stranded conductors with a cable outside diameter of 3–9 mm.

Compatibility & Ordering Notes
Before ordering 6ES7407-0KR00-0AA0: Match the redundant-capable rack, two-slot space, universal input supply and the 5 V and 24 V backplane load budgets.

Antequam Installatio

  • Use the rack and power-supply arrangement intended for redundant operation.
  • Budget both backplane output currents and provide the required 200 mA base load on 5 V.
  • Reserve two rack slots and connect the protective conductor.
  • Match the optional backup batteries and the controller backup settings to the installation.
Hot Selling Models
ZAS/10s/1Uz 650115
1250/5
BWU1939
LNH2080T
ET200 6ES7195-7HD10-0XA0
3WL9111-0AT21-0AA0
OJ100-F6-E23
7PA1013-6EA
7PA1033-6ED
7PA1030-6EA
ADVU-40-200-APA
7000-17121-2911000
VS-M12MS-8CON-RJ45-940
GBK0801003F
ADN-40-80-A-PPS-A

Accipe Aestimationem Gratuitam

Legatus noster te mox contactabit.
Epistula electronica
Nomen
Nomen societatis
Nuntius
0/1000
epistula electronica ad Summum ire

Evolo Automation non est distributor autorizatus nisi aliter specificatum, nec representans, nec affinis fabricantis huius producti. Omnia signa propria et documenta sunt proprietatis suorum dominorum respective et data sunt ad identificationem et informationem.