Siemens 6ES7334-0CE01-0AA0 SIMATIC S7-300 SM 334 Analog Input and Output Module
Manufacturer: Siemens
Condition: Brand New
Lead Time: In Stock
Origin: Germany
Warranty: 12 Months
Email: [email protected]
whatsApp: +86-18150117685
- Overview
- Hot Selling Models
- Recommended Products
Overview
- Keep this 8-bit 0CE01 version distinct from the 12-bit 0KE00 temperature-capable module.
- Provide four-wire current transducers where current measurement is required.
- Check the voltage and current output load limits before connecting actuators.
- Use an active backplane if removal and insertion during station operation is required.
SIEMENS SIMATIC S7-300
6ES7334-0CE01-0AA0 SIMATIC S7-300 SM 334 Analog Input and Output Module
Compact non-isolated analog module with four inputs and two outputs for voltage or current signals, using a 20-pin front connector.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7334-0CE01-0AA0 |
| Product Type | SM 334 analog I/O module |
| Core Function | Analog signal acquisition and output |
| Application | SIMATIC S7-300 and ET 200M stations |
Mixed analog channels
Four analog inputs and two analog outputs in one module.
Voltage and current
Use 0–10 V or 0–20 mA signal ranges.
Active backplane
Removal and insertion are possible with an active backplane bus.
Product Overview
6ES7334-0CE01-0AA0 combines four analog inputs and two analog outputs in the SIMATIC S7-300 SM 334 module for compact voltage and current signal handling.
Inputs and outputs provide 8-bit resolution including overrange, with a maximum input cycle time of 5 ms and a 20-pin front connection.
Key Functions
Mixed-signal processing
The four inputs and two outputs support 0–10 V and 0–20 mA signals in a single non-isolated module.
Transducer interfacing
Voltage sensors and four-wire current transducers can be connected, while two-wire current transducers are not supported.
Controlled analog output
Voltage outputs include short-circuit protection, and the analog output conversion time is 500 µs per channel.
Official Specifications
| Analog channel capacity | 4 inputs and 2 outputs |
|---|---|
| Input and output signal ranges | 0–10 V or 0–20 mA |
| Input resistance | 100 kΩ for 0–10 V; 50 Ω for 0–20 mA |
| Input and output resolution | 8 bits including overrange |
| Maximum input cycle time | 5 ms for all channels |
| Output conversion time | 500 µs per channel |
| Output settling time | 0.3 ms for resistive or inductive loads; 3 ms for capacitive loads |
| Voltage-output load limits | Minimum 5 kΩ; maximum capacitance 1 µF |
| Current-output load limits | Maximum 300 Ω; maximum inductance 1 mH |
| Voltage-output short-circuit current | 11 mA maximum |
| Maximum current-output no-load voltage | 15 V |
| Rated load supply | 24 V DC |
| Maximum no-load supply current | 110 mA from L+ |
| Maximum backplane current | 55 mA at 5 V DC |
| Typical power loss | 3 W |
| Shielded signal cable length | 200 m maximum |
| Front connector | 20-pin |
| Dimensions (W × H × D) | 40 × 125 × 117 mm |
Frequently Asked Questions
Can I connect voltage and current instruments to 6ES7334-0CE01-0AA0?
The analog channels support 0–10 V and 0–20 mA signal ranges.
Does 6ES7334-0CE01-0AA0 support Voltage and current for mobile equipment?
Thermocouple, resistance thermometer and resistance measurement are not supported by this version.
Can I use a two-wire current transmitter with 6ES7334-0CE01-0AA0?
Current measurement supports four-wire transducers rather than two-wire transducers.
Which front connector should I order for 6ES7334-0CE01-0AA0?
A 20-pin S7-300 front connector is required.
What output load can I connect to 6ES7334-0CE01-0AA0?
Voltage loads must be at least 5 kΩ and current loads must not exceed 300 Ω.
Can I exchange 6ES7334-0CE01-0AA0 without interrupting the active backplane?
Removal and insertion are possible when the station uses an active backplane bus.
Will 6ES7334-0CE01-0AA0 generate diagnostic interrupts for channel faults?
This module provides neither alarms nor a diagnostic function.