- Use with the supported S7-22X CPU family.
- Distinguish this relay-output variant from transistor-output EM 223 modules.
- Wire the input common groups of eight and relay output groups of four correctly.
- Keep each output within its switching rating and each output group within 8 A.
- Provide external short-circuit protection and suitable suppression for the connected load circuits.
6ES7223-1PL22-0XA0 S7-200 EM 223 16DI 16 Relay Output Module
An EM 223 expansion with sixteen 24 V DC sink/source inputs and sixteen relay outputs rated at 2 A per channel.
At a Glance
| Brand | Siemens |
|---|---|
| Model | 6ES7223-1PL22-0XA0 |
| Product Type | EM 223 digital mixed I/O expansion |
| Core Function | Adds discrete sensing and relay switching |
| Application | SIMATIC S7-22X CPUs |
Sixteen DC inputs
Sink/source input wiring accepts nominal 24 V DC field signals.
Sixteen relay outputs
Relay contacts switch the external load circuits in groups of four.
Plug-in I/O terminals
Removable terminal connections assist field wiring and module servicing.
Product Overview
6ES7223-1PL22-0XA0 adds sixteen digital inputs and sixteen relay outputs to a compatible S7-22X CPU in the SIMATIC S7-200 family.
The input channels use 24 V DC sink/source signals, while the relay outputs switch external AC or DC loads and require the load circuit to provide the appropriate short-circuit protection.
Key Functions
Sink/source digital input expansion
Sixteen 24 V DC inputs accept sinking or sourcing field wiring, with optocoupler isolation in groups of eight channels.
Relay switching for external loads
Sixteen relay outputs provide 2 A rated switching per channel and isolation in groups of four, with an 8 A maximum group-current limit.
Serviceable field connections
Plug-in I/O terminals allow the field connections to be removed from the module, and the combined input/output layout reduces the number of separate expansion modules needed.
Official Specifications
| Input Channel Arrangement | 16 digital inputs, 24 V DC, sink/source |
|---|---|
| Relay Output Arrangement | 16 relay outputs, rated 2 A per channel |
| Switched DC Load Range | 5–30 V DC |
| Switched AC Load Range | 5–250 V AC |
| Input Signal Thresholds | Signal 0: 0–5 V; signal 1: 15–30 V DC |
| Typical Input Current | 4 mA at signal 1 |
| Maximum Input On-delay | 4.5 ms |
| Maximum Backplane Current | 150 mA from the 5 V DC bus |
| Relay Coil Current | 9 mA maximum per energized output |
| Typical Power Loss | 6 W |
| Maximum Output Group Current | 8 A |
| Relay Mechanical Endurance | 10,000,000 operations maximum |
| Relay Endurance at Rated Load | 100,000 operations |
| Lamp-load Switching Limits | 30 W DC; 200 W AC |
| Maximum Cable Lengths | 500 m shielded; 150 m unshielded |
| Input and Output Isolation Groups | Inputs: optocouplers in groups of 8; outputs: relays in groups of 4 |
| Isolation Test Voltage | 500 V AC |
| I/O Terminal Construction | Plug-in terminals |
| Dimensions (W × H × D) | 137.5 × 80 × 62 mm |
| Approximate Weight | 400 g |
Frequently Asked Questions
Can 6ES7223-1PL22-0XA0 be used as an expansion for an S7-21X CPU?
The module is intended only for S7-22X CPUs.
Does 6ES7223-1PL22-0XA0 provide relay contacts or transistor outputs?
The output section uses sixteen relay channels rather than transistor outputs.
How should I group the sensor commons for 6ES7223-1PL22-0XA0?
The digital inputs are isolated in groups of eight channels, so the wiring must follow the corresponding input common groups.
Can four relay channels on 6ES7223-1PL22-0XA0 each switch a 2 A load?
A four-channel relay group must remain within its 8 A total current limit.
What input voltage will reliably register as signal 1 on 6ES7223-1PL22-0XA0?
An input voltage from 15 V to 30 V DC is recognized as signal 1.
Does 6ES7223-1PL22-0XA0 protect the relay load circuit against a short circuit?
The relay outputs have no integrated short-circuit protection, so the external load circuit must provide suitable protection.
Can I remove the field terminals separately when servicing 6ES7223-1PL22-0XA0?
The I/O terminal connections are plug-in assemblies and can be removed separately from the module.